Application
Installation Method
Actionair SmokeShield
Actionair FireShield
Vertical DWFX-F In A Plasterboard
Wall
Page 3, [AA/F13069]
Page 3, [AA/F10704]
Page 3, [AA/F10705]
Vertical DWFX-F, Ablative Batt In A
Plasterboard Wall
Page 4, [AA/F10710]
Page 4, [AA/F10711]
Vertical DWFX-3F (Top Flange Remo-
ved) In A Plasterboard Wall Under
Concrete Slab
Page 5, [AA/F11945]
Page 5, [AA/F11944]
Vertical DWFX-F In A Masonry Wall
Page 6, [AA/F10706]
Page 6, [AA/F10707]
Vertical DWFX-F, Ablative Batt In A
Masonry Wall
Page 7, [AA/F10712]
Page 7, [AA/F10713]
Vertical DWFX-F, In A Masonry Wall
With Pattress
Page 8, [AA/F12493]
N/A
Vertical DWFX-3F (Top Flange Remo-
ved) In A Masonry Wall Under Con-
crete Slab
Page 9, [AA/F12394]
Page 9, [AA/F12827]
• The methods in this manual should be followed to
ensure a CE-marked installation. This CE installation
document covers single dampers only. If a multiple
damper assembly or, if a non-standard install is requi-
red, talk to us as early as possible in the project to get
important stakeholders engaged and ensure an instal-
lation solution can be found.
• The instructions are based on the tested method using
Actionair Smoke Shield PTC fire/smoke dampers and
Firetherm products.
• Our SmokeShield dampers are designed to be used
with fire separating elements to maintain fire compart
-
ments. The SmokeShield is an actuated failsafe close
damper with low smoke leakage, often referred to in
the industry as a Fire/Smoke damper.
• Under the Fire Damper Product standard BS EN 15650
our Fire Damper products are tested to BS EN 1366-2
and classified under BS EN 13501-3.
•
Notified body - BRE Global
• Test report P112628-1006 (Vertical Test) P112628-1014
(Actuator in Horizontal test) P112628-1015 (Actuator
out Horizontal Test)
• For smoke control, the product you use should be
tested to BS EN 1366-10 and drive open, drive closed
without failsafe position, see our website for informa-
tion on the Actionair SmokeCommand smoke con-
trol damper documentation and suitable installation
methods.
CE Installation Method Overview