Molded-case circuit breaker (MCCB) and power supply magnetic contactor. (MC)
Be sure to connect MCCBs between AC main circuit power supply and 7200M3, input terminals R , S , T,
to protect wiring. Recommended MCCBs are listed in Table1.2.
When a ground fault interrupter is used, select one not influenced by high frequency. Setting current
should be 200mA or more and operating time, 0.1sec or more to prevent malfunctions.
Table 1.2 Molded-case Circuit Breakers and Magnetic Contactors
•220V Class (3-Phase & Single-Phase Input Series)
Voltage Class 220V 3-phase 220V Single-phase
Inverter model JNTABDCB JK--- JNTBBDCB JK---
R500
0001 0002 0003 0005 7R50 0010 R500 0001 0002 0003 0005
Capacity KVA 1.4
2.1
2.7
4.1
6.9
10.3
13.7
1.4
2.1
2.7
4.1
6.9
Rated Output 3.2
Current A
4.8 6.5 9.6 16 24 32 3.2 4.8 6.5 9.6 16
MCCB 5A
10A
20A
20A
30A
50A
60A
10A
20A
20A
40A
50A
TAIAN CN-11
Magnetic
Contactors
Model
CN-11 CN-11 CN-11
CN-16
CN-18
CN-25
CN-11
CN-11 CN-16 CN-18
CN-25
•440V Class (3-Phase Input Series)
Voltage Class
440V 3-phase
JNTABDCB AZ---
Inverter model
R500
0001
0002
0003
0005
7R50
0010
Capacity KVA
1.4
2.2
3.4
4.1
6.9
10.3
13.7
Rated Output Current A
1.6
2.6
4
4.8
8
12
16
MCCB
5A
10A
10A
10A
20A
20A
30A
TAIAN Magnetic
Contactors Model
CN-11
CN-11
CN-11
CN-11
CN-18
CN-18
CN-25
(4)
Surge absorber
The surge absorbers should be connected to the coils of control relays , magnetic contactors ,magnetic
valves ,or magnetic brake used for the 7200M3 periphery. Otherwise ,large surge voltage occurs at