background image

Electrical Information

The unit must be electrically grounded in accordance 
with the current National Electrical Code, ANSI/NFPA 
70. In Canada, use the current CSA Standard C22.1, 
Canadian Electrical Code, Part 1. In addition, the 
installer should be aware of any local ordinances or 
electrical company requirements that might apply. 
System power wiring must be properly fused and 
conform to the local and national electrical codes. 
System power wiring is to the unit main disconnect 
(door interlocking disconnect switch standard on most 
units) or distribution block and must be compatible 
with the ratings on the nameplate: supply power 
voltage, phase and amperage (Minimum Circuit 
Amps - MCA; Maximum Overcurrent  Protection - 
MOP). All wiring beyond this point has been done by 
the manufacturer and cannot be modified without 
affecting the unit’s agency / safety certification. If 
field installing an additional disconnect switch, it 
is recommended that there is at least four feet of 
service room between the switch and system access 
panels. When providing or replacing fuses in a fusible 
disconnect, use dual element time delay fuses and 
size according to the rating plate.

Field Power Connection

All power and control connections should be run 
through the floor or side panel of the unit.

If power supply is desired through bottom of unit, run 
the wiring through the curb, cut a hole in the cabinet 
bottom and run wires to the disconnect switch. Seal 
the penetration in cabinet bottom to prevent leakage.

The electric supply to the unit must meet stringent 
requirements for the system to operate properly. 
Voltage supply and voltage imbalance between 
phases should be within the following tolerances.

If the power is not within these voltage tolerances, 
contact the power company prior to operating the 
system.

Voltage Supply

See Voltage Use Range on the rating plate. Measure 
and record each supply leg voltage at all line 
disconnect switches. Readings must fall within the 
allowable range on the rating plate.

Voltage Imbalance

In a 3-phase system, excessive voltage imbalance 
between phases will cause motors to overheat and 
eventually fail. Maximum allowable imbalance is 2%. 
To determine voltage imbalance, use recorded voltage 
measurements in this formula.

Low Voltage Controller Circuitry

Manufacturer recommends that all low voltage 
wiring be run in conduit wherever it may be 
exposed to the weather.

 

Most factory-supplied electrical components are 
pre-wired. To determine what electrical accessories 
require additional field wiring, refer to the unit-specific 
wiring diagram located on the inside of the control 
center access door.

The low voltage control circuit is 24 VAC and control 
wiring should not exceed 0.75 ohms.

Refer to Field Control Wiring Length/Gauge table for 
wire length maximums for a given wire gauge.

Control wires should not be run inside the same 
conduit as that carrying the supply power. Make sure 
that field-supplied conduit does not interfere with 
access panel operation. All low voltage wiring should 
be run in conduit wherever it may be exposed to the 
weather.

If wire resistance exceeds 0.75 ohms, an industrial-
style, plug-in relay should be added to the unit 
control center and wired in place of the remote 
switch (typically between terminal blocks R and G 
on the terminal strip (refer to Typical Control Center 
Components). The relay must be rated for at least 5 
amps and have a 24 VAC coil. Failure to comply with 
these guidelines may cause motor starters to “chatter” 
or not pull in which can cause contactor failures and/
or motor failures.

WARNING

The roof lining contains high voltage wiring. To 
prevent electrocution, do not puncture the interior or 
exterior panels of the roof.

Key:

  

V1, V2, V3 = line voltages as measured

 

VA (average) = (V1 + V2 + V3) / 3

 

VD = Line voltage (V1, V2 or V3) that  

 

deviates farthest from average (VA)

Formula:

 % Voltage Imbalance = [100 x (VA-VD)] / VA

CAUTION

If any of the original wire as supplied with the unit 
must be replaced, it must be replaced with wiring 
material having a temperature rating of at least 
105ºC.

WARNING

To prevent injury or death due to electrocution or 
contact with moving parts, lock disconnect switch 
open.
For units with a gas furnace, if you turn off the 
power supply, turn off the gas.

Field Control Wiring Length/Gauge

Total 

Wire Length

Minimum 

Wire Gauge

125 ft.

18

200 ft.

16

300 ft.

14

450 ft.

12

9

Model MPX Make-Up Air Unit

Model XMPX Make-Up Air Unit

Summary of Contents for XMPX Series

Page 1: ...r seismic activity are present If more information is needed contact a licensed professional engineer before moving forward 1 Follow all local electrical and safety codes as well as the National Elect...

Page 2: ...ed to be taken to prevent deterioration of the unit during storage The user assumes responsibility of the unit and accessories during storage The manufacturer will not be responsible for damage during...

Page 3: ...Center Components DDC Control Package 12 Digital Scroll Compressor Controller 12 Fan Proving Switch 12 Variable Frequency Drives VFD 13 Phase Monitor 13 Typical Wiring Diagram 14 15 Controller Sequenc...

Page 4: ...Operation and Maintenance manuals for additional information Plenum and Plug Indirect Gas Fired Furnace Model PVF PCO3 Controller MPX Subassemblies Blower Each unit has just one backward curved blowe...

Page 5: ...ATER 4 INCH FILTERS I H MPX H34 Unit Size Dimensions MPX H14 MPX H24 MPX H34 MPX H34 Furnaces Single Furnace Double Furnace A 54 3 67 2 72 2 76 2 B 86 6 96 7 97 7 97 7 C 34 0 36 4 33 2 33 2 D 48 1 58...

Page 6: ...mage from occurring to the refrigerant system This unit contains a system that is pressurized with refrigerant and if it is damaged the refrigerant could leak into the atmosphere or cause bodily harm...

Page 7: ...be level Shim as required to level 3 Install Ductwork Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines Duct adapter provided to support ducts prior to setting the...

Page 8: ...rovided with the P trap If local and area building codes permit the condensate may be drained from the P trap onto the roof but a drip pad should be provided beneath the outlet If local and area codes...

Page 9: ...o overheat and eventually fail Maximum allowable imbalance is 2 To determine voltage imbalance use recorded voltage measurements in this formula Low Voltage Controller Circuitry Manufacturer recommend...

Page 10: ...e Air Temperature Sensor All units are supplied with a Discharge Air Temperature Sensor that is to be eld installed prior to unit start up The sensor is to be installed at least three duct diameters d...

Page 11: ...use Blocks 10 Step Down Transformers number varies Low Voltage Side 11 DDC Controller 12 Relays 13 Fan Proving Switch Dirty Filter Switch on side wall 14 Low Voltage Terminal Strip 15 Hot Gas Reheat C...

Page 12: ...ch The unit uses a pressure switch to prove fan operation before operating any heating or cooling sequence It does this by verifying a difference in air pressure on both sides of the air supply fan Wh...

Page 13: ...ed sensors and controlling devices such as CO2 sensors dehumidistats or pressure sensors Refer to the VFD manufacturer s information and unit speci c wiring diagram supplied with the unit For addition...

Page 14: ...R R7 21 24 12 FPS NO C 90 NO3 OAI OAD ACC W BL Y PK Y BL W PK BL R 111 112 SUPPLY FAN M MAIN POWER TO UNIT GROUND L1 L2 L3 DB1 DS1 Y Y PM T1 T2 T3 PM C OUT DL1 4 D1 S4 S6 Y 1 2 ST1 O L 95 96 ST1 A2 A...

Page 15: ...RESSOR RELAY CIRCUIT B R7 COMPRESSOR INTERLOCK RELAY CIRCUIT A R8 COMPRESSOR INTERLOCK RELAY CIRCUIT B RBV REHEAT VALVE CONDENSER RH HEAT RELAY RHV REHEAT VALVE HOT GAS REHEAT S1 EXHAUST SWITCH S3 SUP...

Page 16: ...ehumidi cation Sequence The cooling is controlled to maintain the cooling coil set point The dehumidi cation sequence will be locked out when the OA is less than 10 F above the cold coil set point The...

Page 17: ...the proving switch on the supply air blower and displays an alarm in case of blower failure DX Alarm The DDC monitors the refrigerant pressure and shuts off the refrigeration circuit in the case of hi...

Page 18: ...to enable or disable speci c functions of the unit A unit speci c wiring diagram is included with each panel If speci ed by the owner the remote panel may have a Remote Interface factory installed ins...

Page 19: ...Coil M 1 2 3 4 13 5 12 9 11 13 10 8 13 14 7 15 6 Service Valve for Subcooling Gauge High Side Pressure Drop Circuit A Pressure Port for Troubleshooting Valve Service Valve for Superheat and Low Side P...

Page 20: ...le but excessive bubbles may indicate improper charge or a leak in the system A green dot means that moisture is below a safe operation level in the refrigerant while a yellow dot indicates moisture h...

Page 21: ...n system is excessive cycling on and off The digital scroll compressor eliminates excessive cycling by allowing the compressor to continue to run but internal compression is eliminated in brief cycles...

Page 22: ...Once the call for cooling exceeds 70 then the digital scroll will begin running again in conjunction with the xed scroll compressor see below System Start Up During unit start up amperage draw readin...

Page 23: ...l mode during start up Use necessary precautions to avoid injury All data must be collected while the unit is running In order to measure volts and amps the control center door must be open and the un...

Page 24: ...e Yes No If bubbles are visible in sight glass stop the start up process Refrigerant charge may not be adequate Consult factory Color of Center Dot Green Yellow Hot Gas Bypass Operational Yes No Not p...

Page 25: ...which may cause personal injury or failure of the following components Fan Shaft Bearings Motor Fan Wheel Belt Tighten all fasteners and set screws securely and realign drive pulleys after adjustment...

Page 26: ...cess doors open or without proper ductwork in place as the fan motors will overload Vibration Excessive vibration may be experienced during initial start up Left unchecked excessive vibration can caus...

Page 27: ...low prior to contacting the factory please determine the following information Air ow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with S...

Page 28: ...FD to regulate fan speed in response to various optional sensors such as dehumidistats pressure sensors or CO2 sensors These may be factory installed or they may be provided and installed by the owner...

Page 29: ...t Check motor wiring Check motor nameplate versus supplied voltage Motor horsepower too low See speci cations and catalog for fan curves to determine if horsepower is suf cient Shorted windings in mot...

Page 30: ...a 1 64 inch de ection per foot of span between sheaves Worn belt Replace Motor base or blower loose Tighten mounting bolts Bearing and drive misaligned Realign Noise being transmitted by duct Make sur...

Page 31: ...ine voltage Check line voltage If more than 10 from compressor marking correcting is necessary Compressor motor protector open Motor thermal protector automatically resets Allow time 2 hours for compr...

Page 32: ...erload If compressor is hot allow compressor to cool for two hours Recheck for open circuit Improper refrigerant charge Check subcooling Improperly wired Review wiring schematics Loose wiring Check al...

Page 33: ...ove non condensable from system Dirty condenser coil Clean condenser coil Condenser fan not running or running backwards Check electrical circuit and fuse Check fan cycling controls High load conditio...

Page 34: ...n oversized Contact factory Compressor loses oil Refrigerant leak Check system for leaks Repair leaks and add refrigerant Short cycling Check low pressure control settings Refrigerant ood back Check t...

Page 35: ...air ow Check air ow check lters check drive for loose parts or belts Malfunctioning or defective expansion valve Check bulb of thermal expansion valve Frost on evaporator coil Hot gas bypass valve not...

Page 36: ...ess panels and unit components can be heavy and serious injury may occur This unit requires minimal maintenance to operate properly To ensure proper operation and longevity the following items should...

Page 37: ...ted and require no further lubrication under normal use Normal use being considered 20 F to 120 F and in a relatively clean environment Some bearings are relubricatable and will need to be re greased...

Page 38: ...less may be used to clean coils with a n thickness over 0 0095 inches thick TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the ns will withstand the spray pressure For coils...

Page 39: ...____________________________ _________________________________________________ Date __________________ Time _____________ AM PM Notes ___________________________________________ ______________________...

Page 40: ...transportation prepaid Motors are warranted by the motor manufacturer for a period of one year Should motors furnished by Accurex prove defective during this period they should be returned to the nea...

Reviews: