Charts and Drawings
Table 8 - EQ Air Cooled Chiller Electrical Specifications
Model
Voltage
Compressor
Pump
Condenser Fan
Control Circuit
Unit MCA
2
RLA
1
Power (HP)
FLA
Power (HP)
FLA
FLA
EQ3A01
208/1/60
5.9
¼ (.186 kW)
2.7
1
/
4
(.186 kW)
1.7
0.24
12.8
230/1/60
5.4
2.4
1.6
0.22
11.8
EQ2A02
208/3/60
9.5
1 (.745 kW)
3.9
1
/
4
(.186 kW)
(single phase)
1.7
0.24
18.5
230/3/60
8.6
3.6
1.6
0.22
17.0
460/3/60
4.3
1.8
0.8
0.11
9.0
208/3/60
9.5
2 (1.49 kW)
7.5
1.7
0.24
22.1
230/3/60
8.6
6.8
1.6
0.22
20.2
460/3/60
4.3
3.4
0.8
0.11
10.6
208/3/60
9.5
3 (2.24 kW)
10.6
1.7
0.24
25.2
230/3/60
8.6
9.6
1.6
0.22
23.0
460/3/60
4.3
4.8
0.8
0.11
12.0
208/3/60
9.5
2 (1.49 kW)
2-stg
8.8
1.7
0.24
23.4
230/3/60
8.6
8.0
1.6
0.22
21.4
460/3/60
4.3
3.7
0.8
0.11
10.9
EQ2A03
208/3/60
12.6
1 (.745 kW)
3.9
½ (.372 kW)
(single phase)
3.0
0.24
23.6
230/3/60
11.4
3.6
2.9
0.22
21.5
460/3/60
6.2
1.8
1.5
0.11
11.9
208/3/60
12.6
2 (1.49 kW)
7.5
3.0
0.24
27.3
230/3/60
11.4
6.8
2.9
0.22
25.0
460/3/60
6.2
3.4
1.5
0.11
13.7
208/3/60
12.6
3 (2.24 kW)
10.6
3.0
0.24
30.4
230/3/60
11.4
9.6
2.9
0.22
27.8
460/3/60
6.2
4.8
1.5
0.11
15.1
208/3/60
12.6
2 (1.49 kW)
2-stg
8.8
3.0
0.24
28.6
230/3/60
11.4
8.0
2.9
0.22
26.2
460/3/60
6.2
3.7
1.5
0.11
14.0
Notes:
RLA (Rated Load Amps) based on a percentage of the MMTC (Maximum Must Trip Current) as established by the manufacturer in accordance with UL
Standard 465.
MCA (Minimum Circuit Ampacity) based on 125% of the compressor RLA plus 100% of remaining components FLA in accordance with NEC 440-33. MCA
shown also include 1 amp value for the control circuit.
Voltage Utilization range is: 208 (187 to 229), 230 (187 to 254), and 460 (414 to 506).