67
2.6.3
C Group Functions (Constant Pn-30 to 59)
Function
Pn-
Name
Description
Initial
Setting
User
Set
Valu
es
Ref.
Par.
30
Level of Stall
Preventive
Operation during
Acceleration
Setting unit:1%,
Setting range:30 to 200%of
inverter rated current
170%
(Note 1)
Stall
Prevention
31
Level of Stall
Preventive
Operation during
run
Setting unit:0%
Setting range:30 to 200%of
inverter rated current
160%
(Note 2)
2.7.14
32
Multifunction
Input Selection 1
(Terminal 4
Function Selection
0:FWD/REV run command(3-wire
sequence selection)
1:External fault(No contact input)
2: External fault(NC contact input)
3:Multi-step speed reference 1
4:Multi-step speed reference 2
5:JOG command
6:Accel/decel time select
7:External baseblock(No contact input)
8: External baseblock(NC contact input)
9:Search command from maximum
frequency
10: Search command from setting
frequency
11:Accel/decel prohibit
1
Multifunction Selection
Contact
Input
Signal
33
Multifunction
Input Selection 2
(Terminal 5
Function Selection)
1:External fault(No contact input)
2: External fault(NC contact input)
3:Multi-step speed reference 1
4:Multi-step speed reference 2
5:JOG command
6:Accel/decel time select
7:External baseblock(No contact input)
8: External baseblock(NC contact input)
9:Search command from maximum
frequency
10: Search command from setting
frequency
11:Accel/decel prohibit
3
2.7.15
2.7.25
Note:1. Stall prevention during acceleation does not operate at 200%.
2. Stall prevention during run does not operate at 200%.