BusWorks Model XT1533-000
4 CH Current 4 CH Digital I/O w/USB & Profinet
Acromag, Inc. Tel: 248-295-0880
- 7 -
http://www.acromag.com
- 7 -
http://www.acromag.com
Power Connections
Connect a DC power supply from 12-32V as shown in the drawing below. Observe
proper polarity (input power is reverse-polarity protected). Optionally, the unit may
be powered (or redundantly powered) via its DIN rail connector (optional terminal
required, see bottom figure below). For supply connections, use 14 AWG wire rated
for at least 80°C. Do not exceed 36V DC peak. Note that output channels of this
model will require separate connections to power (see Output Connections).
MODEL XT1xxx-000 POWER WIRING
+
-
DC SUPPLY
(12-32V)
EARTH
GROUND
DC POWER
TERMINALS
TB3
TB4
RIGHT EDGE VIEW
+
-
24
23
UNIT IS DC-POWERED ONLY AT 12 TO 32VDC.
RIGHT SIDE
TB1
DIN RAIL SPRING CLIP
FUSE
POWER INPUT IS ISOLATED FROM I/O
AND NETWORK CIRCUITS.
CAUTION: DO NOT EXCEED 36VDC, OR
DAMAGE TO THE UNIT MAY RESULT.
NOTE: IT IS RECOMMENDED THAT
SUPPLIES CAPABLE OF DELIVERING
MORE THAN 2.5A TO THE UNIT BE
FUSED WITH A HIGH SURGE
TOLERANT FUSE.
TB6 OF TX6
20
19
18
17
-
+
ANY
(I/O)
TB5 OF TX5
TB4 OF TX4
(I/O)
(DC POWER)
16
15
14
13
XT1xxx-000
TB2
TB5
TB6
35mm DIN RAIL
MALE TERMINAL BLOCK
ACROMAG 1005-221
(RIGHT-SIDE CONNECTION)
FEMALE TERMINAL BLOCK
ACROMAG 1005-220
(LEFT-SIDE CONNECTION)
DC-
DC+
DC-
DC+
+
-
DC SUPPLY
(12-32V)
EARTH
GROUND
+
-
DIN RAIL BUS POWER
FUSE
CAUTION: DO NOT EXCEED 36VDC, OR DAMAGE
TO THE UNIT MAY RESULT.
NOTE: IT IS RECOMMENDED THAT SUPPLIES
CAPABLE OF DELIVERING MORE THAN 2.5A TO
THE BUS BE FUSED WITH A HIGH SURGE
TOLERANT FUSE.
-
+
YOU CAN OPTIONALLY CONNECT POWER
TO THE DIN RAIL BUS CONNECTOR ALONG
THE DIN RAIL USING AN OPTIONAL
TERMINAL AS SHOWN.
LEFT
RIGHT
BUSWORKS
XT
U
S
B
R
U
N
S
T
A
T
+
-
+
-
24
23
22
21
OPTIONAL/REDUNDANT
RAIL (BUS) POWER
POWERING INDIVIDUAL MODULES
VIA SCREW TERMINALS ON UNIT
ANY XT MODEL
EARTH
GROUND
OR
HERE
(GROUND ONE END, NOT BOTH)
IT IS BEST TO APPLY EARTH GROUND
CLOSEST TO THE MODULE, BUT NEVER
AT BOTH ENDS OF THE CONNECTION.
HERE
IT IS BEST TO APPLY EARTH GROUND
CLOSEST TO THE MODULE, BUT NEVER
AT BOTH ENDS OF THE CONNECTION.