4.5
Configuration examples
4.5.1
Signaller (inverse)
ConF
/
Cntr
:
SP.Fn
=
0
set-point controller
C.Fnc
=
0
signaller with one output
C.Act
=
0
inverse action
(e.g. heating applications)
ConF
/
Out.1
:
O.Act
=
0
action
Out.1
direct
Y.1
=
1
control output Y1 active
PArA
/
Cntr
:
SH
= 0...9999
switching difference (symmetrical
to the trigger point)
PArA
/
SEtP
:
SP.LO
= -1999...9999 set-point limit low for Weff
SP.Hi
= -1999...9999 set-point limit high for Weff
g
For direct signaller action, the controller action must be changed
(
ConF
/
Cntr
/
C.Act
=
1
)
Configuration level
Operating manual MIR-491
43
Configuration examples
InH.1
InL.1
SP.LO
SP
SP.Hi
100%
0%
SH
Out.1
Â
InP.1
Ê
setpoint
output
process value
SH