8. Troubleshooting
IMPORTANT!
The troubleshooting chart covers most of the difficulties that you may encounter under
normal working conditions. If the UPS fails to operate properly, please review the following
steps before contacting the service center.
Fault
code
Description
Possible cause and solution
01
UPS start up not
successful
Battery Low
UPS Internal failure,
Please contact the distributor
02
Internal DC BUS
over-voltage protection
Improper load connected (home appliance with an electric
motor, or a capacitor with a residue charge). Please
disconnect this device from the UPS.
Over mains voltage, turn on the UPS again.
UPS Internal failure,
Please contact the distributor
03
Internal DC BUS
undervoltage protection
Battery Low or overload
UPS Internal failure,
Please contact the distributor
10
UPS Output Short-Circuit
Remove short-circuit equipment from the UPS
22
UPS Over Load
Reduce loading capacity below the UPS power rating
23
UPS Over Temperature
Ensure that the ambient temperature is within the limits
of –10~45C. If the ambient temperature can't meet this
spec, try to reduce the load output.
Please check if the UPS ventilation from the front and the
rear is not blocked.
UPS Internal failure,
Please contact the distributor
29
UPS Input rectifier
protection
Low input voltage and overload
UPS Internal failure,
Please contact the distributor
57
Battery UN-connected
Check battery input wiring and battery cutoff device such
as circuit breaker etc.
59
Charger Fail
UPS Internal failure,
Please contact the distributor
60
EPO activated
Reset the External EPO switch. If there's no EPO switch
installed, please turn off the EPO function via the
operation panel.
Battery Icon Flashing
Battery not connected or battery low
Charger failure,
Please contact the distributor
UPS not working normal line mode,
With normal mains input
Make sure Input circuit breaker is ON
Turn on the UPS via ON/OFF button
Backup time is not as long as
expected
Battery low. Please charge the battery long enough.
Overload, reduce the loading
Battery aged,
Please contact the distributor
UPS not turn ON after pressing
ON/OFF button
Press the ON/OFF button for 3 seconds, or until you hear
the alarm beep.
Battery low or not connected
UPS Internal failure,
Please contact the distributor