73
Prevents accidental selection of reverse rotation.
Reverse run command is disregarded if input
20 = X X X 1
1st digit
0: Reverse rotation is possible
1: Reverse rotation is impossible.
2.7.3
V/f CHARACTERISTIC SETTING
Item Name
Constant to be set
Factory Preset
Max. Output Frequency
2
60.0Hz
Max. Voltage
3
220.0V
Max. Voltage Output Frequency
4
60.0Hz
Intermediate Output Frequency
5
1.5Hz
Intermediate Output Frequency Voltage
6
13.2V
Min. Output Frequency
7
1.5Hz
Min. Output Frequency Voltage
8
13.2V
Output Voltage Limiter Selection
1
0000
z
V/F pattern setting
Any desired v/f pattern can be set for special specifications, too. Any v/f pattern can be set according
to the load characterics. The factory preset value is set to
60 Hz saturation type pattern.
V
max.
(Pn-03)
V
V
C.
(Pn-06)
V
max.
(Pn-03)
V
min.
(Pn-08)
V