6.5.10.4
AccuNet
AccuNet
™ is a high
-speed serial bus that is designed to provide a room-level network for
summing the airflow volume of multiple AccuValves while providing a single analog
signal representing the total sum of the AccuValve airflows.
The primary application for AccuNet is in laboratories that have multiple VAV fume
hoods which require the total lab exhaust airflow to be instantly tracked by the supply
airflow to maintain the proper room pressurization. AccuValves must be equipped with
the optional AccuNet Module to operate on the AccuNet Network. Reference Appendix
C for detailed field instructions for configuring the AccuNet Network.
6.5.10.5
Help
About AccuValve Insight
dialog box is shown below.