background image

MENU ADJUSTMENTS

1. Button definition

Set/Save 

Bit Select/decrease 

Adjust/increase

Users can adjust the parameters.
The backlight of LCD will be off after 30s without any key’s operation.
Note: the LCD will display "----" when the settings are successful, and display "Err" when failed.

2. Operation instruction

Users can adjust transmitter parameters. Push 

button to enter programming. "P000" will be displayed. Push 

button to select the Column and push 

 button to cycle 0-9 settings. Select different Codes to enter 

corresponding parameter group settings.

FIGURE 6:

 EOL TERMINATION

Relays parameters and descriptions: 

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

3. System Error signal

DEVICE CONFIGURATION THROUGH MODBUS RTU

MODBUS RTU INTERFACE

The Modbus Remote Terminal Unit (RTU) data link protocol uses EIA-485 as a two-wire, daisy chain 
network. A branch is a discrete chain of devices connected to a controller. The max number of devices per 
segment is (32), as per the Modbus specifications. 4000 ft (1219.2 m) is the maximum recommended length 
for a segment, which includes all devices from the controller to the last device in the daisy chain. 

Each branch must have all devices connected with (A) connected to (A) and (B) connected to (B). If a 
shielded cable is used, this is not to be connected to the devices. The shield cable should only be 
connected on one end to earth ground, usually at the controller. 

Each device must be configured for the correct baud rate and have a unique address in each branch. The 
baud rate for the branch is set by the controller.

EOL TERMINATION RESISTANCE SELECTION

RS-485 requires that the last device in a chain have a termination resistor. This is controlled using a jumper 
in the center and right pins(120 Ω) position marked on FIGURE 7. When the jumper is set to 120 Ω, a 120 Ω 
resistance is added in parallel to the data line. When the jumper is set to left and center pins(disabled), the 
resistance is not added. By default, the jumper is placed in the disabled position.

A typical Modbus RTU mode message frame is shown below. In the Modbus RTU mode, the messages 
between frames are separated by at least 3.5 characters time’s silent interval. If the silent interval between 
two characters is more than 3.5 characters time, the former character was transferred successfully, and the 
current character’s transmission starts.

ADDRESS SELECTION 

Modbus can locate up to 256 different addresses, including valid addresses from 1-247. Address 0 is for 
broadcast and address 248~255 are reserved for special addresses. 

Slave address can be set with compatible Modbus RTU software or via Menu selection(see above for Menu 
Adjustments). Default address is 1.

BAUD RATE, DATABITS, PARITY, AND STOPBITS SELECTION

Baud rate is set to 9600, but can also be configured to 4800 via the register or via Menu selection(see above 
for Menu Adjustments). 

The device that requests information is called the Modbus Master and the devices giving the information 
are Modbus Slaves.  The Modbus sensors are slave devices and the number of Data Bits needs to be the 
same as in the Master device configuration. ACI’s Modbus RTU sensors utilize 8 data bits during 
communication exchange.

Parity default setting is NONE. Stopbit default setting is 1. Both settings can adjusted via the register or via 
Menu selection(see above for Menu Adjustments).

FUNCTION

The function code is the second data in the frame. Valid function codes are from 0~127 (01H~7FH). See the 
relevant Modbus standard. It supports 03H/06H function codes, shown as the following Modbus Poll 
software. The detail register addresses are in:  6 General registers table.

BROADCAST MODE TO WRITE DATA TO SLAVE

Using broadcast mode, customer can write data to all slaves connected to the network. Address of 
broadcast mode to write data is 0.

For example: change slave address with broadcast mode, customer can set a new slave address. Note: since 
this operation will modify all the addresses of the slavers to the same address, it is NOT applicable for 
network of more than one slave.

ERROR CODE

Err 
Er4

POSSIBLE PROBLEMS

Key input error
The sensor’s reading is abnormal

SOLUTION

Input correct code
Check if the sensor is in good connection with the PCB

J8

120Ω

END OF LINE

TERMINATION DISABLED

END OF LINE

TERMINATION ENABLED

J8

120Ω

Mode

0
1

2

3

4

Mode Description

Disable Relay
Activate Relay Below 
Set Point
Activate Relay Above 
Set Point
Activate Relay Between 
High and Low Limits
Activate Relay Outside 
High and Low Limits

PARA. #1

N/A
Set Point

Set Point

Low Limit

Low Limit

PARA. #2

N/A
Dead 
Band
Dead 
Band
High Limit

High Limit

PARA. #3

N/A
Actuate 
Delay(S)
Actuate 
Delay(S)
Actuate 
Delay(S)
Actuate 
Delay(S)

PARA. #4

N/A
Restore 
Delay(S)
Restore 
Delay(S)
Restore 
Delay(S)
Restore 
Relay(S)

Definition

Relay OFF

Relay ON

Relay ON

Relay OFF

Relay OFF

Relay OFF
Low limit

High limit

Dead band
Set point

Relay OFF

Relay ON

Dead band

Set point

Relay OFF

Relay ON

Relay ON
Low limit

High limit

SPECIAL MODE TO READ DATA FROM SLAVE

With the special mode, customer can read the register data under the circumstance of NOT knowing the 
slave address.

Address of special mode read data: 255(0xFF)

Note: this operation is applicable for ONLY ONE slave in the network.

Version: 1.0

I0000941

Summary of Contents for PM2.5-ROOM

Page 1: ...set to Auto Mode IMPORTANT PRECAUTIONS This product uses a laser particulate matter sensor It is strictly prohibited to be disassembled It is dangerous if the human body is exposed to the laser directly If the environment exceeds the measurement range for an extended period it may lead to a decrease of the measurement accuracy The performance of the sensor may be decreased due to excessive dust an...

Page 2: ...ansformer IF THE 24 VDC OR 24VAC POWER IS SHARED WITH DEVICES THAT HAVE COILS SUCH AS RELAYS SOLENOIDS OR OTHER INDUCTORS EACH COIL MUST HAVE AN MOV DC AC TRANSORB TRANSIENT VOLTAGE SUPPRESSOR ACI PART 142583 OR DIODE PLACED ACROSS THE COIL OR INDUCTOR THE CATHODE OR BANDED SIDE OF THE DC TRANSORB OR DIODE CONNECTS TO THE POSITIVE SIDE OF THE POWER SUPPLY WITHOUT THESE SNUBBERS COILS PRODUCE VERY ...

Page 3: ... measuring time to extend the service life of the sensor when the dust concentration changes very slightly Use MODE jumper to choose the mode The factory default mode is AUTO Notes P999 Reset Once entered rST is displayed Press button All factory default settings will be restored P161 1 Point Calibration The current value is displayed Press button to increase an offset Press button to decrease an ...

Page 4: ...uires that the last device in a chain have a termination resistor This is controlled using a jumper in the center and right pins 120 Ω position marked on FIGURE 7 When the jumper is set to 120 Ω a 120 Ω resistance is added in parallel to the data line When the jumper is set to left and center pins disabled the resistance is not added By default the jumper is placed in the disabled position ERROR C...

Page 5: ...Menu selection see above for Menu Adjustments The device that requests information is called the Modbus Master and the devices giving the information are Modbus Slaves The Modbus sensors are slave devices and the number of Data Bits needs to be the same as in the Master device configuration ACI s Modbus RTU sensors utilize 8 data bits during communication exchange Parity default setting is NONE St...

Page 6: ...emarks PM series Product code 9070 PM2 5 Value ug m PM10 Value ug m Default slave address 1 RTU 9600 n 8 1 Write 40016 21845 to reset to factory default setting 0 Off 1 Relay activated Below the set point 2 Relay activated Higher than set point 3 Relay activated in the set range 4 Relay activated outside the set range Relay control parameters set Baud rate 9600 default or 4800 Parity 0 NONE 1 ODD ...

Page 7: ...0 reading 100 500 600µg m3 25 C 50 RH 1 μg m3 In continuous service mode sample time 1s response time 10s 15 minutes MTBF more than 3 years in continuous service mode service life up to 8 10 years in auto intermittent service mode Modbus RTU EIA RS 485 1 247 4800 or 9600 None Even Odd 1 8 ScrewTerminal Blocks 16 AWG 1 31 mm2 to 22 AWG 0 33 mm2 0 45 lbf in 0 5 Nm nominal 32 to 122 F 0 to 50 C 30 to...

Page 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 1 0 I0000941 ...

Reviews: