66
Function
Pn-
Name
Description
Initial
Setting
User
Set
Values
Ref.
Par.
22
Frequency
Reference
Gain
Setting unit: 0.01,
Setting range: 0.01 to 2.00
1.00
23
Frequency
Reference
Bias
Setting unit: 0.01,
Setting range:-1.00 to 1.00
0.00
2.7.10
24
Frequency
Upper Limit
Setting unit: 1%,
Setting range: 0 to 110%
100%
Frequency
Limit
Control
25
Frequency
Lower Limit
Setting unit: 1%,
Setting range: 0 to 110%
0%
2.7.11
26
DC Injection
Braking
Current
Setting unit: 1%,
Setting range:0 to 100% of
inverter rated current
50%
27
DC Injection
Braking
Time at Stop
Setting unit:0.1s,
Setting range:0.0 to 5.0s
0.5s
DC
Injection
Braking
28
DC Injection
Braking
Time at Start
Setting unit:0.1s,
Setting range:0 to 5.0s
0.0s
2.7.12
Torque
Compen-
sation
29
Automatic
Torque Boost
Gain
Setting unit:0.1,
Setting range:0.0 to 3.0
1.0
2.7.13