3×40W
Alternatively Display voltage and FUL when battery is fully charged
The unit has a 6-stage charging algorithm.
Diagnose* - Soft Charge – Bulk Charge - Absorption charge – Equalizing Charge* - Float Mode
The VOLT/AMP button can be changed at any time during charging process.
The LCD also can be treated as an independent voltage meter or thermometer.
CHARGINGSTAGE
Diagnose *
– Only for Lithium battery type, subjected to the Lithium battery initial voltage then
determine going to Soft start or Bulk charge; if the Lithium battery is protected by BMS, the
controller will automatically send the signal periodically to the battery terminal to activate the BMS
against protection.
Soft start
-When batteries suffer an over-discharge,the controller will softly ramp the battery
voltage upto10V for 12V battery, 20V for 24V battery.
Bulk Charge
- Maximum current charging until batteries rise to Absorption level. For Leadcrystal
battery type, the charge controller will deliver two step level of Bulk charge,when the first level rises
the battery voltage up to14.4V, then switch into the second level of the 50% of the first bulk charge
rate, until the Lead crystal battery voltage up to14.7V.
Absorption
-Constant voltage charging and battery is over 85% for lead acid battery; a Li-ion
battery, LiFePO4 battery and LTO battery will close fully charging after absorption stage, the
absorption voltage level will reach12.6V for Li-ion battery, 14.4V for LiFePO4 battery; 14.0V for LTO
battery. 14.7V for Lead crystal battery.
Equalization*
- Only for WET battery or Calcium battery type, when the battery is deeply drained
below10 Vore very 28 day scycle,it will automatically run this stage to bring the internal cells as an
equal state and fully complement the loss of capacity. (Lead crystal, Li-ion, LiFePO4,LTO, Gel and
AGM battery do not run Equalization charge)