background image

Upblast Centrifugal Roof Exhaust

9

Tapered Bushing Hub Installation  
and Removal

For wheel hubs and shaft pulleys utilizing a tapered 
bushing interface, follow this procedure for installation 
and removal. There are two possible set ups for the 
tapered bushing, both have the same procedure, but 
orientation of the hub varies.

Tapered Bushing Removal:

1.  If present, loosen the setscrew holding the bushing 

and shaft key in place. 

2.  Loosen and remove the socket head cap screws 

which fasten the bushing to the hub as shown in the 
section views and examples of Figures 18-21.

3. 

Standard Mounting:

  Take the two socket head cap 

screws that were removed and install them into the 
visibly threaded holes on the wheel hub.  

Reverse Mounting:  

Install the two socket head cap 

screws into the visibly threaded holes of the bushing 
flange.

4.  Once both socket head cap screws are installed, 

tighten them an eighth of a turn at a time, alternating 
between the two until the hub comes loose from the 
bushing.

Standard Mounting

Reverse Mounting

Figure 18

Figure 19

Figure 20 

Standard Bushing Orientation

Figure 21

Reverse Bushing Orientation

Bushing

Washers

Cap Screws

Hub

Bushing

Washers

Cap Screws

Hub

Bushing Installation

1.  Clean all surfaces of hub and bushing to remove any 

oil or residue present and do not use any lubricant to 
install bushing into the hub. For both standard and 
reverse mounting styles, the socket head cap screws 
are adjustable from the inlet of the fan.

2.

 Standard Mounting:

  Slide the bushing and shaft 

key onto the fan shaft followed by the wheel and hub 
assembly. If present, use the keyway setscrew to 
hold the shaft key and bushing in place but DO NOT 
overtighten as this can damage the bushing. Align 
the unthreaded holes of the hub with the threaded 
holes of the tapered bushing.  

Reverse Mounting:

  Slide the wheel and hub 

assembly onto the fan shaft followed by the bushing 
and shaft key. If present, use the keyway setscrew to 
hold the shaft key and bushing in place but DO NOT 
overtighten as this can damage the bushing. Align 
the unthreaded holes of the tapered bushing with the 
threaded holes of the hub.

Installation and maintenance are to be performed only 
by qualified personnel who are familiar with local codes 
and regulations and who are experienced with this type 
of equipment.

Motor maintenance is generally limited to cleaning 
and lubrication (where applicable). Cleaning should be 
limited to exterior surfaces only. Removing dust buildup 
on motor housing ensures proper motor cooling.

Greasing of motors is only intended when fittings are 
provided. Many fractional horsepower motors are 
permanently lubricated and should not be lubricated 
after installation. Motors supplied with grease fittings 
should be greased in accordance with manufacturer’s 
recommendations. Where motor temperatures do not 
exceed 104ºF 

(40ºC)

, the grease should be replaced 

after 2,000 hours of running time as a general rule.

Wheels require very little attention when moving clean 
air. Occasionally, oil and dust may accumulate causing 
imbalance. When this occurs, the wheel and housing 
should be cleaned to ensure smooth and safe operation.

All fasteners should be checked for tightness each time 
maintenance checks are performed prior to restarting 
unit.

•  When installing fans for restaurant exhaust 

applications follow NFPA 96 for cleaning fans.

•  Grease containers must be emptied at regular 

intervals to prevent overflow. 

A proper maintenance program will help these units 
deliver years of dependable service.

IMPORTANT

Uneven cleaning of the wheel will produce an out of 
balance condition that will cause vibration in the fan.

Summary of Contents for XRUB Belt Drive

Page 1: ...icals Replace cord immediately if damaged 6 Verify that the power source is compatible with the equipment Direct Drive Upblast Centrifugal Exhaust Fan These fans are specifically designed for roof and wall mounted applications The maximum continuous operating temperature for fan sizes 099 300 is 400 F 204 C and for fan sizes 060 095 is 130 F 54 C Direct drive fans are available with nominal wheel d...

Page 2: ...oid lifting fans in a way that will bend or distort fan parts Never pass slings or timbers through the venturi of fan Fans with special coatings or paints must be protected in handling to prevent damage 4 Drive Frame Lifting Points 2 Bearing Plate Lifting Points Hook With Safety Latch Supplied by others Figure 2 Screw Screw Figure 3 Figure 1 Handling Direct and Belt Drive Units Lift Direct Drive u...

Page 3: ...isture proof paper or polyethylene sheathing Aisles between parts and along all walls should be provided to permit air circulation and space for inspection IMPORTANT Installation troubleshooting and parts replacement are to be performed only by qualified personnel Consult and follow all applicable national state and local codes They will supercede this document Outdoor Fans designed for outdoor ap...

Page 4: ...terial 6 Verify power line wiring is de energized before connecting fan motor to power source 7 For commercial kitchen and UL Listed emergency smoke control applications the electrical supply must enter the motor compartment through the breather tube For other non flammable applications the electrical supply can be routed through the conduit chase between the curb cap and the bottom of the motor co...

Page 5: ...er DO NOT install it Perform steps 3 12 of General Ventilation Installation IMPORTANT The size of the duct must be equal to or larger than the inlet opening of the fan To comply with NFPA 96 the fan discharge must be a minimum of 40 in 1016 mm above the roof surface and a minimum of 10 ft 3048 mm from any building air intake Per NFPA 96 ductwork to an upblast discharge exhaust fan must be construc...

Page 6: ... Hinge Kit Fan to Curb Mounting 5 16 inch 7 9 mm self drilling fasteners are to be installed on each side of fan with one fastener 4 inches 102 mm from each edge and one fastener in the center Figure 9 Fasteners are to be equally spaced Mounting for Severe Duty Installation Optional Hinged Base Mounting For installations that include the optional hinged base accessory the fan must be secured to th...

Page 7: ...NT La turbine doit impérativement tourner dans le bon sens Une rotation en sens inverse entraînerait de mauvaises performances de soufflage une surcharge du moteur voire un grillage du moteur CORRECT WRONG WRONG WRONG Figure 15 Belt Drive Pre Starting Belt Tension Checks 4 Always loosen tension enough to install belts without stretching Do not force belt s see Figure 14 Forcing belts will break th...

Page 8: ... system in full operation and all ductwork attached measure current input to the motor and compare with the nameplate rating to determine if the motor is operating under safe load conditions 6 Keep inlets and approaches to fan clean and free from obstruction IMPORTANT Adjust tighten belt tension after the first 24 48 hours of operation 9 The adjustable motor pulley is factory set for the RPM speci...

Page 9: ...gn the unthreaded holes of the hub with the threaded holes of the tapered bushing Reverse Mounting Slide the wheel and hub assembly onto the fan shaft followed by the bushing and shaft key If present use the keyway setscrew to hold the shaft key and bushing in place but DO NOT overtighten as this can damage the bushing Align the unthreaded holes of the tapered bushing with the threaded holes of th...

Page 10: ...can be classified in two groups relubricating and non relubricating All non relubricating bearings on belt drive fans are factory lubricated and require no further lubrication under normal use between 20º to 180ºF 29º to 82ºC in a relatively clean environment 8 On belt drive fans the standard cast pillow block bearings are factory lubricated and are provided with external grease fittings Annual lubr...

Page 11: ...ey Drive Frame Assembly Vibration Isolators Vertical Support Windband Wheel Breather Tube Birdguard in tube Hoodband Disconnect Switch Hoodband Bracket Horizontal Support Belt Drive Direct Drive Curb Cap Venturi Wheel Vibration Isolators Motor Hoodband Conduit Chase Horizontal Support Vertical Support Hood Clip Motor Cover Birdguard Breather Tube Motor Support Pan Disconnect Drain Trough Windband ...

Page 12: ...e ductwork Check proper operation of face and bypass dampers Check filters and access doors Fan does not operate Electrical supply Check fuses circuit breakers Check for switches off Check for correct supply voltage Drive Check for broken belts Tighten loose pulleys or belts Motor Ensure motor is correct horsepower and not tripping overload protector Motor overloads or overheats Lubrication Check ...

Reviews: