background image

15 

 

 
The compressor is the heart of the refrigeration circuit.  It takes the cool, low-pressure gas entering the compressor and 
compresses it, which creates the hot, high-pressure gas that exits the compressor.  Since the compressor is not 100% 
efficient, some extra heat is added to the refrigerant as it is being compressed.  
 
The hot, high-pressure gas that exits the compressor is delivered to the condenser.  In the condenser, the heat is 
transferred from the refrigerant into the air or water that is passing through the condenser.  As the heat is transferred, the 
refrigerant changes from a gas to a liquid.  The condenser has been sized to remove the heat from the process load and the 
heat that was added by the compressor. 
  
After leaving the condenser, the liquid refrigerant passes through the filter drier and sight glass.  The filter drier removes 
any particles or moisture from the refrigerant.  The sight glass is used to monitor the stream of liquid refrigerant.  The liquid 
refrigerant then passes through the thermal expansion valve (TXV) which meters the flow into the evaporator where the 
process starts all over again.  
 
Capacity and temperature control is accomplished with a hot gas bypass system.  If the chiller were catering to a partial 
load from the process, the coolant supply temperature would normally tend to drop.  The microprocessor senses this drop 
in temperature, and opens the hot gas bypass solenoid valve.  When this valve is open, some of the hot compressor 
discharge gas is directed to the inlet of the evaporator instead of going through the condenser.  This reduces the chillers 
cooling capacity and puts an additional heat load on the evaporator, which brings the coolant temperature back up to set 
point.  The microprocessor cycles the hot gas solenoid valve as is needed to maintain the coolant temperature to within 1°F 
(1°C) of the set point even with loads as low as 10% to 25% of full capacity.  
 
If the process heat load is extremely low, or even nonexistent, the hot gas bypass system may not be able to put enough of 
a load on the evaporator, and the coolant temperature will begin to drop.  When the coolant temperature drops 7°F (3°C) 
below the set point temperature, the controller will shut the compressor off.  When the coolant temperature rises back to 
the set point temperature, the compressor comes back on.  The compressor will remain off for at least two and one half 
minutes to prevent short cycling.  
 

Chiller Construction 

 

Compressor  

The chiller is equipped with either a hermetic rotary vein or scroll compressor.  Both the compressor and the motor are 
encased together and solidly mounted in the cabinet.  The compressor is unidirectional, so it is important to have power 
phased correctly when operating on a three-phase power supply.  The cool refrigerant suction gas cools the motor 
windings, and there is an internal thermal overload to protect the windings from overheating.  The compressor is lubricated 
with oil that travels throughout the system with the refrigerant. 
 

Air Cooled Condenser 
(Air Cooled Units Only)  

The condenser is constructed of heavy gauge copper tubing and aluminum fins for maximum heat transfer capabilities.  The 
condenser has been generously sized so the chiller can operate with full cooling capacities in ambient air temperatures of 
up to 95°F (35°C).  When the ambient air temperatures are above 95°F (35°C) the chiller will lose approximately 1% of its 
cooling capacity per 1°F (0.5°C) above 95°F (35°C).  The chiller is capable of operating in ambient temperatures of up to 
105°F (40.5°C). 
 
The fan draws cool air through the condenser and discharges warm air out the top of the cabinet.  The unit is designed to 
draw sufficient air through the chiller as long as there are no obstructions.  The fans are not designed to draw air through 
ductwork or discharge air through ductwork.  The discharge air will be approximately 20°F (12°C) warmer than the intake 
air.  
 

Water Cooled Condenser 
(Water Cooled Units Only)  

The condenser is a coaxial tube-in-tube type heat exchanger constructed of a steel outer tube with copper inner tubes.  The 
condenser water passes through the copper inner tubes, while the refrigerant passes around the tubes, in the outer steel 
tube. 

Summary of Contents for EQ Series

Page 1: ...Copyright Thermal Care Inc 2010 EQ Series Portable Chillers Installation Operation and Maintenance Manual ...

Page 2: ...roprocessor Control Fault Logic 7 Power 8 Start 8 Stop 8 Alarm Reset 8 Alarm Silence 8 Lower Set Point Temperature 8 Raise Set Point Temperature 8 No Flow 8 High Refrigerant Pressure 9 Low Refrigerant Pressure 9 Freezestat 9 Low Oil Pressure 9 Over Set Point 9 Under Set Point 9 Pump On 9 Compressor On 9 Partial Load 10 Water Make Up 10 Low Water Level 10 High Water Temperature 10 Probe Fault 10 Ch...

Page 3: ...ant Pump 17 Pressure Gauge 17 Y Strainer 17 High Refrigerant Pressure Switch 17 Low Refrigerant Pressure Switch 17 Freezestat 17 Coolant Pressure Switch 18 Automatic Water Make Up Optional 18 Upgraded Pumps Optional 18 Preventive Maintenance 18 Once a Week 18 Once a Month 18 Every Three Months 19 Preventive Maintenance Checklist 20 Troubleshooting 21 Charts and Drawings 23 Table 8 EQ Air Cooled Ch...

Page 4: ...nicians must be certified by an EPA approved organization It is recommended that good piping practices are followed and that the information in this manual is adhered to We cannot be held responsible for liabilities created by substandard piping methods and installation practices external to the chiller We trust your equipment will have a long and useful life If you should have any questions pleas...

Page 5: ...up for all three phase systems Operation of the compressor with incorrect electrical phase sequencing will result in mechanical damage to the compressors The phasing must be checked with a phase sequence meter prior to applying power The proper sequence should read ABC on the meter If the meter reads CBA open the main power disconnect and switch two line leads on the line power terminal blocks or ...

Page 6: ...24 C 3 11 3 3 8 14 3 GPM L min 80 F 27 C 4 2 15 9 5 4 20 4 GPM L min 85 F 29 C 6 4 24 2 8 2 31 GPM L min 90 F 32 C Call factory Call factory The minimum flows are determined using the condenser water regulating valve setting of 210 PSI 1 45 Mpa for a given supply temperature The supply temperature range is from 40 F 4 4 C to 90 F 32 C Supply temperatures beyond this range are not recommended and m...

Page 7: ... the air cooled condenser The installing contractor need only provide the interconnecting piping between the chiller and the air cooled condenser Refrigerant piping size and piping design has a significant effect on system performance and reliability For specific pipe sizing and configuration refer to the EQR Series Chiller Remote Air Cooled Condenser Installation Guidelines Manual All piping shou...

Page 8: ... connections are secure Open the cabinet and fill the chilled water reservoir with the proper water or water glycol solution See Table 4 for recommended glycol solutions 25 glycol is recommended even if running at temperatures higher than 25 F to help protect the evaporator from potential freezing Use glycol with a corrosion inhibitor only The external sight glass located at back of unit may also ...

Page 9: ...shed through the evaporator before the compressor can operate Under certain conditions the pressure loss in process lines may not be great enough to allow the pressure switch to close A process throttling valve must be installed to regulate process pressure if this condition appears 12 Set water flow through the evaporator as indicated in Table 3 A significant increase in flow beyond the recommend...

Page 10: ...ired2 Remote Alarm Activated3 No Flow LED Yes Yes No No Yes High Refrigerant Pressure LED Yes Yes Yes No Yes Low Refrigerant Pressure LED Yes No Yes No Yes Freezestat LED Yes No Yes Yes Yes Low Oil Pressure LED Yes Yes Yes Yes Yes Over Set Point LED No No No No Yes Under Set Point LED Yes No Yes No Yes Low Water Level LED No No No No No High Water Temperature LED No No No No No Probe Fault LED Yes...

Page 11: ...chased depressing the Alarm Silence button will disable the horn The horn will not reactivate until the alarm has been reset and a subsequent alarm has been triggered If the Remote Alarm contacts option has been purchased depressing the Alarm Silence button will open the contact that was closed when the alarm occurred The contact will not close again until the alarm has been reset and a subsequent...

Page 12: ...ops below the factory set level on the oil pressure switch the compressor and pump will shut off and the Low Oil Pressure LED will be illuminated In order to reset the Low Oil Pressure fault press the Alarm Reset button after resetting the mechanical pressure switch located inside of the cabinet near the compressor Over Set Point The Over Set Point LED will be illuminated if the To Process tempera...

Page 13: ...k has developed in the system If this occurs the Water Make Up LED turns off and the Low Water Level LED remains illuminated Low Water Level This LED is nonfunctional on standard units and will only be active if the Low Water Level option or the Water Make Up option has been purchased When the water level in the reservoir drops below the lower limit of the float switch the Low Water Level LED is i...

Page 14: ...nd release the Start button to store the new selection into the controller memory 6 Press and release the Power button once to exit the function Press and release the Power button again to restore controller power ...

Page 15: ... Data direction register failure Controller requires servicing Contact Manufacturer for repair or replacement 120 Communication data register failure Controller requires servicing Contact Manufacturer for repair or replacement 121 Timer data register failure Controller requires servicing Contact Manufacturer for repair or replacement 122 Hardware watchdog data register failure Controller requires ...

Page 16: ...ncludes an alarm horn that will be activated by certain faults Refer to Table 5 for the Microprocessor Control Fault Logic to determine which faults will trigger the Alarm Horn The Alarm Horn will be silenced by clearing the fault or by pressing the Alarm Silence button If this option is selected in conjunction with the remote control panel the Alarm Horn will be mounted on the chiller and not the...

Page 17: ... the coolant being delivered to the process is controlled by adjusting the amount of heat transferred in the evaporator After leaving the evaporator the coolant passes the Freezestat and thermocouple The Freezestat only on EQ2 series is a safety control that is connected to the microprocessor The thermocouple senses the temperature of the coolant being delivered to process and communicates this te...

Page 18: ...system may not be able to put enough of a load on the evaporator and the coolant temperature will begin to drop When the coolant temperature drops 7 F 3 C below the set point temperature the controller will shut the compressor off When the coolant temperature rises back to the set point temperature the compressor comes back on The compressor will remain off for at least two and one half minutes to...

Page 19: ...frigerant into the evaporator Superheat is the difference between the saturated evaporative temperature and the actual measured temperature at the TXV sensor bulb The superheat is factory set for 10 F to 12 F 5 C to 6 C and should never exceed 15 F 8 C Only a trained refrigeration technician should adjust this valve Refrigerant Sight Glass The refrigerant sight glass is located in the liquid line ...

Page 20: ...ld be installed external to the cabinet on the return from process line High Refrigerant Pressure Switch The High Refrigerant Pressure switch is designed to limit the compressor discharge pressure within the design parameters of the compressor The switch is located on the discharge side of the compressor and can be reset by first pressing the manual reset button located on the High Refrigerant Pre...

Page 21: ...substantially reduced downtime reduced repair costs and an extended useful lifetime for the chiller Any monetary costs of implementing these procedures will almost always more than pay for it To make this as simple as possible a checklist should be prepared which lists the recommended service operations and the times at which they are to be performed At the end of this section we have included a c...

Page 22: ...r fans or blowers on air cooled units and pump to confirm that they are drawing the proper current Every Three Months Repeat items 1 through 9 listed above and continue with the following 10 The Y strainer basket should be removed and cleaned if necessary This may be required more often if contaminants can easily get into the process water 11 Have a qualified refrigeration technician inspect the o...

Page 23: ...led units Temperature Control Pump Discharge Pressure Coolant Level Glycol Concentration Pump Seal Refrigerant Sight Glass Electrical Connections Incoming Voltage Compressor L1 Amps Compressor L2 Amps Compressor L3 Amps Pump L1 Amps Pump L2 Amps Pump L3 Amps Fan L1 Amps Fan L2 Amps Fan L3 Amps Clean Y Strainer Refrigerant Circuit Check Refrigerant Suction Pressure Refrigerant Discharge Pressure Re...

Page 24: ...on pressure sensor Check for proper range replace if faulty Microprocessor control board Replace if faulty High refrigerant pressure Dirty air filters air cooled units only Clean filters Air flow obstruction air cooled units only Make sure chiller is installed in accordance with recommendations in this manual High ambient air temperature air cooled units only Ambient temperature must be reduced be...

Page 25: ... Erratic temperature control Low coolant flow through evaporator Adjust flow to proper level Intermittent overloading of chiller capacity Check to make sure chiller is properly sized for process load Hot gas bypass valve Contact refrigeration service technician Microprocessor control board Replace if faulty Thermocouple Replace if faulty Insufficient cooling temperature continues to rise above set...

Page 26: ... 4 3 3 7 0 8 0 11 10 9 EQ2A03 208 3 60 12 6 1 745 kW 3 9 372 kW single phase 3 0 0 24 23 6 230 3 60 11 4 3 6 2 9 0 22 21 5 460 3 60 6 2 1 8 1 5 0 11 11 9 208 3 60 12 6 2 1 49 kW 7 5 3 0 0 24 27 3 230 3 60 11 4 6 8 2 9 0 22 25 0 460 3 60 6 2 3 4 1 5 0 11 13 7 208 3 60 12 6 3 2 24 kW 10 6 3 0 0 24 30 4 230 3 60 11 4 9 6 2 9 0 22 27 8 460 3 60 6 2 4 8 1 5 0 11 15 1 208 3 60 12 6 2 1 49 kW 2 stg 8 8 3...

Page 27: ...30 3 60 11 4 3 6 0 22 18 9 460 3 60 6 2 1 8 0 11 10 6 208 3 60 12 6 2 1 49 kW 7 5 0 24 24 3 230 3 60 11 4 6 8 0 22 22 1 460 3 60 6 2 3 4 0 11 12 2 208 3 60 12 6 3 2 24 kW 10 6 0 24 27 4 230 3 60 11 4 9 6 0 22 24 9 460 3 60 6 2 4 8 0 11 13 6 208 3 60 12 6 2 1 49 kW 2 stg 8 8 0 24 25 6 230 3 60 11 4 8 0 22 23 3 460 3 60 6 2 3 7 0 11 12 5 Notes RLA Rated Load Amps based on a percentage of the MMTC Ma...

Page 28: ...0 20 30 40 50 60 70 80 90 100 0 5 10 15 20 25 30 PUMP FLOW GPM PUMP PRESSURE PSI 0 20 40 60 80 100 120 140 160 180 200 220 0 10 20 30 40 50 60 70 80 90 100 110 PUMP FLOW L MIN PUMP PRESSURE FT HP positive discplacement pump EQ3A01 2 HP 2 stage 3 HP 2 HP 1 HP ...

Page 29: ...er Pump Curves 50 Hz 0 10 20 30 40 50 60 70 0 5 10 15 20 25 PUMP FLOW GPM PUMP PRESSURE PSI 0 20 40 60 80 100 120 140 160 0 20 40 60 80 PUMP FLOW L MIN PUMP PRESSURE FT HP positive discplacement pump EQ3A01 2 HP 2 stage 3 HP 2 HP 1 HP ...

Reviews: