86
NORMAL FREQUENCY
2.7.14 MOTOR STALL PREVENTION FUNCTION
Item Name
Constant to be set
Factory Preset
Operation Level for Stall Prevention
during Acceleration
30
170%
Operation Level for Stall Prevention
during Running
31
160%
Stall Prevention Function during
Deceleration
20
0000
Automatically adjusts output frequency according to the load so as to continue operation of the machine
without stalling the motor.
˙
Stall prevention during acceleration.
If the motor current exceeds the value set to Pn-30 during acceleration, accleration is stopped until the
motor current is reduced to the Pn-30 set value or less.
Pn-30
Motor current
TORQUE DECREASE