2-point correction
(
ConF
/
InP.1
/
Corr
=
2
):
InL.1
:
The input value of the lower scaling point is displayed.
The operator must adjust the lower input value by means of a
process value simulator and confirm the input value by pressing key
Ù
.
OuL.1
:
The display value of the lower scaling point is displayed.
Before calibration,
OuL.1
equals
InL.1
.
The operator can correct the lower display value by pressing the
ÈÌ
keys. Subsequently, he confirms the display value by pressing key
Ù
.
InH.1
:
The input value of the upper scaling point is displayed. .
The operator must adjust the upper input value by means of the
process value simulator and confirm the input value by pressing key
Ù
.
OuH.1
:
The display value of the upper scaling point is displayed.
Before calibration
OuH.1
equals
InH.1
.
The operator can correct the upper display value by pressing keys
ÈÌ
Subsequently, he confirms the display value by pressing key
Ù
.
g
The parameters (
OuL.1
,
OuH.1
) changed at
CAL
level can be reset by adjusting
the parameters below the lowest adjustment value (
OFF
) by means of decrement
key
Ì
.
Calibration level
Operating manual MIR-491
57
r
Ì
Ù
3 sec.
r
PArA
CAL
r Ù r
InP.1
Ù
r
InL.1
r
r Ù
r
:
OuL.1
r
r Ù
End
r
r Ù
InH.1
r
r Ù
OuH.1
r
r Ù
Ì
È
Ì
È
1200
1199
°C
°F
SP.2
SP.E
para
func
Ada
Err