42
Parameter
Settable values
Default values
Note
P46
Modulating pump speed selection
0 - 1
1
0 =
not modulated
1 =
automatic
60% ÷ 100%
P47
ΔT selection for pump modulation (°C)
10 ÷ 40
20
P48
Pump operation selection
0 - 1
0
0 =
intermittent
1 =
continuous
P49
Enable OEM
0 ÷ 99
0
49 =
allows reading / writing of the following parameters
P50
Not used
P51
Not used
P52
Automatic water filling selection
0 - 1
0
0 =
not present
1 = present
DO NOT CHANGE THIS VALUE
P53
Not used
P54
Minimum DHW flow selection for required
activation
10 ÷ 40 (lx10)/min
15 (1,5l/min)
P55
DHW post-ventilation time selection
1 ÷ 30 sec x 10
3
P56
DHW post-circulation time selection
0 ÷ 100 sec
30
P57
Fan speed increase selection
0 ÷ 10%
0
DO NOT MODIFY
P58
Not used
P59
Not used
P60
Additional offset to the switch-off temperature
after burner ignition
0 ÷ 20
0
DO NOT MODIFY
P61
Smoke outlet temperature alarm selection
20 ÷ 150
105
P62
Not used
P63
Not used
P64
Not used
P65
Anti-legionella duration selection
5 ÷ 30 min
15 min
Only for boiler with thermostat
P66
Not used
P67
Not used
P68
DO NOT MODIFY
-
Not used
P69
DO NOT MODIFY
-
Not used
P80
Heating ΔT selection for circulation
block detection
0 ÷ 20
5
0 =
disabled
P81
Maximum heating temperature
0 ÷ 150
90
0 =
disabled
P82
Selection of maximum acceptable
delivery/return ΔT
0 ÷ 50
30
0 =
disabled
-
DO NOT MODIFY
P83
Select months left for maintenance
0 ÷ 255
0
0 =
disabled
P98
Reset TSP to factory values
0 - 1
0
P99
OEM reset to factory values
0 - 1
0
Table 25 - General table of TSP parameters