DC Inverter
X-Series
for R410A Unitary Split Air Conditioner
11
3.2 Unit Installation
3.2.1 Outdoor Unit Installation
(1) If the outdoor unit is installed on a solid ground such as concrete, use M10
screw bolts and nuts to secure the unit and make sure the unit stands erect and
level.
(2) Do not install it on top of the building.
(3) If it vibrates and causes noise, please add rubber cushion between the outdoor
unit and the installation base.
(4)
Plugs and drainage connector are not recommended if there is an electrical
heater on the chassis.
3.2.2 Connection Pipe Installation
3.2.2.1 Installation Notice and Requirement on Connection Pipe
Installation method: Connect the connection pipes first to the unit. When bending a
connection pipe, be careful not to damage the pipe. Do not over-tighten the screw nut,
otherwise leakage will occur. Besides, the outside of connection pipe should be added
with a layer of insulating cotton to protect it from mechanical damage during installation,
maintenance and transportation.
Item
Model
Size of fitting
pipe(inch)
Maximum
pipe
length
feet(m)
Biggest drop between
indoor and outdoor
units
feet(m)
Liquid
pipe
Gas
pipe
A
ULD36W2/A-D(U)
A
ULD60W2/A-D(U)
Φ
3/8
Φ
3/4
98.4(30)
49.2(15)
Connection pipe should adopt water-proof insulating material. Its wall thickness
should be 0.5-1.0mm and the pipe wall should be able to withstand 6.0MPa. The longer
the connection pipe is the worse cooling performance it has.