Model DT233-0600
Dual Two-Wire mV/TC Input Transmitters
Acromag, Inc. Tel: 248-295-0880
- 10 -
http://www.acromag.com
- 10 -
https://www.acromag.com
Output/Power
Connections
…
WARNING:
For compliance to applicable safety and performance standards,
the use of twisted pair output wiring is recommended. Failure to adhere to
sound wiring and grounding practices as instructed may compromise safety,
performance, and possibly damage the unit.
TIP - Ripple & Noise:
Place additional capacitance at the load to help reduce the
60Hz/120Hz ripple sometimes present in industrial applications. For large 60Hz
ripple, connect an external 1uF or larger capacitor directly across the load to reduce
excess ripple. Most modern systems will use high-speed acquisition at the load
making them more sensitive to noise--high frequency noise may be significantly
reduced in these applications by placing a 0.1uF or 0.01uF capacitor directly across
the load, as close to the load as possible (this may also raise RF immunity).
TIP - Inductive Loads:
If either two-wire current loops include a highly inductive
load (such as an I/P current-to-pressure transducer), this may reduce output
stability. In this case, place a 0.1uF capacitor directly across the inductive load(s)
and this will typically cure the problem.