BusWorks® 961/962EN User’s Manual Modbus TCP/IP Differential I/V Input
___________________________________________________________________
_______________________________________________________________________________________
Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:
sales@acromag.com
http://www.acromag.com
13
Update Time:
Specify a time from 0-90 seconds between messages.
Specify 0 to turn mapped messaging OFF.
Map To IP Address:
This is the Static IP Address of the target output
device (a 972/973EN module on the network).
Map To Holding Register Address:
Specify a valid 4xxxx holding register
address in the target device for writing to the output. For the 972/973EN,
only addresses 40019 to 40024 will apply and correspond to channels 0-5.
Mapping Method (962EN):
Since the input signal is bipolar and the output
channel is unipolar, you may select “Unipolar” to map 0V input to 0% output,
or “Bipolar” to map 0V input to 50% output.
WEB BROWSER
I/O Mapping Page
(Optional i2o Function)
Test Page
After the username and
password assignment, plus
setting your network
configuration parameters, you
can use the Test Page shown
at left to operate your module.
The Test Page will allow you
to read inputs and change
input ranges on this model.