Configuration level
Configuration parameters
26
Operating manual MIR-491
Name
Value range Description
Default
51
Potentiometer ( 0...450 Ohm)
52
Potentiometer ( 0...1600 Ohm)
53
Potentiometer ( 0...4500 Ohm)
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at
CAL
level)
2
2-point correction (at
CAL
level)
3
Scaling (at
PArA
level)
In.F
-1999...9999
Alternative value for error at INP2
OFF
fAI2
Forcing INP2
(only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
InP.3
Name
Value range Description
Default
I.Fnc
Function selection of INP3
1
0
no function (subsequent input data are skipped)
1
heating current input
2
external set-point (
SP.E
)
3
Yp input
4
Second process value X2
5
Y.E
input
6
no controller input (e.g. transmitter input instead)
S.Lin
Linearization (only at S.tYP = 30 (0..20mA) and 40
(0..10V) adjustable)
0
0
none
1
Linearization (only at
S.tYP
= 30 (0..20mA) and 40
(0..10V) adjustable) to specification. Creation of
linearization table with BlueControl (engineering tool)
possible. The characteristic for KTY 11-6 temperature
sensors is preset.
S.tYP
Sensor type selection
30
0
thermocouple type L (-100...900°C) , Fe-CuNi DIN
1
thermocouple type J (-100...1200°C) , Fe-CuNi
2
thermocouple type K (-100...1350°C), NiCr-Ni
3
thermocouple type N (-100...1300°C), Nicrosil-Nisil
4
thermocouple type S (0...1760°C), PtRh-Pt10%
5
thermocouple type R (0...1760°C), PtRh-Pt13%
6
thermocouple type T (-200...400°C), Cu-CuNi
7
thermocouple type C (0...2315°C), W5%Re-W26%Re
8
thermocouple type D (0...2315°C), W3%Re-W25%Re