background image

ACTpro DESFIRE EV1 Operating and Installation Manual 

                     Rev 1.0 

 

Reader Configuration 

 

About DESFire EV1 File operation 

The default operation of all ACTpro MIFARE DESFire EV1 readers configured for file operation, to read the 

number that is encoded in a file on the ACT MIFARE DESFire EV1 cards, the number is also printed on the 

cards. 

 

About Serial and Reverse Serial operation 

When in Serial or reverse serial mode the MIFARE DESFire EV1 card serial number is read by the reader. 

 

 

Operation: ACTpro MIFARE DESFire EV1 1030PM / 1040 / 1050 

The ACTpro MIFARE DESFire EV1 readers can be configured to operate in file operation mode (the default) 

or as a serial/reverse serial reader which is selectable via a jumper.  

 

The default position of the jumper is set for file operation (jumper on pins 1 and 2). To change the operation 

power down the reader, change the jumper for the desired operation and then reapply power. 

 

 

DESFire EV1 File  

Serial 

Reverse Serial 

 

 

Connect pins 1&2

 

 

 

Connect pins 2&3 

 

 

Do NOT connect Jumper 

 

 

 

 

Jumper selects 1 of 3 modes 
1. DESFire EV1 File operation 
2. Serial number operation 
3. Reverse Serial number operation 

 

 

 

Operation: ACTpro MIFARE DESFire EV1 1030  

 

The operation of the ACTpro DESFire EV1 1030 is selectable via cable configuration, the default setting is File 

operation where both Orange and Purple cables are connected to 0V. To change the operation power down 

the reader, change the Orange and Purple cable for the desired operation and then reapply power. 

 

 

 

Colour 

DESFire EV1 File 

Serial Reverse 

Serial 

Orange 0V 

0V 

Not 

Connected 

Purple 0V 

Not 

Connected 

0V 

 

4

Summary of Contents for ACTPRO MIFARE DESFIRE EV1 1030

Page 1: ...Operating Installation Instructions for ACTpro MIFARE DESFire EV1 Readers 18 00072...

Page 2: ..._____________________________4 Operation ACTpro MIFARE DESFire EV1 1030PM 1040 1050 ______________________________________ 4 Operation ACTpro MIFARE DESFire EV1 1030___________________________________...

Page 3: ...DESFire EV1 1040 DESFire EV1 1050 Description MIFARE DESFire EV1 proximity reader MIFARE DESFire EV1 proximity reader MIFARE DESFire EV1 proximity reader MIFARE DESFire EV1 pin and proximity reader Mo...

Page 4: ...iring Information for Clock Data Output The standard Clock Data wiring colours for ACTpro MIFARE DESFire EV1 readers are shown below Reader PIN Description Recommended wiring colour Description Sense...

Page 5: ...ite Direction connect for entry Clock D1 Green Clock D1 Data D0 Blue Data D0 12 24 V DC Red Voltage 0 V Black Voltage Red Brown Red LED Green Yellow Green LED Wiring for Entry Exit Wiegand Readers Wir...

Page 6: ...ctable via a jumper The default position of the jumper is set for file operation jumper on pins 1 and 2 To change the operation power down the reader change the jumper for the desired operation and th...

Page 7: ...pplied and sounds continuously until the 0V is removed buzzer Control not available on the ACTpro MIFARE DESFire EV1 1030 reader The Red and Green LEDs are activated by applying 0V to the respective R...

Page 8: ...ACTpro DESFIRE EV1 Operating and Installation Manual Rev 1 0 Installation diagram for DESFire EV1 Surface Flush Mount Readers Flush Mount Unit Surface Mount Unit 6...

Page 9: ...ACTpro DESFIRE EV1 Operating and Installation Manual Rev 1 0 7 Installation diagram for DESFire EV1 Panel Mount Reader...

Reviews: