The ACI BACnet and Modbus RTU Room Series temperature sensors are covered by ACI’s Five (5) Year
Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be
found on ACI’s web site: www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE
Standard 135 is the responsibility of BACnet International (BI). BTL is a registered trademark of BACnet International.
Version: 2.0
I0000927
PRODUCT SPECIFICATIONS
12 to 36 VDC / 24 VAC +/- 10%, 50/60 Hz (Reverse Polarity Protected)
25 mA maximum (0.67 VA)
One
-22 to 176°F (-30 to 80°C)
-40 to 302°F (-40 to 150°C)
-40 to 176°F (-40 to 80°C)
@ 77°F (25°C):
+/- 1.0°F (+/- 0.5°C)
+/- 9°F (+/- 5°C) (Field Configurable)
One
0 to 100%
@ 77°F (25°C):
+/- 2% from 10 to 90% RH
+/- 10% RH (Field Configurable)
4 seconds
BACnet MS/TP or Modbus RTU = Field Selectable; EIA RS-485
0 to 127 (0 (Default - Must be changed if Modbus RTU is selected protocol);
Field Selectable)
Auto Baud (Default,
BACnet Only
), 9600, 19200, 38400, 57600, 76800, 115200
(Field Selectable)
1 Address (example: Address 127 = 1035127; Field Configurable)
None/Even/Odd = Field Selectable
1 or 2 = Field Selectable
8
Screw Terminal Blocks / 16 AWG (1.31 mm
2
) to 22 AWG (0.33 mm
2
)
0.45 lbf-in (0.5 Nm) nominal
-40 to 185°F (-40 to 85°C)
10 to 95% RH, non-condensing
304 Stainless Steel | Diameter: 0.750” (19.05 mm)
“-PB” Enclosure:
ABS Plastic, UL94-HB, Plenum Rated
“-EH” Enclosure:
ABS Plastic with UV Protectant, UL94-V0
Neoprene/EPDM/SBR Polymer / UL94-HBF; FMVSS-302; MIL-R-6130C
Supply Voltage:
Current Consumption:
Number Temperature Sensing Points:
Operating Temperature Range:
Transmitter:
Sensor (Temp-Only):
Sensor (RH and Temp/RH):
Temperature Measurement Accuracy:
Temperature Calibration Offset:
Number RH Sensing Points:
RH Measurement Range:
RH Measurement Accuracy:
RH Calibration Offset:
Temperature / RH Update Rate:
Communication Protocol:
Sensor Addresses:
Supported Baud Rates:
Device Instance Number:
Parity (Modbus RTU)
Stop Bits (Modbus RTU)
Databits (Modbus RTU)
Connections / Wire Size:
Terminal Block Torque Rating:
Storage Temperature Range:
Operating Humidity Range:
Sensing Probe & Filter Material:
Enclosure Specifications:
Foam Pad Material / Flammability: