The following table outlines the register map for the Model 961EN-4006 and 
962EN-4006 network input modules.  The Modbus functions operate on 
these registers using the data types noted above (except for the Reset Slave 
and Report Slave ID functions).  Unless otherwise noted, Holding Register 
values are maintained in flash memory and are non-volatile. 
 

Ref  Addr. Description Data 

Type/Format 

Input Registers (3x References, Read-Only) 

3

0001 

0000 Module 

Status 

Bit 15: 0 (Not Used) 
Bit 14: Wink Mode Flag 
1 = Wink Mode (Blinks Run LED for ID) 
0 = Normal Operation 
(See Wink Module Register) 
Bit 13: Default Mode Flag 
1 = Default Mode Indicator 
0 = Not Default Mode 
Bits 12-0: 0 (Not Used) 

Bits 15-4:  0 (Not Used) 

Bits 

3,2,1,0: 

 
961EN 

 
962EN 

0000 0=0-20mA  0=±10V 
0001 1=4-20mA  1=±5V 
0010 2=0-11.17mA 

2=±2.5V 

0011 3=0-1mA  3=±1.25V 
0100 

Reserved 

4=±625mV 

0101 

Reserved

 5=±313mV 

0110 

Reserved

 6=±156mV 

0111 

Reserved

 7=±78mV 

3

0002 

0001 Input 

Range 

(CH 0,1,2 ) 

1000-1111

Reserved 

3

0003 

0002 Input 

Range 

(CH 3,4,5 ) 

Format is same as Above. 

Bits 15-2:  0 (Not Used) 
Bits 1,0: 

Input Signal Status 

00 In 

Range 

01 Over-Range 
10 Under-Range 

3

0004 

0003 CH00 

Status 

11 Not 

Used 

Bits 15-2:  0 (Not Used) 
Bits 1,0: 

Input Signal Status 

00 In 

Range 

01 Over-Range 
10 Under-Range 

3

0005 

0004 CH01 

Status 

11 Not 

Used 

Bits 15-2:  0 (Not Used) 
Bits 1,0: 

Input Signal Status 

00 In 

Range 

01 Over-Range 
10 Under-Range 

3

0006 

0005 CH02 

Status 

11 Not 

Used 

Register Map 

 
Model 961EN-4006 
Model 962EN-4006 

Summary of Contents for 961EN-4006

Page 1: ...ent Inputs Model 962EN 4006 Six Differential Voltage Inputs USER S MANUAL ACROMAG INCORPORATED Tel 248 624 1541 30765 South Wixom Road Fax 248 624 9234 P O BOX 437 Wixom MI 48393 7037 U S A Copyright...

Page 2: ...18 Getting Out Of Trouble 18 TECHNICAL REFERENCE KEY FEATURES 19 HOW IT WORKS 20 ABOUT MODBUS TCP IP 21 IP Addressing 21 Dynamic Host Configuration Protocol 23 Domain Name System DNS 23 MODBUS REGIST...

Page 3: ...006 IN4 44 41 36 33 PWR NETWORK 13 IN0 16 IN1 21 24 IN2 TB3 TB1 GND INPUTS 4 5 IN5 46 43 45 RX 35 42 DC DC 32 31 34 TB1 11 14 12 IN0 TB2 22 15 TX IN1 5V 3V TB4 TB4 25 23 26 IN3 IN2 IN3 INPUTS 2 3 DC P...

Page 4: ...il until it snaps into place To remove first separate the input terminal block s from the bottom side of the module to create a clearance to the DIN mounting area Next while holding the module in plac...

Page 5: ...ED MDI ETHERNET SWITCHES AND HUBS ARE WIRED MDI X THE ACROMAG ETHERNET SWITCH IS AUTOMATIC MDI MDI X AND ELIMINATES THE NEED FOR MAKING A DISTINCTION BETWEEN THE USE OF STRAIGHT THROUGH MDI AND CROSSO...

Page 6: ...WIRE TRANSMITTER 961EN 5020 350 SENSOR AC CURRENT SENSOR INPUT 961EN 9 Connect 15 36V DC to the power terminals labeled DC DC Observe proper polarity For supply connections use No 14 AWG wires rated f...

Page 7: ...R S IN1 IN1 FIELD XMTR 250 OHMS IN0 IN0 INP DCS PLC TB1 DIFFERENTIAL VOLTAGE MONITORING Temperature Pressure Level Flow Speed CHART RECORDER DATA LOGGER OR TRANSMITTER 962EN 24V DC 250 OHMS OUT NOTE 9...

Page 8: ...web pages of this module that are used to configure the network parameters change the user name and password map inputs to calibrate the module and operate test the module For each new browser session...

Page 9: ...s you may be prompted to re enter your new username and password before being permitted to move to other pages You can click the Network Configuration Page button to set the network configuration para...

Page 10: ...ddresses while the DHCP server is responsible for dynamically passing out IP addresses A Subnet Mask is used to subdivide the host portion of the IP address into two or more subnets The subnet mask wi...

Page 11: ...ocol refers to a protocol for assigning dynamic IP addresses to devices on a network With dynamic addressing a device can have a different IP address every time it connects to the network In some syst...

Page 12: ...pdate time Note that the target output channels may still be controlled independently but their level will be overwritten by subsequent mapped messages when enabled Use the scroll bar on the right to...

Page 13: ...e on the network Map To Holding Register Address Specify a valid 4xxxx holding register address in the target device for writing to the output For the 972 973EN only addresses 40019 to 40024 will appl...

Page 14: ...ration Control of this page to change the input range for each channel group 0 1 2 or 3 4 5 For the 961EN shown you may select from 0 20mA 4 20mA 0 11 17mA and 0 1mA DC current ranges For the 962EN yo...

Page 15: ...t register access as described in Method 2 of the following page Your success in recalibrating the input will strongly depend upon the accuracy and precision of your signal source If recalibration of...

Page 16: ...continue Repeat this process for the other endpoint span 7 Repeat steps 2 5 for the other input channels to be calibrated Method 2 Calibration Via The Modbus TCP IP Interface 1 Write to the appropria...

Page 17: ...s ethernet port is wired MDI You must use a crossover cable when connecting this module to your PC or another device also wired MDI If you are connecting to an Ethernet switch or hub then a direct ca...

Page 18: ...revent you from writing invalid values to a configuration register As such if you inadvertently write an invalid value to an internal register you could cause the module to become inoperable under cer...

Page 19: ...D EFT and other transients 10Base T and 100Base TX Support Integrated IEEE 802 3 802 3u 100Base TX 10Base T Auto Negotiated 10 100Mbps Half or Full Duplex Flexible Multi Range Analog Inputs Accepts ei...

Page 20: ...le The current input model 961EN uses precision 24 9 current sink resistors across the inputs Voltage input models use 10 1 precision resistor voltage dividers at the input A multiplexer is used to co...

Page 21: ...ng data Modbus A Modbus TCP IP message is simply a Modbus communication encapsulated in an Ethernet TCP IP wrapper In practice Modbus TCP embeds a Modbus data frame into a TCP frame without the Modbus...

Page 22: ...k of 255 255 255 0 then the first three numbers represent this Class C network at address 128 1 1 0 the last number identifies a unique host node on this network node 100 at address 128 1 1 100 A Subn...

Page 23: ...xxx Read Input Registers A 3x reference register contains a 16 bit number received from an external source e g an analog signal 4xxxx Read Write Output or Holding Registers A 4x register is used to st...

Page 24: ...1 FIELD DESCRIPTION Unit ID Echo Unit ID Sent In Query Function Code 11 Byte Count 42 Slave ID Model No 00 961EN 4006 6 Diff Current In w Modbus 01 962EN 4006 6 Diff Voltage In w Modbus Run Indicator...

Page 25: ...il ON Writing to multiple coils is not supported via register mirroring you must use the Write Multiple Coils function for that Note that with respect to Acromag 9xxMB Modbus RTU modules only 3xxxx In...

Page 26: ...atus Bit 15 0 Not Used Bit 14 Wink Mode Flag 1 Wink Mode Blinks Run LED for ID 0 Normal Operation See Wink Module Register Bit 13 Default Mode Flag 1 Default Mode Indicator 0 Not Default Mode Bits 12...

Page 27: ...0009 CH00 Value Percentage 30011 000A CH01 Value Percentage 30012 000B CH02 Value Percentage 30013 000C CH03 Value Percentage 30014 000D CH04 Value Percentage 30015 000E CH05 Value Percentage 30016 00...

Page 28: ...0F Reserved Do Not Use 40017 0010 Reserved Do Not Use 40018 0011 Reserved Do Not Use 40019 0012 Reserved Do Not Use 40020 0013 Reserved Do Not Use 40021 0014 Calibration Access And Wink Mode Toggle An...

Page 29: ...40031 001E CH0 Cal Lo Range 4 Raw A D Count Value See Note 2 625mV 962EN 40032 001F CH0 Cal Hi Range 5 Raw A D Count Value See Note 2 313mV 962EN 40033 0020 CH0 Cal Lo Range 5 Raw A D Count Value See...

Page 30: ...ue See Note 2 4 20mA 961EN or 5V 962EN 40057 0038 CH2 Cal Lo Range 1 Raw A D Count Value See Note 2 4 20mA 961EN or 5V 962EN 40058 0039 CH2 Cal Hi Range 2 Raw A D Count Value See Note 2 0 11 17mA 961E...

Page 31: ...See Note 2 313mV 962EN 40081 0050 CH3 Cal Lo Range 5 Raw A D Count Value See Note 2 313mV 962EN 40082 0051 CH3 Cal Hi Range 6 Raw A D Count Value See Note 2 156mV 962EN 40083 0052 CH3 Cal Lo Range 6 R...

Page 32: ...unt Value See Note 2 4 20mA 961EN or 5V 962EN 40106 0069 CH5 Cal Hi Range 2 Raw A D Count Value See Note 2 0 11 17mA 961EN or 2 5V 962EN 40107 006A CH5 Cal Lo Range 2 Raw A D Count Value See Note 2 0...

Page 33: ...0081 Ideal Range 6 Hi Ideal A D Count Value See Note 2 156mV 962EN 40131 0082 Ideal Range 6 Lo Ideal A D Count Value See Note 2 156mV 962EN 40132 0083 Ideal Range 7 Hi Ideal A D Count Value See Note 2...

Page 34: ...a group network and power are isolated from each other Non volatile reprogrammable memory in the module stores configuration and calibration information The BusWorks model prefix 900 denotes the Serie...

Page 35: ...to the 961EN s process current input terminals Input Burden A function of the wire gauge resistance used for primary turns the current carrying wire being monitored AC Current Sensor to Transmitter Wi...

Page 36: ...ide 4 68 inches tall 4 35 inches deep Refer to the dimensions drawing at the front of this manual DIN Rail Mount Type EN50022 T rail 35mm I O Connectors Removable plug in type terminal blocks rated fo...

Page 37: ...n Degree 2 environment with an installation category over voltage category II rating Electromagnetic Interference Immunity EMI Unit has demonstrated measurement shift less than 0 25 of input span with...

Page 38: ...s or 100Mbps Duplex Auto negotiated Full or Half Duplex Compliance IEEE 802 3 802 3u 802 3x Modbus TCP IP Protocol Support Up to 10 sockets may be selected Web pages for configuration and control are...

Page 39: ...esigned for use in harsh industrial environments Acromag recommends the use of shielded cable when wiring to this device Select STP Shielded Twisted Pair cable rather than UTP Unshielded Twisted Pair...

Page 40: ...e and an RJ45 plug at both ends This cable performs the Ethernet crossover function and is used to connect a PC directly to an Acromag Series 9xxEN I O module Note that you do not need to use a crosso...

Reviews: