Installation & Operation Manual - Model AVC6000
Contents of this Manual are Subject to Change Without Notification
Page 25
6.5.4.2.1.1 Vertical Sash Only (AI-2) Configuration
Follow the steps below to configure the controller for a
Vertical Sash
style fume hood.
Note:
Most VAV fume hoods are designed with some open area located above and below the sash to
provide a means for air to enter the fume hood from the room when the sash is in the closed position. The
open area above the sash, usually referred to as a
“restricted
upper
bypass”, allows a
ir to enter the fume
hood only when the sash is closed, or nearly closed. As the sash is raised, the upper bypass becomes
blocked limiting the amount of air that can enter from this opening. The lower bypass or airfoil slot
provides a means below the sash for air to enter the fume hood and flow over the work surface. The lower
bypass area is not affected by the sash position.
6.5.4.2.1.2 Horizontal Sash Only (AI-3) Configuration
Refer to the Horizontal Sash Sensor Installation Guide for proper installation of the Accutrol
Horizontal Sash Sensor.
Follow the steps below to configure the controller for a Horizontal Sash style fume hood.
1.
Select
2.
Position Panels to Achieve the
Maximum Opening
3.
Measure Max Open Width &
Height and enter values into the
boxes provided
4.
Measure the slot between work
surface and airfoil and Enter Value
in the Box Provided. If there is a
slot above the horizontal panels,
measure and add this value to the
“Airfoil Opening Height” value.
5.
Enter “
0
” for the Upper Bypass
Opening Height.
6. Select the Monitor configuration (Velocity or Volume)
1.
Select
2.
Open Sash to 100%
3.
Measure Max Open Width &
Height and enter values in the
boxes provided
4.
Measure the Upper Bypass
with Sash Closed and enter
value in the box provided
5.
Measure the Lower Bypass
between Work Surface &
Lower Airfoil and enter value in
the box provided
6. Select the configuration (Velocity or Volume) to be used for the Fume Hood Monitor