BusWorks Model XT1533-000
4 CH Current 4 CH Digital I/O w/USB & Profinet
Acromag, Inc. Tel: 248-295-0880
- 6 -
http://www.acromag.com
- 6 -
http://www.acromag.com
ELECTRICAL CONNECTIONS
WARNING
–
EXPLOSION HAZARD
–
Do not disconnect equipment unless power has
been removed or the area is known to be non-hazardous.
WARNING
–
EXPLOSION HAZARD
–
Substitution of any components may impair
suitability for Class I, Division 2.
WARNING
–
EXPLOSION HAZARD
–
The area must be known to be non-hazardous
before servicing/replacing the unit and before installing.
Wire terminals can accommodate 14
–
26 AWG (2.08
–
0.13mm
2
) solid or stranded
wire with a minimum temperature rating of 85
o
C. Input wiring may be shielded or
unshielded type. Twisted pair, or shielded twisted pair, input wiring is
recommended. Terminals are pluggable and can be removed from their sockets by
prying outward from the top with a flat-head screwdriver blade. Strip back wire
insulation 0.25-inch on each lead and insert the wire ends into the cage clamp
connector of the terminal block. Use a screwdriver to tighten the screw by turning
it in a clockwise direction to secure the wire (use 0.5-0.6nM torque). Since common
mode voltages can exist on I/O wiring, adequate wire insulation should be used and
proper wiring practices followed. As a rule, output wires are normally separated
from power and network wiring for safety and isolation, as well as for low noise.
T-Rail
35mm DIN Rail
SCREWDRIVER SLOT
FOR REMOVAL FROM
"T" TYPE DIN RAIL
TILT MODULE UPWARD TOWARDS RAIL AND
HOOK ONTO UPPER LIP OF RAIL. ROTATE
MODULE DOWNWARD TO ENGAGE SPRING
CLIP ONTO LOWER LIP OF RAIL.
TOP
BOTTOM
SERIES XT MODULE DIN RAIL MOUNTING AND REMOVAL
SPRING CLIP
USE SCREWDRIVER TO REMOVE
MODULE FROM RAIL AS SHOWN
SERIES XT MODULE
(POWER THIS SIDE)
BUSWORKS
XT
U
S
B
R
U
N
S
T
A