background image

 

Water Cooled Condenser Lines 
(Water Cooled Units Only) 

The performance of the condenser is dependent on maintaining the proper flow and temperature of water through the 
heat exchanger.  Insufficient water flow or high condenser water supply temperatures will result in the reduction of cooling 
capacity of the chiller.  Extreme conditions will eventually result in the chiller shutting down due to high refrigerant 
pressure.  Performance can be adversely affected if the condenser is allowed to plug up from contaminants in the 
condenser water stream.  In order to reduce maintenance costs and chiller downtime, a water treatment program is highly 
recommended for the condenser cooling water.  If any condenser does become plugged, contact our Customer Service 
Department for assistance in the proper procedure for cleaning out the condenser.  
 
The standard cooling capacity is based upon 85°F (29°C) condenser cooling water supply.  Under normal operating 
conditions there will be a 10°F (6°C) rise through the condenser resulting in 95°F (35°C) exiting water temperature from the 
condenser.  To ensure proper water flow through the condenser, the condenser water pump should be able to handle up to 
25 PSI (172 kPa) pressure drop through the condenser.  While the design pressure loss is much lower than 25 PSI (172 kPa), 
we recommend the pumping system be sized for this loss to ensure there will be sufficient supply pressure to the 
condensers.  To prevent damage to the condenser or regulating valve, the condenser water pressure should not exceed 150 
PSIG (1034 kPa). The condenser water regulating valve controls the condenser water flow.  The chiller loading and 
condenser water inlet temperature will determine the actual flow.  Table 2 shows minimum condenser water flow 
requirements for the different size chillers at different supply temperatures under fully loaded conditions.  
 

Table 2 - Condenser Water Flow Requirements 

 

EQ2W02 

EQ2W03 

GPM (L/min) @ or below 70°F (21°C) 

2.2 (8.3) 

3 (11.3) 

GPM (L/min) @ 75°F (24°C) 

3 (11.3) 

3.8 (14.3) 

GPM (L/min) @ 80°F (27°C) 

4.2 (15.9) 

5.4 (20.4) 

GPM (L/min) @ 85°F (29°C) 

6.4 (24.2) 

8.2 (31) 

GPM (L/min) @ 90°F (32°C) 

 Call factory 

 Call factory 

 
The minimum flows are determined using the condenser water regulating valve setting of 210 PSI (1.45 Mpa) for a given 
supply temperature.  The supply temperature range is from 40°F (4.4°C) to 90°F (32°C).  Supply temperatures beyond this 
range are not recommended and may lead to improper chiller operation.  
 

Air Cooled Chillers Condenser Air 
(Air Cooled Units Only) 

In order to accommodate the air-cooled condenser, the chiller must be located in a well-ventilated area.  A minimum of 
three feet of clearance is recommended at both the condenser air inlet and condenser air discharge.  The air cooled chillers 
were not designed to have the condenser air discharge ducted.  Improper clearance or poor ventilation will reduce the 
cooling capacity of the chiller and may cause high refrigerant pressure problems.  The condenser air inlet temperature 
should be maintained above 50°F (15°C) in order to avoid possible low refrigerant pressure safety trips during start-up.  
 

Chilled Water Lines 

All chilled water piping should be adequately insulated to prevent condensation.  If water is allowed to condense on the 
piping, the state change of the water from gas to liquid will result in a substantial heat load that becomes an additional 
burden for the chiller.  Standard portable chillers have been designed to provide 50°F (10°C) coolant to the process.  Under 
normal operating conditions there will be a 10°F (6°C) rise through the process resulting in 60°F (16°C) return coolant 
temperature to the chiller. 
 

Table 3 - EQ Series Chilled Water Flow Requirements 

Model 

Nominal Flow 

GPM (L/min) 

Pressure Drop 

PSI (kPa) 

EQ3A01 

2.4 (9) 

1 (6.89) 

EQ2A02 

4.8 (18.1) 

3 (20.68) 

EQ2A03 

EQ2W02 
EQ2W03 

7.2 (27.2) 
4.8 (18.1) 
7.2 (27.2) 

5 (34.47) 
3 (20.68) 
5 (34.47) 

 
The importance of properly sized piping between the chiller and process cannot be overemphasized.  See the ASHRAE 
Handbook or other suitable design guide for proper pipe sizing.  In general, run full size piping out to the process and then 
reduce the pipe size to match the connections on the process equipment.  One of the most common causes of 

Summary of Contents for EQ Series

Page 1: ...Copyright Thermal Care Inc 2010 EQ Series Portable Chillers Installation Operation and Maintenance Manual ...

Page 2: ...roprocessor Control Fault Logic 7 Power 8 Start 8 Stop 8 Alarm Reset 8 Alarm Silence 8 Lower Set Point Temperature 8 Raise Set Point Temperature 8 No Flow 8 High Refrigerant Pressure 9 Low Refrigerant Pressure 9 Freezestat 9 Low Oil Pressure 9 Over Set Point 9 Under Set Point 9 Pump On 9 Compressor On 9 Partial Load 10 Water Make Up 10 Low Water Level 10 High Water Temperature 10 Probe Fault 10 Ch...

Page 3: ...ant Pump 17 Pressure Gauge 17 Y Strainer 17 High Refrigerant Pressure Switch 17 Low Refrigerant Pressure Switch 17 Freezestat 17 Coolant Pressure Switch 18 Automatic Water Make Up Optional 18 Upgraded Pumps Optional 18 Preventive Maintenance 18 Once a Week 18 Once a Month 18 Every Three Months 19 Preventive Maintenance Checklist 20 Troubleshooting 21 Charts and Drawings 23 Table 8 EQ Air Cooled Ch...

Page 4: ...nicians must be certified by an EPA approved organization It is recommended that good piping practices are followed and that the information in this manual is adhered to We cannot be held responsible for liabilities created by substandard piping methods and installation practices external to the chiller We trust your equipment will have a long and useful life If you should have any questions pleas...

Page 5: ...up for all three phase systems Operation of the compressor with incorrect electrical phase sequencing will result in mechanical damage to the compressors The phasing must be checked with a phase sequence meter prior to applying power The proper sequence should read ABC on the meter If the meter reads CBA open the main power disconnect and switch two line leads on the line power terminal blocks or ...

Page 6: ...24 C 3 11 3 3 8 14 3 GPM L min 80 F 27 C 4 2 15 9 5 4 20 4 GPM L min 85 F 29 C 6 4 24 2 8 2 31 GPM L min 90 F 32 C Call factory Call factory The minimum flows are determined using the condenser water regulating valve setting of 210 PSI 1 45 Mpa for a given supply temperature The supply temperature range is from 40 F 4 4 C to 90 F 32 C Supply temperatures beyond this range are not recommended and m...

Page 7: ... the air cooled condenser The installing contractor need only provide the interconnecting piping between the chiller and the air cooled condenser Refrigerant piping size and piping design has a significant effect on system performance and reliability For specific pipe sizing and configuration refer to the EQR Series Chiller Remote Air Cooled Condenser Installation Guidelines Manual All piping shou...

Page 8: ... connections are secure Open the cabinet and fill the chilled water reservoir with the proper water or water glycol solution See Table 4 for recommended glycol solutions 25 glycol is recommended even if running at temperatures higher than 25 F to help protect the evaporator from potential freezing Use glycol with a corrosion inhibitor only The external sight glass located at back of unit may also ...

Page 9: ...shed through the evaporator before the compressor can operate Under certain conditions the pressure loss in process lines may not be great enough to allow the pressure switch to close A process throttling valve must be installed to regulate process pressure if this condition appears 12 Set water flow through the evaporator as indicated in Table 3 A significant increase in flow beyond the recommend...

Page 10: ...ired2 Remote Alarm Activated3 No Flow LED Yes Yes No No Yes High Refrigerant Pressure LED Yes Yes Yes No Yes Low Refrigerant Pressure LED Yes No Yes No Yes Freezestat LED Yes No Yes Yes Yes Low Oil Pressure LED Yes Yes Yes Yes Yes Over Set Point LED No No No No Yes Under Set Point LED Yes No Yes No Yes Low Water Level LED No No No No No High Water Temperature LED No No No No No Probe Fault LED Yes...

Page 11: ...chased depressing the Alarm Silence button will disable the horn The horn will not reactivate until the alarm has been reset and a subsequent alarm has been triggered If the Remote Alarm contacts option has been purchased depressing the Alarm Silence button will open the contact that was closed when the alarm occurred The contact will not close again until the alarm has been reset and a subsequent...

Page 12: ...ops below the factory set level on the oil pressure switch the compressor and pump will shut off and the Low Oil Pressure LED will be illuminated In order to reset the Low Oil Pressure fault press the Alarm Reset button after resetting the mechanical pressure switch located inside of the cabinet near the compressor Over Set Point The Over Set Point LED will be illuminated if the To Process tempera...

Page 13: ...k has developed in the system If this occurs the Water Make Up LED turns off and the Low Water Level LED remains illuminated Low Water Level This LED is nonfunctional on standard units and will only be active if the Low Water Level option or the Water Make Up option has been purchased When the water level in the reservoir drops below the lower limit of the float switch the Low Water Level LED is i...

Page 14: ...nd release the Start button to store the new selection into the controller memory 6 Press and release the Power button once to exit the function Press and release the Power button again to restore controller power ...

Page 15: ... Data direction register failure Controller requires servicing Contact Manufacturer for repair or replacement 120 Communication data register failure Controller requires servicing Contact Manufacturer for repair or replacement 121 Timer data register failure Controller requires servicing Contact Manufacturer for repair or replacement 122 Hardware watchdog data register failure Controller requires ...

Page 16: ...ncludes an alarm horn that will be activated by certain faults Refer to Table 5 for the Microprocessor Control Fault Logic to determine which faults will trigger the Alarm Horn The Alarm Horn will be silenced by clearing the fault or by pressing the Alarm Silence button If this option is selected in conjunction with the remote control panel the Alarm Horn will be mounted on the chiller and not the...

Page 17: ... the coolant being delivered to the process is controlled by adjusting the amount of heat transferred in the evaporator After leaving the evaporator the coolant passes the Freezestat and thermocouple The Freezestat only on EQ2 series is a safety control that is connected to the microprocessor The thermocouple senses the temperature of the coolant being delivered to process and communicates this te...

Page 18: ...system may not be able to put enough of a load on the evaporator and the coolant temperature will begin to drop When the coolant temperature drops 7 F 3 C below the set point temperature the controller will shut the compressor off When the coolant temperature rises back to the set point temperature the compressor comes back on The compressor will remain off for at least two and one half minutes to...

Page 19: ...frigerant into the evaporator Superheat is the difference between the saturated evaporative temperature and the actual measured temperature at the TXV sensor bulb The superheat is factory set for 10 F to 12 F 5 C to 6 C and should never exceed 15 F 8 C Only a trained refrigeration technician should adjust this valve Refrigerant Sight Glass The refrigerant sight glass is located in the liquid line ...

Page 20: ...ld be installed external to the cabinet on the return from process line High Refrigerant Pressure Switch The High Refrigerant Pressure switch is designed to limit the compressor discharge pressure within the design parameters of the compressor The switch is located on the discharge side of the compressor and can be reset by first pressing the manual reset button located on the High Refrigerant Pre...

Page 21: ...substantially reduced downtime reduced repair costs and an extended useful lifetime for the chiller Any monetary costs of implementing these procedures will almost always more than pay for it To make this as simple as possible a checklist should be prepared which lists the recommended service operations and the times at which they are to be performed At the end of this section we have included a c...

Page 22: ...r fans or blowers on air cooled units and pump to confirm that they are drawing the proper current Every Three Months Repeat items 1 through 9 listed above and continue with the following 10 The Y strainer basket should be removed and cleaned if necessary This may be required more often if contaminants can easily get into the process water 11 Have a qualified refrigeration technician inspect the o...

Page 23: ...led units Temperature Control Pump Discharge Pressure Coolant Level Glycol Concentration Pump Seal Refrigerant Sight Glass Electrical Connections Incoming Voltage Compressor L1 Amps Compressor L2 Amps Compressor L3 Amps Pump L1 Amps Pump L2 Amps Pump L3 Amps Fan L1 Amps Fan L2 Amps Fan L3 Amps Clean Y Strainer Refrigerant Circuit Check Refrigerant Suction Pressure Refrigerant Discharge Pressure Re...

Page 24: ...on pressure sensor Check for proper range replace if faulty Microprocessor control board Replace if faulty High refrigerant pressure Dirty air filters air cooled units only Clean filters Air flow obstruction air cooled units only Make sure chiller is installed in accordance with recommendations in this manual High ambient air temperature air cooled units only Ambient temperature must be reduced be...

Page 25: ... Erratic temperature control Low coolant flow through evaporator Adjust flow to proper level Intermittent overloading of chiller capacity Check to make sure chiller is properly sized for process load Hot gas bypass valve Contact refrigeration service technician Microprocessor control board Replace if faulty Thermocouple Replace if faulty Insufficient cooling temperature continues to rise above set...

Page 26: ... 4 3 3 7 0 8 0 11 10 9 EQ2A03 208 3 60 12 6 1 745 kW 3 9 372 kW single phase 3 0 0 24 23 6 230 3 60 11 4 3 6 2 9 0 22 21 5 460 3 60 6 2 1 8 1 5 0 11 11 9 208 3 60 12 6 2 1 49 kW 7 5 3 0 0 24 27 3 230 3 60 11 4 6 8 2 9 0 22 25 0 460 3 60 6 2 3 4 1 5 0 11 13 7 208 3 60 12 6 3 2 24 kW 10 6 3 0 0 24 30 4 230 3 60 11 4 9 6 2 9 0 22 27 8 460 3 60 6 2 4 8 1 5 0 11 15 1 208 3 60 12 6 2 1 49 kW 2 stg 8 8 3...

Page 27: ...30 3 60 11 4 3 6 0 22 18 9 460 3 60 6 2 1 8 0 11 10 6 208 3 60 12 6 2 1 49 kW 7 5 0 24 24 3 230 3 60 11 4 6 8 0 22 22 1 460 3 60 6 2 3 4 0 11 12 2 208 3 60 12 6 3 2 24 kW 10 6 0 24 27 4 230 3 60 11 4 9 6 0 22 24 9 460 3 60 6 2 4 8 0 11 13 6 208 3 60 12 6 2 1 49 kW 2 stg 8 8 0 24 25 6 230 3 60 11 4 8 0 22 23 3 460 3 60 6 2 3 7 0 11 12 5 Notes RLA Rated Load Amps based on a percentage of the MMTC Ma...

Page 28: ...0 20 30 40 50 60 70 80 90 100 0 5 10 15 20 25 30 PUMP FLOW GPM PUMP PRESSURE PSI 0 20 40 60 80 100 120 140 160 180 200 220 0 10 20 30 40 50 60 70 80 90 100 110 PUMP FLOW L MIN PUMP PRESSURE FT HP positive discplacement pump EQ3A01 2 HP 2 stage 3 HP 2 HP 1 HP ...

Page 29: ...er Pump Curves 50 Hz 0 10 20 30 40 50 60 70 0 5 10 15 20 25 PUMP FLOW GPM PUMP PRESSURE PSI 0 20 40 60 80 100 120 140 160 0 20 40 60 80 PUMP FLOW L MIN PUMP PRESSURE FT HP positive discplacement pump EQ3A01 2 HP 2 stage 3 HP 2 HP 1 HP ...

Reviews: