background image

cycles  themselves,  are  set  during  start-up  of  system.  The  controller  has  16  preset  on 
and off interval settings ranging from 3 to 48 doses per day.  The zone dosing time can 
be set from 6 minutes to 16 minutes.   This allows the operator to closely approximate 
the  design  loading  rate.  The  dual  alternating  pump  control  panel  ensures  that  both 
pumps  get  equivalent  use.    The  control  panel  allows  both  pumps  to  operate 
simultaneously  only  during  field  flush  cycle,  when  a  larger  volume  of  flow  (velocity)  is 
needed to friction-scour the interior of all piping. 

Disc Filtration --All suspended solids larger than 100 micron in size are filtered out of the 
effluent  stream  before  entering  the  driplines.  For  this  purpose, 

ACT

  WFS

”  uses  an 

appropriately sized disc filter battery; each filter element has a stack of serrated plastic 
rings that provide length, width and depth for solids removal. 

The  plastic  discs  are permanent,  and  the  automatic back flush  is triggered  by  either  a 
pre-set time interval and/or pressure drop across the filters (say, > 6 PSI). Back flushed 
liquids and solids are returned upstream to the primary treatment process (if nearby) or 
to an adjacent back flush tank for settling.  

Flow  meter  --Placed  in-line  downstream  from  the  filters,  the  flow  meter  allows  the 
operator to monitor both instantaneous and daily flows. 

Solenoid  Valves  --The  "workhorses"  of  the  pump  station  are  the  solenoid  valves 
controlling  direction  of  the  flow  at  pump  start.  During  back  flushing,  filter  valves  are 
closed  sequentially  to  back  flush  each  element,  and  the  master  valve  is  closed  to 
concentrate all flow to the specific filter element being back flushed. 

Drain field Equipment and Operation 

Equipment in the irrigated zones includes 1/2" diameter drip tubing buried 6-12" below 
grade, PVC supply and return headers and mains, one electric solenoid valve per drip 
field zone and a return main valve for monthly field flushing. 

Drip  Tubing  --  The  standard  emitter  used  by 

“ACT WFS” discharge 0.61 gph over the 

pressure  range  of  7-70  PSI  in  the  drip  lines.  Precise  emission  over  a  wide  pressure 
range allows much greater uniformity of subsoil wetting than is otherwise possible. Drip 
lines  are  typically  laid  on  2’  centers,  with  a  24"  spacing  between  emitters  inside  the 
tubing.  The  pressure-compensating  diaphragm  within  each  emitter  accomplishes 
emission  uniformity  and  functions  as  a  self-cleaning  mechanism.    Other  emitter  flow 
rates are available and include 0.42 gph and 0.92 gph. 

PVC  Mains  --  Effluent  is  transported  from  the  pump  station  via  supply  mains  of 
Schedule  40  PVC  pipe.  Tees  and  adapters  are  inserted  at  specified  intervals  within 
each zone’s supply header for effluent feed into each drip line. At the end of each drip 
line  run,  adapters  and  tees  are  again  inserted  to  connect  drip  tubing  to  the  return 
header,  creating  a  circular  system  for  periodic  field  flushing  of  all  mains,  headers  and 
drip tubing in the system. 

Field Solenoid Valving -- The drain field to be used for effluent disposal is divided into a 
number of zones which are dosed one at a time and sequentially.  

Summary of Contents for ACT-100S

Page 1: ...ubsurface drip irrigation it is possible to quickly change dosing amounts in the controller if ponding occurs in any of the zones 5 No Size Limitation the size of standard absorption fields is limited by the need to increase depth of the lines for gravity flow ACT WFS installations are unlimited in size because pressure dosed effluent is applied uniformly throughout the dripper line matrix by pres...

Page 2: ...flow at pump start During back flushing filter valves are closed sequentially to back flush each element and the master valve is closed to concentrate all flow to the specific filter element being back flushed Drain field Equipment and Operation Equipment in the irrigated zones includes 1 2 diameter drip tubing buried 6 12 below grade PVC supply and return headers and mains one electric solenoid v...

Page 3: ...esidential and small commercial systems The ACT WFS Model ACT 100S is designed to protect subsurface drip tubing used for effluent dispersal by removing potential clogging agents The Bioline Dosing Management Controller monitors the system and regulates its operation The ACT Water Filtration System removes suspended solids so only those particles smaller than 100 micron may pass into the drip tubi...

Page 4: ...tling The ACT 200S head works include the same automatic back flushing filter as found in the ACT 100S but in multiples The primary difference between the multiple filter units is that there is no secondary flush only filter as found on the 100S The 200S filter systems use the additional filters as a source of back flush water ACT 100S and Major Accessories ...

Page 5: ...ter for the pre set back flush cycle During the back flush no water is allowed to discharge from the filter units unless equipped with a pressure sustaining valve pilot Operation ACT 100S Filtration Mode Refer to Single Filter Illustration Water enters the inlet fitting and moves through the normally open valve Water moves through the main ring disc filter and discharges through the normally open ...

Page 6: ...ment system Typical flushing events last from 30 seconds to 2 minutes Once the filter back flush is completed the controller turns off the 24 VAC signal and the filter system returns to the Filtration Mode Tank Return Field Flush Backflush Filter Filter ACT 100S Inlet Supply Valve N O Field Flush Valve N C ...

Page 7: ...ial applications where reliability is a must The filter is equipped in a modular design Each filter is independent with regards to filter back flush Each filter side is equipped with a normally open and normally closed valve that reverse during filter back flush In addition the 200S is equipped with a master valve that closes during back flush and does not permit effluent flow to the dispersal fie...

Page 8: ...nds about 2 from the edge of the platform Prepare the site for the head works platform The unit can be installed so that it sits on the ground surface is partially buried or fully buried DO NOT cover the top of the head works box The unit requires occasional maintenance and must be left at or above the finished grade Be careful to set the final grade of the top of box so that grass and surrounding...

Page 9: ...ened to the skid and not allowed to carry any unsupported piping or other loads such as pumps OPERATION Note The following describes startup using the ACT Bioline Dosing Management System IF you are using a different dosing and filter flush controller you must follow the controller manufacturer s recommendations for operation Startup Startup is a critical operation where the system is tested witne...

Page 10: ...e Alarm button for more than 5 seconds or the controller will enter the programming mode Release the button and the pump will start The pump will run for the programmed dosing time and then go into a rest mode until time to start the next scheduled dose The alarm float can be tested in two ways It is recommended the test be done by raising the high water float by hand or with another object The fl...

Page 11: ...rned off and on again in the dosing mode as described under Testing and Inspection MAINTENANCE The components making up the ACT WFS ACT 100S dispersal system require limited maintenance and inspection The operator and or maintenance provider should inspect the entire system for potential leaks and component deterioration a minimum of two times per year The following should be performed each time t...

Page 12: ...re that the gray stack base remains firmly set in the filter body Be careful not to loose the compression spring on top of the disc stack It has two parts the spring and alignment button Place the rings on a small rope or length of braded wire Clean the rings with detergents and treat with a chlorine solution such as household bleach Agitate aggressively and rinse Inspect the rings and insure that...

Page 13: ... filter flush Carefully remove the flush filter cover by unscrewing the top Open the filter carefully and expose the screen filter element This is a course filter 50 30 mesh so the openings will appear fairly large Grasp the filter element carefully and pull it out of the filter housing Be sure that the spinner plate is attached Remove the plate from the housing if it fails to remain with the filt...

Page 14: ...screen and examine it for clogging A high pressure sprayer can be used to remove stubborn residues The finger filter can also be cleaned by soaking it in a detergent and chlorine combination which will help to remove and oxidize organic materials typical of primary effluent systems Use Teflon tape to seal the threads on the finger filter and reinstall the unit Be sure to reconnect the control tubi...

Page 15: ...be removed and cleaned This may be necessary on an annual basis especially if sunlight is present and encourages algal growth The return valve and air vacuum relief valve typically require no annual maintenance but should be observed for leaks or other outward problems TROUBLE SHOOTING System problems can occur that may cause the DRIP TECH system not to function properly Always begin by servicing ...

Page 16: ... option to repair or replace part or all of a defective product or refund part or all of the original purchase price if any part proves to be defective in material or workmanship after return of such product at customer s expense and after such return has been authorized in writing by JNM Technologies Inc THIS BASIC MANUFACTURER S LIMITED WARRANTY IS SUBJECT TO THE TERMS AND PROVISIONS IN SUBSECTI...

Page 17: ...LAIMS JNM TECHNOLOGIES INC SHALL NOT BE RESPONSIBLE FOR THE AFORESAID DAMAGES CLAIMS OR LOSSES DUE TO LATE DELIVERY OR DELIVERY OR NON DELIVER OR OTHERWISE THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION AS SET FORTH HEREIN IF JNM TECHNOLOGIES INC SHALL FURNISH TECHNICAL ADVICE OR ASSISTANCE WITH RESPECT TO THE PRODUCTS SOLD HEREUNDER IT SHALL BE GIVEN WITHOUT CHARGE TO BUYER AND SHALL...

Page 18: ...notice of claim offer JNM Technologies Inc in writing prompt opportunity to examine the defective product and correct the defect if possible This warranty shall be void unless buyer delivers the defective product to JNM Technologies Inc at buyer s sole cost and in accordance with JNM Technologies Inc s instructions ...

Reviews: