BusWorks Model XT1531‐000
4 CH Current 4 CH Digital I/O w/USB & Modbus
Acromag, Inc. Tel: 248‐295‐0880
‐
11
‐
Current Output Connections
(Requires Additional
Excitation at TB3)
The
XT1531
model can drive four
DC current outputs up to 22mA each
(0‐20mA &
4‐20mA range support). The maximum digital output current is 22.1901mA. A 16‐
bit voltage DAC drives a voltage‐to‐current converter at each channel and sources
DC current to the load to output return (RTN). Outputs share a common return
connection and are not isolated channel‐to‐channel. Outputs require external
analog excitation to operate. Outputs include current limiting. There are two
analog excitation inputs, one for 12V (10‐15V), another for 24V (20‐28V), and their
outputs are diode‐coupled to allow redundant excitation. Do not connect 24V
excitation to the 12V terminals, or damage will result. Refer to the following
figures for example DC current output & excitation connections to this model.
NOTE THAT CURRENT IS SOURCED FROM THE CHANNEL TERMINAL AND
RETURNED AT ANY RETURN (RTN) TERMINAL.
1-8 OR
13-20
OUTPUT
LOAD
THERE ARE ELEVEN COMMON RETURN TERMINALS
ON THIS MODEL AT TB2, TB3, TB5, & TB6.
CONNECT INPUT
RETURN TO EARTH
GROUND.
THE CURRENT OUTPUTS CAN DRIVE UP TO 22.2mA INTO 550 OHMS.
16-BIT OUTPUT IS 5.5253/ 249=22.1901mA MAX at 32767.
0-20mA OUTPUT (0 to 29533) IS NORMALIZED TO 0-30000,
OR 0 TO 20000 WITH LEGACY SUPPORT ENABLED.
4-20mA IS A SUB-RANGE OF 0-20mA (5907 TO 29533) AND IS
NORMALIZED TO 0-30000 OR 0-20000 WITH LEGACY SUPPORT
ENABLED.
THE 0-20mA NORMALIZED 0-30K MAX CURRENT IS 21.845mA (32767).
THE 0-20mA NORMALIZED 0-20K MAX CURRENT IS 22.1901mA (22190).
THE 4-20mA NORMALIZED 0-30K MAX CURRENT IS 21.476mA (32767).
THE 4-20mA NORMALIZED 0-20K MAX CURRENT IS 22.1901mA (22738).
OR 6, 7, 8,
9, 11
USE 24V (20-28V) OR 12V (10-15V) TO POWER THE CURRENT OUTPUT
CHANNELS AS SHOWN.
ONLY ONE SOURCE IS
NEEDED, BUT BOTH
ARE DIODE-COUPLED
TO CURRENT OUTPUTS
AND MAY CONNECT
REDUNDANTLY.
CAUTION: DO NOT CONNECT 20-28V TO THE 10-15V
EXCITATION TERMINALS OR DAMAGE WILL RESULT.
THERE ARE ELEVEN COMMON RETURN TERMINALS
ON THIS MODEL AT TB2, TB3, TB5, & TB6.
IT IS BEST TO APPLY EARTH GROUND TO RETURN
AT ONE MODULE RETURN (RTN) TERMINAL.
CONNECT RETURN TO
EARTH GROUND AT ONE
MODULE RTN TERMINAL.
WARNING:
In order to operate current outputs, you must additionally provide 12V or 24V excitation to the appropriate
analog Excitation terminals as shown above.
DO NOT CONNECT 24V EXCITATION TO THE 12V TERMINALS, OR DAMAGE
IF THE OUTPUT CURRENT LOAD IS NOT
ALREADY GROUNDED, CONNECT
EARTH GROUND AT ONE RETURN AS
SHOWN.