Configuration level
Operating manual MIR-491
35
Configuration parameters
LOGI
Name
Value range Description
Default
L_r
Local / Remote switching (Remote: adjusting of all values
by front keys is blocked)
0
0
no function (switch-over via interface is possible)
1
always active
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è
- key switches
SP.2
Switching to second setpoint
SP.2
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è
- key switches
SP.E
Switching to external setpoint
SP.E
0
0
no function (switch-over via interface is possible)
1
always active
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è
- key switches
Y2
Y/Y2 switching
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è
- key switches
6
Ò
- key switches
Y.E
Switching to fixed control output
Y.E
0
0
no function (switch-over via interface is possible)
1
always activated (manual station)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è
- key switches
6
Ò
- key switches