Configuration level
Operating manual MIR-491
29
Configuration parameters
Name
Value range Description
Default
Src.3
Source of limit 3
0
0
process value
1
control deviation xw (process value - set-point)
2
control deviation xw (with suppression after start-up and
set-point change)
3
measured value INP1
4
measured value INP2
5
measured value INP3
6
effective setpoint Weff
7
correcting variable y (controller output)
8
control variable deviation xw (actual value - internal
setpoint) = deviation alarm to internal setpoint
9
difference x1 - x2
HC.AL
Alarm heat current function (INP2)
0
0
switched off
1
Overload short circuit monitoring
2
Break and short circuit monitoring
LP.AL
Monitoring of control loop interruption for heating
0
0
switched off / inactive
1
active.
If
ti1
=0 LOOP alarm is inactive!
dAc.A
DAC alarm function
0
0
DAC alarm switched off / inactive
1
DAC alarm active
Hour
OFF...10000
Operating hours
(only visible with BlueControl!)
OFF
Swit
OFF...10000
Output switching cycles
(only visible with BlueControl!)
OFF
Out.1
Name
Value range Description
Default
O.Act
Method of operation of output OUT1
0
0
direct / normally open
1
inverse / normally closed
Y.1
Controller output Y1
1
0
not active
1
active
Y.2
Controller output Y2
0
0
not active
1
active