This function is used when operation at an arbitrary speed must be indicated. By setting either set value to
multifunction contact output function ( Pn-34 , Pn-35 ) the following signal output to control circuit
terminal 13 or 14 is enabled. Set 1 or 3 to Pn-34 or Pn-35 when the signal is to be output to control circuit
terminals 13 and 14 , respectively.
(1) Set value = 1 : frequency agreed
(2) Set value = 3 : output frequency
≧
frequency detection level
However, When “frequency agreed” is selected, the frequency agreed signal is turned OFF immediately at
stop signal input.
2.7.18
OVERTORQUE DETECTION FUNCTION
Item Name
Constant to be set
Factory Preset
Overtorque Detection Level
38
160%
DETECTION WIDTH ±
2Hz
OUTPUT FREQUENCY
AGREED FREQUENCY
SIGNAL
CLOSED
FREQUENCY REF.
FREQUENCY
DETECTION SIGNAL
Pn-36
CLOSED
OUTPUT FREQUENCY
FREQUENCY AGREED
SIGNAL
CLOSED
OUTPUT FREQUENCY
RUN SIGNAL
DETECTION WIDTH
±
2Hz