Fire Ready Hood
12
NOTE
To comply with ADA standards,pull station (if mounted
on an unobstructed wall) must be a max of 48 inches
off of the finished floor.
Manual Pull Station (if applicable)
A manual pull station may be included to manually
trigger and discharge the hood fire suppression
1. Surface mount the manual pull station near the hood
within the path of egress (cable provided is 30 feet in
length).
2. Follow electrical installation instructions for manual
pull station on page 15.
Horn Strobe (if applicable)
If the facility does not have a fire alarm panel, the horn
strobe can provide visual and audible notification of a
fire.
1. Surface mount the horn strobe near the hood (cable
provided is 8 feet in length).
2. Follow electrical installation instructions for horn
strobe on page 15.
Fire Extinguisher (if applicable)
The system may be provided with a separate K-Class,
6 liter wet chemical fire extinguisher.
1. Surface mount the extinguisher per NFPA and local
code requirements.