Model DT233-0600
Dual Two-Wire mV/TC Input Transmitters
Acromag, Inc. Tel: 248-295-0880
- 42 -
http://www.acromag.com
- 42 -
https://www.acromag.com
Agency Approvals
Electromagnetic Compatibility (EMC
): CE marked, per EMC Directive 2014/30/EU.
FCC Conformity:
This device complies with Part 15, Class B of the FCC rules.
Safety Approvals:
cULus Listed Class I, Division 2, Groups A, B, C, D Hazardous
Location or Nonhazardous Locations only. These devices are open-type devices that
are to be installed in an enclosure suitable for the environment. Consult Factory.
ATEX/IECEx Certified:
ATEX/IECEx Certified for Explosive Atmospheres per ATEX
Directive 2014/34/EU which complies with standards EN IEC 60079-0:2018, EN
IEC 60079-7:2015 +A1:2018, IEC60079-0 Edition 7, and IEC 60079-7 Edition 5.1.
II 3 G Ex ec IIC T4 Gc -40
o
C
≤
Ta
≤
+80
o
C
UL 20 ATEX 2416
X
IECEx UL 20.0088
X
X
= Special Conditions
1)
The equipment shall only be used in an area of not more than pollution
degree 2, as defined in EN/IEC
60664‐1.
2)
The equipment shall be installed in an enclosure that provides a degree of
protection not less that IP 54 and only accessible with the use of a tool in
accordance with EN/IEC
60079‐
0.
3)
Transient protection should be provided and set to a level not exceeding
140% of the peak rated voltage value at the supply terminals to the
equipment.
Reliability Prediction
Reliability Prediction
MTBF (Mean Time Between Failure):
MTBF in hours using MIL-HDBK-217F, FN2.
Per
MIL-HDBK-217, Ground Benign, Controlled, G
B
G
C
Temperature
MTBF (Hours)
MTBF (Years)
Failure Rate (FIT
1
)
25°C
1,197,365 hrs
136.7 years
835.2
40°C
798,569 hrs
91.2 years
1,252.2
1
Note: FIT is Failures in 10
9
hours
Configuration Controls
Software Configuration Only via USB/Windows or USB-OTG/Android & Agility
This dual transmitter modulates the level of analog output current in separate 2-wire
current loops proportional to their sensor inputs based on its differential voltage
measurement across its input at TB1 and TB3. No switches or potentiometers are
used to make adjustment to this transmitter. Its behavior as an isolated signal
amplifier/transducer is determined via programmed variables set using a temporary
USB connection to a host computer or laptop running a Windows-compatible
configuration software program specific to the transmitter model, or a wired USB-
OTG connection to an Android smartphone or tablet running Agility. The USB
software or Agility app provides the framework for digital control of all configuration
and calibration parameters, which are stored in non-volatile memory of the unit.
LED Indicators, Red FLT1 & FLT2
One Red FLT LED per output current loop. Blinking red continuously indicates the
corresponding output load resistance is too high to drive its current accurately, or
the loop voltage level is too low to drive the loop resistance at the desired current
level. OFF is normal and LED will blink once if loop power is lost or the loop is
opened.