Refer to the following table for obtaining the codes of the standard configurations  of the various models (for selecting the 

accessories, just set the corresponding variant to the desired value according to the TABLE FIELDS/VARIANTS described above): 

Model 

Description 

Standard configuration 

HPE

 25

Capacity of 25 kW without injection 

0110516#00000000000001 

HPE

 35

Capacity of 35 kW without injection 

0110516#01000000000001 

HPE

 50

Capacity of 50 kW without injection 

0110516#02000000000001 

HPE

 60

Capacity of 60 kW without injection 

0110516#03000000000001 

HPE

 50F

Capacity of 50 kW, fixed and inverter compressors, without injection 

0110516#04000000000001 

HPE

 70

Capacity of 70 kW, without injection 

0110516#05000000000001 

HPE

-LT 25

Capacity of 25 kW, with injection 

0110516#00010000000001 

HPE

-LT 35

Capacity of 35 kW, with injection 

0110516#01010000000001 

HPE

-LT 50

Capacity of 50 kW, with injection 

0110516#02010000000001 

Name of factory-fitted accessories: 

Field 

Variant 

Description 

Name 

CI 

High efficiency integrated circulator 

CI1 

CI 

Shut-off valve 

CI2 

CI 

High efficiency auto-adaptive integrated circulator 

CI3 

CI 

AC inverter pump 

CI6 

KA 

Antifreeze kit 

KA 

GI 

Management plant module 

GI 

SIL 

Silencing 

SL 

SIL 

Super silencing 

SSL 

TR 

Heat exchanger treatment finguard with 

TR2 

AC1 

Switch magnetermic 

7

 

INSTALLATION 

WARNING: All the operation described in next chapters MUST BE DONE BY TRAINED PEOPLE ONLY. Before any 

operation on the unit, be sure that the electric supply is disconnected. 

7.1

 

GENERALITY 

When installing or servicing the unit, it is necessary to strictly follow the rules listed in this manual, to conform to all the 

specifications of the labels on the unit, and to take any possible precautions. Not observing the rules reported on this manual can 

create dangerous situations. 

After receiving the unit, immediately check its integrity. The unit left the factory in perfect condition; any eventual 

damage has to be questioned to the carrier and recorded on the Delivery Note before signing it. 

The company has to be informed, within 8 days, of the extent of the damage. The Customer should prepare a written statement of 

any severe damage.  

WARNING: The i-HP units are designed for outdoor installation and for places not directly accessible to unqualified 

personnel. The place of installation must be entirely far away from fire risk. All the necessary measures should be 

adopted in order to prevent the fire risk in the place of installation. The outdoor ambient temperature shall not 

exceed 46°C. Above this value, the unit is no longer covered by the directives in force in the area of pressure 

equipment. 
WARNING:  The unit should be installed so that adequate clearance is available for maintenance and repair. The 

warranty does not cover costs related to platforms or handling equipment necessary for any maintenance. 
All maintenance and testing operations should be carried out only by QUALIFIED PERSONNEL. 

Before any operation on the unit, make sure the power supply is disconnected. 
WARNING: MOVING PARTS, RISK OF DEATH. 

Disconnect the power supply and ensure that the fan is stopped before opening the front panel. 

The top part and discharge pipes of the compressor operate at high temperatures. Be sure to let the unit to become 

cool before beginning any maintenance work. 

Be careful to the surface of the driver boards’ heatsinks which could be too hot. 

Be careful when working near condensing coils. 

The aluminum fins are very sharp and can cause serious injuries. 
After the maintenance operations, close the panels tightly with the fastening screws. 
It recommended not to remove/tamper with the safety pressure switch and its connections in order not to endanger 

its functionality as safety device. Burst risk. 

Summary of Contents for HPE 35

Page 1: ...TECHNICAL INFORMATION HPE 25 70 HPE LT 25 50 INVERTER Air water inverter heat pumps with axial fans and steam injection versions HPE 25 70 HPE LT 25 50 INVERTER...

Page 2: ...m the application of Directive 2014 68 UE Reference to Art I paragraph 2 point f L attrezzatura a pressione rientra nella CAT I L unit quindi esente dall applicazione della normativa PED 2014 68 UE Ri...

Page 3: ...3 LOCATION AND MINIMUM TECHNICAL CLEARANCES 14 7 4 DIMENSIONS 15 7 5 HYDRAULIC CONNECTIONS 15 7 5 1 Characteristics of water of the plant circuit 16 7 5 2 Hydraulic circuit type 16 7 5 3 Handbook 17...

Page 4: ...D PRESSURE OF THE UNIT WITH INTEGRATED CIRCULATOR 32 16 CIRCULATOR S CURVES 33 16 1 MODELS HPE 25 35 33 16 2 MODEL HPE 50 50F 33 16 3 MODEL HPE 60 34 16 4 MOD HPE 60 HPE 70 34 16 5 CIRCULATOR CHARACTE...

Page 5: ...g or transcription errors The customer must keep any updated copy of the manual or parts of it delivered by the manufacturer as an attachment to this manual The company is available to give any detail...

Page 6: ...ce s health and safety including 89 391 CEE 89 686 CEE 89 655 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such norms and ensure that workers to respect them It...

Page 7: ...or each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator The vapors are heavier than air and can cause suffocation by re...

Page 8: ...diameter is 7 94 mm the thickness of the aluminium fins is 0 12 mm The pipes are mechanically expanded into the aluminium fins in order to improve the heat transfer coefficient The geometry of this he...

Page 9: ...gy provide maximum efficiency regarding the standard units with scroll compressors The EVI technology consists of injecting the refrigerant vapour at the intermediate stage of the compression process...

Page 10: ...which identify the sizes versions and factory mounted accessories no 1 fixed digits equal to 0 for now it is not used 0110516 CT1 TA IV CI KA GI FAN SIL TR 00 MC FATHER CODE SIZE VERSION 0110516 CT T...

Page 11: ...Module not present 1 GI Module present 2 Modbus communication protocol 4 3 Modbus communication protocol and GI module present 0 DC fan 0 Not silenced 1 Silenced 2 Super silenced 0 Coil without treatm...

Page 12: ...provides thermo acoustic insulators on compressors 2 The super silenced unit with SSL accessory provides thermo acoustic insulators on compressors and a special diffuser installed on the fan which re...

Page 13: ...this manual can create dangerous situations After receiving the unit immediately check its integrity The unit left the factory in perfect condition any eventual damage has to be questioned to the car...

Page 14: ...CLEARANCES All i HP models are designed for outdoor installations any cover over the unit or locating near trees even if they partially cover the unit has to be avoided in order to allow the air recir...

Page 15: ...Make sure that when designing the pipe length and diameter do not exceed the maximum head loss on the plant side please see the technical data available head pressure WARNING An air vent valve should...

Page 16: ...h lack of washing of the system or lack tampering of the Y filter the company reserves the right not to pass the replacement of the component as a guarantee 7 5 1 Characteristics of water of the plant...

Page 17: ...ter on the charging topping up pipe must be suitably pre filtered from any impurities and suspended particles Make sure that you have installed a cartridge filter removable WARNING Before beginning th...

Page 18: ...CIRCULATOR ON BOARD UNIT M AXIAL FAN PV PRESSURE CHECK VALVE CP CAPILLARY SE OUTDOOR AIR TEMPERATURE SENSOR V ON OFF VALVE WITH SOLENOID 7 6 2 Refrigerant circuit of HPE 50 model EEV ELECTRONIC EXPANS...

Page 19: ...VERTER COMPRESSOR P CIRCULATOR ON BOARD UNIT M AXIAL FAN PV PRESSURE CHECK VALVE 7 6 4 Refrigerant circuit of HPE 50F model EEV ELECTRONIC EXPANSION VALVE NRV NO RETURN VALVE ST COMPRESSOR INLET TEMPE...

Page 20: ...TEMPERATURE INJP INJECTION PRESSURE TRANSDUCER INJ INJECTION VALVE 7 7 ELECTRICAL CONNECTIONS Check if the power supply circuit meets the unit s electric nominal data tension phases frequency reporte...

Page 21: ...not ground the unit with pipes or lightning rods A poor grounding of the unit can result in electrocution Warning Electrostatic discharges can damage the electronic components before performing any w...

Page 22: ...lectric box is opened i HP 0125 i HP 0135 i HP 0250F i HP 0250 On board terminal block and user s terminal block Support boards Transformer Driver board one for each inverter compressor Disconnecting...

Page 23: ...Ph N PE 400V 50Hz The power cables should be brought inside the electrical panel of the unit and connected to the disconnecting switch inside the electric panel itself in the bottom at the left as sho...

Page 24: ...tput 230Vac 50Hz 5A resistive 1A inductive 1 2 Secondary circulator GNDR Serial communication Modbus ground reference connection terminal for remote supervision R Serial communication Modbus signal co...

Page 25: ...l indications on unit labels are respected Check if all power cables are properly connected and all terminals are tightly fixed Check if the electrical connections are performed according to the norms...

Page 26: ...regarding the limits set out in Paragraph 20 4 Before you turn the unit on after a long off period make sure that the temperature of the mixture of water and glycol is higher than or at least equal t...

Page 27: ...to direct the water jet perpendicular to the surface of the condenser for not to bend the aluminum fins Avoid hitting the condenser with the water hose It is recommended not to place your thumb on th...

Page 28: ...ion 12 1 Residual risks In this paragraph we point out the most common situations that could give rise to risks that cannot be eliminated by the manufacturer during the design phase of the project Ris...

Page 29: ...98 1 97 Load losses user s side heat exchanger 4 kPa 33 46 28 Energetic class Water temp 35 C 55 C Classe A A A A A A Compressor Type Scroll DC Inverter Scroll DC Inverter Scroll DC Inverter Rfrigeran...

Page 30: ...ger 4 kPa 27 74 25 Energetic class Water temp 35 C 55 C Class A A A A A A Compressor Type Scroll DC Inverter Scroll ON OFF Scroll DC Inverter Scroll DC Inverter Rfrigerant oil type FVC68D FVC68D FVC68...

Page 31: ...W W 3 98 4 17 3 90 Water flow rate 1 L s 1 00 1 01 1 36 1 37 1 73 1 74 Load losses user s side heat exchanger 1 kPa 32 37 20 Heating Heating capacity 3 kW 24 15 24 02 32 50 32 36 47 78 47 58 Power inp...

Page 32: ...in apex 1 2 3 and 4 refer to the instantaneous power according to EN 14511 The declared data stated in the apex 6 is determined according to the UNI EN 14825 WARNING The minimum temperature allowed fo...

Page 33: ...circulator with the possibility of choice between constant P and variable P 16 2 MODEL HPE 50 50F Configuration with integrated circulator control via 0 10 volt analogic signal Configuration with auto...

Page 34: ...0 23 Because of the circulators have got similar prevalence curves to those integrated please refer to Paragraph 15 for plant designing 17 HEAD LOSS CURVES OF THE HYDRONIC CIRCUIT We obtain the press...

Page 35: ...1L s we obtaine 1 4kPa valve head loss 30kPa hydronic circuit head loss 34 9 kPa total internal head loss 19 ACCESSORIES TO REDUCE THE NOISE LEVEL 19 1 SL The silenced unit with SL accessory is provid...

Page 36: ...on systems the proper flow rate for getting the best performance from your unit can be found at maximum speed of the circulator using the pressure gauges for controlling the pressure difference betwee...

Page 37: ...30 C Water outlet temperature standard injection version Min 25 C Max 58 C 59 C Heat pump mode for sanitary hot water Ambient temperature standard injection version Min 15 25 C Max 50 38 C Ambient te...

Page 38: ...ater flow rate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation without gly...

Page 39: ...A2B ACCORRONI E G VIA ANCONA 37 60027 OSIMO AN www accorroni it a2b accorroni it...

Page 40: ...tolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d An...

Reviews: