background image

36 

19.2

 

SSL 

The super silenced unit (with SSL accessory) is provided not only with the thermo-acoustic shells on compressors but also with a 

special diffuser installed on the fan. The diffuser structure improves the air flow efficiency and allows a fan speed reduction, 

lowering the acoustic pressure by up to 7,2 dB(A) and energy consumption by up to 27% with unchanged airflow. That could lead 

to a saving up of a lot of money in energy costs per fan per year. Alternatively, you could make use of the greater efficiency to 

boost air performance by up to 9% with comparable energy consumption. 

For more details about the power sound, you can see the technical data listed in paragraph 

Errore. L'origine riferimento non è 

stata trovata.

20

 

OPERATING LIMITS 

20.1

 

EVAPORATOR WATER FLOW RATE 

The nominal water flow rate is referred to a ∆T equal to 5°C, between the evaporator’s inlet a

nd outlet temperatures. The allowed 

maximum flow rate is corresponding to ∆T=3°C. Higher values may produce too high pressure drops. The allowed minimum water 

flow rate is corresponding to ∆T=8°C. Insufficient values

 of water flow may produce too low evaporating temperatures according 

to the operating status with the intervention of safety devices which would stop the unit and, in some particular cases, the water 

can freeze in the evaporator coil which can breakdown the refrigeration circuit  or causes the  increasing  of the condensing 

pressure with the shutdown risk of the appliance and the compressor could be damaged. 

We enclosed below a most accurate table showing the minimum water flow that should be ensured for the plate heat exchanger 

in order to have the proper operation of unit as a function of the model (

note:

 the water flow switch is used for preventing the 

freezing sensor from failure in the case of insufficient water flow but it does not ensure the minimum flow rate required in order 

the unit can work properly). 

Models 

i-HP

0125 

0135 

0250/0250F 

0260 

0270 

Cooling capacity for reference [kW] 

21,02 

26,90 

36,21 

43,00 

53,60 

Minimum water flow rate that to ensure [L/s] 

0,63 

0,80 

1,08 

1,29 

1,59 

As a first approach, and in the absence of other detection systems, the proper flow rate for getting the best performance from 

your unit can be found at maximum speed of the circulator, using the pressure gauges for controlling the pressure difference 

between the return and the delivery water on the outside water connections of the unit and make sure that such value is equal or 

less than the static pressure indicated on the curves shown in paragraph 15 for the respective models and if it’s necessary change 

the settings (for the related circulator) that are reported in the control manual. 

20.2

 

COLD WATER TEMPERATURE (SUMMER OPERATION) 

The minimum temperature that is allowed at the evaporator’s outlet is 5°C:  for lowest  temperatures  the unit should undergo 

some necessaries structural modifications and different setting parameters of the controller with micro-processor.  In this case 

please  contact our company for the feasibility study and evaluation of changes to be made according to your requests. The 

maximum temperature that can be maintained at the outlet of the evaporator is 25°C. Higher temperatures (up to a maximum of 

40°C) can anyway be tolerated during transitions and start-up phases of the system. 

20.3

 

HOT WATER TEMPERATURE (WINTER OPERATION) 

Once the system is working at the right temperature, the inlet hot water temperature should not be lower than 25°C; the lowest 

values that are not related to transitional or start-up stages may cause system’s malfunction and possible compressor 

breakdowns. The maximum outlet water temperature should not exceed 60°C. At this temperature, the power consumption and 

performance in terms of C.O.P. are enhanced if the outdoor temperature is higher than 5°C, even if the unit is still able to work up 

to the limit of -15°C (-25°C for versions with injection). 

For higher temperatures than those pointed out, especially if have a concomitant with the reduction of the water flow rate, it may 

cause abnormalities to the normal operating of the unit, or the safety devices act in critical cases. 
The maximum power consumption of the heat pump alone will take place during the operation with outlet water temperature of 

60°C and outdoor temperature of -15°C(-25°C for versions with injection) 

in KW

1

2

1,5

2,5

-27%

in dB(A)

75

70

80

85

90

-7,2 dB(A)

AxiTop Diffuser 

Less energy consumption at 

constant air volume 

Reduced noise at equal at 

constant volume 

Summary of Contents for HPE 35

Page 1: ...TECHNICAL INFORMATION HPE 25 70 HPE LT 25 50 INVERTER Air water inverter heat pumps with axial fans and steam injection versions HPE 25 70 HPE LT 25 50 INVERTER...

Page 2: ...m the application of Directive 2014 68 UE Reference to Art I paragraph 2 point f L attrezzatura a pressione rientra nella CAT I L unit quindi esente dall applicazione della normativa PED 2014 68 UE Ri...

Page 3: ...3 LOCATION AND MINIMUM TECHNICAL CLEARANCES 14 7 4 DIMENSIONS 15 7 5 HYDRAULIC CONNECTIONS 15 7 5 1 Characteristics of water of the plant circuit 16 7 5 2 Hydraulic circuit type 16 7 5 3 Handbook 17...

Page 4: ...D PRESSURE OF THE UNIT WITH INTEGRATED CIRCULATOR 32 16 CIRCULATOR S CURVES 33 16 1 MODELS HPE 25 35 33 16 2 MODEL HPE 50 50F 33 16 3 MODEL HPE 60 34 16 4 MOD HPE 60 HPE 70 34 16 5 CIRCULATOR CHARACTE...

Page 5: ...g or transcription errors The customer must keep any updated copy of the manual or parts of it delivered by the manufacturer as an attachment to this manual The company is available to give any detail...

Page 6: ...ce s health and safety including 89 391 CEE 89 686 CEE 89 655 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such norms and ensure that workers to respect them It...

Page 7: ...or each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator The vapors are heavier than air and can cause suffocation by re...

Page 8: ...diameter is 7 94 mm the thickness of the aluminium fins is 0 12 mm The pipes are mechanically expanded into the aluminium fins in order to improve the heat transfer coefficient The geometry of this he...

Page 9: ...gy provide maximum efficiency regarding the standard units with scroll compressors The EVI technology consists of injecting the refrigerant vapour at the intermediate stage of the compression process...

Page 10: ...which identify the sizes versions and factory mounted accessories no 1 fixed digits equal to 0 for now it is not used 0110516 CT1 TA IV CI KA GI FAN SIL TR 00 MC FATHER CODE SIZE VERSION 0110516 CT T...

Page 11: ...Module not present 1 GI Module present 2 Modbus communication protocol 4 3 Modbus communication protocol and GI module present 0 DC fan 0 Not silenced 1 Silenced 2 Super silenced 0 Coil without treatm...

Page 12: ...provides thermo acoustic insulators on compressors 2 The super silenced unit with SSL accessory provides thermo acoustic insulators on compressors and a special diffuser installed on the fan which re...

Page 13: ...this manual can create dangerous situations After receiving the unit immediately check its integrity The unit left the factory in perfect condition any eventual damage has to be questioned to the car...

Page 14: ...CLEARANCES All i HP models are designed for outdoor installations any cover over the unit or locating near trees even if they partially cover the unit has to be avoided in order to allow the air recir...

Page 15: ...Make sure that when designing the pipe length and diameter do not exceed the maximum head loss on the plant side please see the technical data available head pressure WARNING An air vent valve should...

Page 16: ...h lack of washing of the system or lack tampering of the Y filter the company reserves the right not to pass the replacement of the component as a guarantee 7 5 1 Characteristics of water of the plant...

Page 17: ...ter on the charging topping up pipe must be suitably pre filtered from any impurities and suspended particles Make sure that you have installed a cartridge filter removable WARNING Before beginning th...

Page 18: ...CIRCULATOR ON BOARD UNIT M AXIAL FAN PV PRESSURE CHECK VALVE CP CAPILLARY SE OUTDOOR AIR TEMPERATURE SENSOR V ON OFF VALVE WITH SOLENOID 7 6 2 Refrigerant circuit of HPE 50 model EEV ELECTRONIC EXPANS...

Page 19: ...VERTER COMPRESSOR P CIRCULATOR ON BOARD UNIT M AXIAL FAN PV PRESSURE CHECK VALVE 7 6 4 Refrigerant circuit of HPE 50F model EEV ELECTRONIC EXPANSION VALVE NRV NO RETURN VALVE ST COMPRESSOR INLET TEMPE...

Page 20: ...TEMPERATURE INJP INJECTION PRESSURE TRANSDUCER INJ INJECTION VALVE 7 7 ELECTRICAL CONNECTIONS Check if the power supply circuit meets the unit s electric nominal data tension phases frequency reporte...

Page 21: ...not ground the unit with pipes or lightning rods A poor grounding of the unit can result in electrocution Warning Electrostatic discharges can damage the electronic components before performing any w...

Page 22: ...lectric box is opened i HP 0125 i HP 0135 i HP 0250F i HP 0250 On board terminal block and user s terminal block Support boards Transformer Driver board one for each inverter compressor Disconnecting...

Page 23: ...Ph N PE 400V 50Hz The power cables should be brought inside the electrical panel of the unit and connected to the disconnecting switch inside the electric panel itself in the bottom at the left as sho...

Page 24: ...tput 230Vac 50Hz 5A resistive 1A inductive 1 2 Secondary circulator GNDR Serial communication Modbus ground reference connection terminal for remote supervision R Serial communication Modbus signal co...

Page 25: ...l indications on unit labels are respected Check if all power cables are properly connected and all terminals are tightly fixed Check if the electrical connections are performed according to the norms...

Page 26: ...regarding the limits set out in Paragraph 20 4 Before you turn the unit on after a long off period make sure that the temperature of the mixture of water and glycol is higher than or at least equal t...

Page 27: ...to direct the water jet perpendicular to the surface of the condenser for not to bend the aluminum fins Avoid hitting the condenser with the water hose It is recommended not to place your thumb on th...

Page 28: ...ion 12 1 Residual risks In this paragraph we point out the most common situations that could give rise to risks that cannot be eliminated by the manufacturer during the design phase of the project Ris...

Page 29: ...98 1 97 Load losses user s side heat exchanger 4 kPa 33 46 28 Energetic class Water temp 35 C 55 C Classe A A A A A A Compressor Type Scroll DC Inverter Scroll DC Inverter Scroll DC Inverter Rfrigeran...

Page 30: ...ger 4 kPa 27 74 25 Energetic class Water temp 35 C 55 C Class A A A A A A Compressor Type Scroll DC Inverter Scroll ON OFF Scroll DC Inverter Scroll DC Inverter Rfrigerant oil type FVC68D FVC68D FVC68...

Page 31: ...W W 3 98 4 17 3 90 Water flow rate 1 L s 1 00 1 01 1 36 1 37 1 73 1 74 Load losses user s side heat exchanger 1 kPa 32 37 20 Heating Heating capacity 3 kW 24 15 24 02 32 50 32 36 47 78 47 58 Power inp...

Page 32: ...in apex 1 2 3 and 4 refer to the instantaneous power according to EN 14511 The declared data stated in the apex 6 is determined according to the UNI EN 14825 WARNING The minimum temperature allowed fo...

Page 33: ...circulator with the possibility of choice between constant P and variable P 16 2 MODEL HPE 50 50F Configuration with integrated circulator control via 0 10 volt analogic signal Configuration with auto...

Page 34: ...0 23 Because of the circulators have got similar prevalence curves to those integrated please refer to Paragraph 15 for plant designing 17 HEAD LOSS CURVES OF THE HYDRONIC CIRCUIT We obtain the press...

Page 35: ...1L s we obtaine 1 4kPa valve head loss 30kPa hydronic circuit head loss 34 9 kPa total internal head loss 19 ACCESSORIES TO REDUCE THE NOISE LEVEL 19 1 SL The silenced unit with SL accessory is provid...

Page 36: ...on systems the proper flow rate for getting the best performance from your unit can be found at maximum speed of the circulator using the pressure gauges for controlling the pressure difference betwee...

Page 37: ...30 C Water outlet temperature standard injection version Min 25 C Max 58 C 59 C Heat pump mode for sanitary hot water Ambient temperature standard injection version Min 15 25 C Max 50 38 C Ambient te...

Page 38: ...ater flow rate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation without gly...

Page 39: ...A2B ACCORRONI E G VIA ANCONA 37 60027 OSIMO AN www accorroni it a2b accorroni it...

Page 40: ...tolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d An...

Reviews: