- Instruction Manual for ESS R050100-
34
Note:
(a)
All charge or discharge settings only work when utility is available. During utility outage, economical
mode does not work and whole system follow the default mode.
(b)
If an overlap of charge & discharge time happened at the same date & time, then charge logic takes
the priority.
(c)
If a same charge or discharge date & time repeated in different options, then the priority drops from
Group 1 to Group 4.
(2) Advanced Setting
:
Steps: Connect “Solar-Wi-Fi” -> Open APP -> Choose the inverter you want to configure -> Click
“Settings” ->Choose “Advanced Setting” ->Enable “Back-up Supply” ->Enable “off-Grid Output”
->Enable “SOC Protect”->Setting “Depth of Discharge”.