background image

 

 

Electrocorder EC-7VAR-RS 
Dual Current Range - User Instructions 

 

 

WARNING! 

 
THIS  PRODUCT  MUST  ONLY  BE  USED  BY  SUITABLY 
QUALIFIED  PERSONNEL;  DO  NOT  ATTEMPT  TO  USE  THIS 
PRODUCT  UNLESS  YOU  ARE  QUALIFIED  TO  DO  SO. 
 
HIGH  VOLTAGES  THAT  CAUSE  BURNS AND LETHAL SHOCKS 
ARE 

PRESENT 

DURING 

VOLTAGE 

MONITORING 

AND 

RECORDING! 
 

 

Voltage  inputs  are  not  isolated  from  each  other,  as 

one input is energised, other will become live!

 

 
 

General Description

 

 

 
Thank  you  for  purchasing  the Electrocorder  EC-7VAR-RS, we hope you enjoy using this 
product, this package consists of seven main components: 
 

1. Electrocorder logger (1)

 

The logging unit is housed in a strong ABS case. 

2. Carry Case (1)

 

The ABS case of the logging unit is in turn contained within a soft carry case. 

3. Voltage Input Leads (4) 

Four voltage input leads are provided to allow easy connection to the voltage system. 

4. Current Sensors (3) 

Three current sensors are provided. 

5. USB Lead (1) 

A USB lead is provided to allow connection between the logger and any modern PC. 

6. Software (download free from www.electrocorder.com) 

Electrosoft software is provided free. 

7. User Instructions (1) 

These User Instructions are provided to give guidance, to qualified personnel. 
 

 

PC Hardware requirements 

To  run  Electrosoft  you  must  have  certain  hardware  and  software  installed  on  your 
computer. The system requirements include:- 
An IBM

®

 - compatible Personal Computer with a minimum of an 80486 processor. 

A hard disk, with at least 5MB spare capacity. 
One CD/DVD drive. 
An SVGA 1024 x 768 or higher resolution display. 
At least 16MB of random access memory (RAM). 
A mouse. 
Microsoft

®

 Windows 9X, NT4.0, 2000, XP, Vista, Windows 7, 8, 10 

 

Installing Electrosoft

 

When  you  run  the  Setup  program,  it  will  automatically  set  a  path  on  your  hard  disk  and 
install Electrosoft there.  
 
In Windows 9X, NT4.0, 2000, XP, Vista, Windows 7, 8, 10 the Setup program will create 
an option in your Programs menu, which is in the Start menu. 
 
Step 1: 

To install Electrosoft; run Setup. 

 

 
 
 

For Windows 9X, NT4.0, 2000, XP, Vista, Windows 7. 

Step 2: 

From  the  Taskbar  menu  click  Start  and  choose  Run.  The  Run  dialogue  box 
appears. 

Step 3: 

Type  a:\Setup.  Click  OK.  Follow  the  instructions  on  the  screen  to  install 
Electrosoft - you will be alerted when the installation is complete.

 

 
Getting started 

In order to set-up an Electrocorder, you must first run Electrosoft on your PC. Then connect 
an Electrocorder to the PC serial port using the correct (supplied) serial lead. In Electrosoft, 
use the ‘Setup’ dialog box window and input the details of the location to be monitored. The 
Electrocorder does NOT need to be connected in to the mains voltage to perform this task.  
 
The recording mode is set by default to commence recording when the Electrocorder 

“Start” 

button is pressed, and to stop recording when the memory is full. This logger can be used to 
record voltage and current separately.  When recording voltage, the logger will take power 
from  the  voltage  supply,  however  when  logging  only  current,  battery  life  will  be  reduced, 
where possible use a voltage input. 
 
Select the recording method - two options are available: 
1.  Record  to  EN50160  standard  -  the  Electrocorder  will  take  16  samples  per  channel  per 
cycle  for  10  minutes.  It  then  averages  the  samples  taken  over  that  10  minute  period  and 
stores  the  TRMS  values  as  well  as  single  Max  and  Min  values  for  each  channel.  In  this 
mode the unit will record for approximately 50 days until the memory is full.

 

 
2. Take a sample over a discrete period  - the Electrocorder can be set to take an average 
over  a  selected  period,  2  (two)  sec  to  60  (sixty)  minutes  and  also record the max and min 
during each period. For example, 

a unit set to record every 2 (two) seconds will record 

for  approximately  4  hours

.  A  unit  set  to  record  every  12  seconds  will  record  for 

approximately  1  day. 

A  unit  set  to  record  every  60  (sixty)  minutes  will  record  for 

approximately 300 days.

 

 
When the required information has been input, download to the connected Electrocorder by 
clicking the ‘Write Setup’ icon. The Electrocorder is now ready to monitor voltage. 

 
DUAL RANGE 
The  range  can  only  be  changed  when  the  logger  has  started  logging.  The  presently 
selected  range  will  automatically  be  displayed  if  power  supply  is  connected  to  the 
voltage  inputs.  If  no  power  is  connected  pres

sing  the  “?”  button  will  display  the 

range, either 5A to 400A or 30A to 3k

A. To change the range, press and hold the “?” 

button and press the adjacent up/down arrow, this will toggle the range. Please note 
that the range should be set once at the beginning of recording and not changed, the 
logger  does  not  record  which  range  it  was  in  so  you  should  make note of the range 
used. 

 
When  the  Electrocorder  is  recording  a  flashing  green  light  will  flash  and  when  it  has 
completed  recording,  a  red  light  will  appear  on  the  unit.  If  both  red  and  green  LEDs  are 
illuminated  when  connected  to  voltage,  this  signifies  a  ‘reset’,  the  battery  may  have  been 
dislodged, check the battery, then again set-up the logger to record.  
 
 
When the Electrocorder is recording with voltage connected a flashing green light will show, 
NOTE  the  green  LED  will  not  flash  when  there  is  no  voltage  connected!   When  it  has 
completed  recording,  a  steady  red  light  will  appear  on  the  unit.  The  database  contained 
within  Electrosoft  will  also  advise  that  the unit has completed recording and is ready to be 
collected.  To  download  the  recorded  data  connect  the  Electrocorder  to  the  PC  serial  port 
and click the ‘Read Setup’ icon. The recorded data is displayed for analysis. 

 

This document is produced in conjunction with the Help file contained in Electrosoft, which 
contains  a  detailed  explanation  of  all  features  and  contains  information,  which  should  be 
studied prior to using this product. 
 
 
When  installed,  make  a  note  of  the  serial  or  COM  port  number  the  converter  has  been 
assigned  to  and  when  you  run  Electrosoft,  select  the  appropriate  serial  port  or  COM  port 
number. 
 
 
 

 

SAFETY TIPS 

 

Voltage inputs are labelled ‘L1’, ‘L2’, ‘L3’ and Neutral is labelled ‘N’. For correct operation 
this recorder must have a proper 

Neutral (N) connection. Current inputs are labelled ‘A1’, 

‘A2’ & ‘A3’. Use correct and approved safety clothing including goggles and gloves! 

 
Prior to connection of the logger to any voltage system:- 
 
1) Electrically isolate the conductors to which you wish to connect. 
 
2) Remove (unplug) all voltage leads from the logger. 
 
3) Current input sensors must only be used around insulated conductors, the arrows on the 
Rogowski Coils should point in the direction of the load. 
 
4) Using insulating gloves, connect the each current sensor in turn around each current 
carrying conductor. 
 
5) Using insulating gloves, connect the each voltage lead in turn to the electrical bus-bar 
with the crocodile clip. 
 
6) When all voltage leads are connected to the voltage bus-bars, then beginning with the 
Neutral (N) input, connect in turn each lead to the logger (with the 4mm shrouded plugs).  
 
7) As you connect L1, L2 and L3 there will be a visual light indication should voltage be 
present on the input. 
 
8) Voltage leads are double layer. The inner layer is white, should the lead become scuffed 
and/or damaged, the white inner layer should become visible, as opposed to the normal red 
or black outer layer. When this occurs, you must replace the voltage lead with a new, 
undamaged one. 
 
Features & Benefits of the EC-7VAR Logger System 

Feature 

Benefit 

Unit is small and lightweight. 

Quick and easy to install 

Easy to use Windows software. 

Can be used by non-technical staff. 

Electrosoft contains internal 
database. 

Allows effective management of distributed 
Electrocorders. 

True RMS voltage measurement. 

Complies to EN50160:1994. 

Soft carry case, with handle 

Allows you to keep and carry all the leads etc. 
together with the logger. 

 
Colour Codes Around the World 

Phase 

IEC Colour 
Code 

Aus/NZ 
Colour Code 

US Color 
Code 

Canadian 
Color Code 

L1

 (A) 

Brown 

Red 

Black 

Red 

L2

 (B) 

Black 

White 

Red 

Black 

L3

 (C) 

Grey 

Blue 

Blue 

Blue 

N

 (Neutral) 

Blue 

Black 

White, grey 

White 

(Ground/Earth) 

Yellow/Green 
Stripe 

Yell/Green 
Stripe 

Green, 
Yell/Green 

Green, bare 
copper 

 
Inputs and Connections on Various Systems 

Colour and Input 
Terminal 

Single 
Phase 
(2-Wire) 

Single 
Phase 
(3-Wire) 

3 Phase 
Delta 

3 Phase 
Wye/Star 

Brown (L1/A1)

 

X (Live) 

X (Live) 

X (L1) 

X (L1) 

Black (L2/A2)

 

 

X (Earth) 

X (L2) 

X (L2) 

Grey (L3/A3)

  

 

 

X (L3) 

X (L3) 

Blue (N)

 

X (Neutral)

 

X (Neutral) 

X (N) 

X (N) 

For correct operation this recorder must have a proper Neutral (N) connection.

 

 