Actionair DWFX-F Installation Guide
8
Swegon reserves the right to alter specifications. 20210408 - LNNN00354 (3.0)
Vertical Damper in a Masonry Wall
with Pattress
Actionair SmokeShield PTC - [AA/F12493]
Installation Method
1.
Drill clearance holes in the damper flange at 150mm
centres.
2.
Install the damper and fix through flange using fire
rated fasteners, min ø4mm.
3.
Back fill between damper casing and wall, with mine
-
ral/stone wool and pattress over this down to the
spigot. Fasten pattress with fire rated fasteners, min
ø4mm. at 300mm centres.
4. Note: Dampers supplied with cleats welded to top
flange to assist with installation only.
5. Connecting ductwork omitted for clarity. Ductwork
must be independently supported. There must be an
appropriate break-away joint between the damper and
connecting ductwork on both sides of assembly. Alu-
minium rivets or plastic cleats, clips, clamps and bolts
etc. should be used for this, unless fire resisting duct-
work is being used where fire resisting fixings should
be used. A minimum of 200 mm between fire dampers
installed in separate ducts and 75 mm between fire
damper and a construction element (wall/floor).
6. For SmokeShield installations, please reference the
actuator installation information on page 11.
Comments:
Rev:
Drawn By:
M. Bushell
Approved By:
S. Wehrle
1 of 1
Reference No:
S. Gore
Date:
Date:
By:
Date:
23/08/18
21/08/18
23/08/18
Date:
.
Checked By:
Sheet
Rev
AAF12493
Description:
If your proposed installation details differ from
that shown here, please discuss this with the
Building Control Authority (BCA), referencing
this documentation, associated fire tests,
assessments, and other documentation shown
below. Deviation from this drawing requires
the approval of the relevant authority.
Installation Detail
Connecting ductwork omitted for clarity.
Ductwork must be independently supported.
There must be an appropriate break-away
joint between the damper and connecting
ductwork on both sides of assembly.
Aluminium rivets or plastic cleats, clips,
clamps and bolts etc. should be used for this,
unless fire resisting ductwork is being used
where fire resisting fixings should be used. A
minimum of 200 mm between fire dampers
installed in separate ducts and 75 mm
between fire damper and a construction
element (wall/floor).
³ stone wool
© Swegon Air Management Limited
South Street, Whitstable, Kent CT5 3DU
Tel: +44 (0)1227 276100
Fax: +44 (0)1227 264262
www.swegonair.co.uk
Applicable Test Report to
BS EN1366-2:
BRE 256493
MINUTES
ES 120
Fire Resistance
Integrity and Leakage
.
EC1879
MJB 23-08-18
Damper Size Range (mm)
VERTICAL APPLICATION
SMOKE DWFX-F WITH
PATTRESS IN MASONRY WALL
200 X 200 to 1000 x 1000
VERTICAL BLADES;
Damper can be installed with the blades
in the vertical orientation with the
actuator mounted at either the top or
bottom. For cleat