Installation & Operation Manual - Model AVC6000
Contents of this Manual are Subject to Change Without Notification
Page 38
Example 2
Control Configuration =
Setback with Pres Sen on DI-1 and Occ Sen on DI-2
Alarm Configuration =
Enable all Alarms
6.5.4.2.5.10 Relay Default Settings in Fume Hood Mode
The Alarm relay in fumehood mode is set to operate as follows:
RA
is
normally closed
, opens upon alarm
RB
is
normally open
, closes on alarm
Note:
The Alarm relay will not close for all alarms. Only Low/High Face Velocity alarms, Low/High Volume alarms,
and Sash % open alarms will trigger the relay to change state from RA to RB.