91
Functions of control circuit terminals 13 - 7 , and 14 - 7 , can be switched.
Function of terminal between 13 - 7 at “L” :Set into Pn-34 .
Function of terminal between 14 - 7 at “L” :Set into Pn-35 .
Set Value Function
0(Note 1) Running
1(Note 2) Frequency agreed
2 Zero
speed
3
Frequency detection (output frequency
≧
frequency detection level)
4 Overtorque
detected
Note: 1. Factory preset value of .
2. Factory preset value of .
˙
Maximum output capacity is 48 VDC 50mA.
˙
To drive an inductive load, be sure to insert a free-wheel diode to control surge voltage.
2.7.17
SPEED AGREED SIGNAL OUTPUT
Item Name
Constant to be set
Factory Preset
Frequency Detection Level
36
0.0 Hz
Multifunction Contact Output Function
34 , 35
See page 64