One metre of halogen free low smoke and fume electric cable is fitted to each control mode for convenience of onsite wiring. This provides 
the distinct safety advantage of all electrics terminating outside the duct, eliminating potential in-duct fire hazards from wiring faults. The 
Electrical Thermal Release is prewired with 0.5m halogen free low smoke and fume cabling to Control Modes 5 and 6. 
A Manual test switch fitted on the ETR allows periodic operation of damper, simulating actual fail-safe release under smoke/fire conditions.

Control Mode Wiring Procedure 

If integrating this unit with an Actionpac damper control system (LNS, EMS or EMB) please refer to the relevant catalogue and specific 
project details.

 

WHITE (2)

BLACK (1)

1

2

3

4

5

6

_

+

SUPPLY 24V A.C. or D.C.
TYPICALLY 10W (MOTORING
2W (RESET)

COMMON

CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED

COMMON

VOLT FREE CONTACT

MADE BETWEEN 1 & 2

WHEN DAMPER

FULLY RELEASED

VOLT FREE CONTACT

MADE BETWEEN 4 & 6

WHEN DAMPER

FULLY RESET

M

AC/DC 24V

50 / 60 Hz

12.5 VA

10 / 2 W

Imax

8.3A @ 5ms

-30°C...+50°C

CONTINUOUS

Smoke Shield Mode 5 PTC

(24V System)

Supply on - Damper motors open
Supply off - Damper spring close

Electrical thermal release (ETR)
(Must be fitted to ducting for

damper operation)

Spring close time ˜  22 seconds
Motor open time ˜  60 seconds

(Connect 24V via a safety
isolating transformer.)

IP54 rated

Smoke Shield Mode 6 PTC

(230V System)

Supply on - Damper motors open
Supply off - Damper spring close

Electrical thermal release (ETR)
(Must be fitted to ducting for

damper operation)

Spring close time ˜  22 seconds
Motor open time ˜  60 seconds

(To isolate from main power
supply, the system must
incorporate a devise which
disconnects the phase
conductors, with at least 3mm
contact gap)

120V A.C. version available

IP54 rated

ELECTRICAL THERMAL RELEASE (ETR)
(MUST BE FITTED TO DUCTING FOR
DAMPER OPERATION).

(SPRING BIASED TEST SWITCH)

TF 72°C

AC

250V

6(3)A

BROWN

BLUE

1

2

3

4

5

6

L1

SUPPLY 230V AC 50/60Hz
TYPICALLY 12W (MOTORING
4W (RESET)

COMMON

COMMON

VOLT FREE CONTACT

MADE BETWEEN 1 & 2

WHEN DAMPER

FULLY RELEASED

VOLT FREE CONTACT

MADE BETWEEN 4 & 6

WHEN DAMPER

FULLY RESET

M

AC/DC 24V

50 / 60 Hz

14 VA

12 / 4 W

-30°C...+50°C

CONTINUOUS

ELECTRICAL THERMAL RELEASE (ETR)
(MUST BE FITTED TO DUCTING FOR
DAMPER OPERATION).

(SPRING BIASED TEST SWITCH)

TF 72°C

AC

250V

6(3)A

N

CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN

CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED

CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN

CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED

CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN

CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED

CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN

Smoke Shield Mode 5-3P PTC

(24V System)

Supply on - Damper motors open
Supply off - Damper spring close

The M5-3P-1 is controlled by a
standard 0...10V control signal.
The actuator motors to the

position specified by the control

signal. If the ETR is activated,

power supply lost or removed the

device springs the damper to the
fail-safe position.

Electrical thermal release (ETR)
(Must be fitted to ducting for

damper operation)

Spring close time ˜  16 seconds
Motor open time ˜  120 seconds

The SiHF connecting cable

needs to be protected from sharp
edges.

(Connect 24V via a safety
isolating transformer.)

IP54 rated

1

2

3

4

5

6

COMMON

COMMON

VOLT FREE CONTACT

MADE BETWEEN 1 & 2

WHEN DAMPER

FULLY RELEASED

VOLT FREE CONTACT

MADE BETWEEN 4 & 6

WHEN DAMPER

FULLY RESET

ELECTRICAL THERMAL RELEASE (ETR)
(MUST BE FITTED TO DUCTING FOR
DAMPER OPERATION).

(SPRING BIASED TEST SWITCH)

TF 72°C

AC

250V

6(3)A

CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED

CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN

CONTINUITY WITH 'COMMON'
WHEN DAMPER CLOSED

CONTINUITY WITH 'COMMON'
WHEN DAMPER OPEN

WHITE (5)

WHITE (3)

Y DC 0...10V

U DC 2...10V

AC/DC 24V

50 / 60 Hz

9.5 VA

7 / 2.5 W

Imax

8.3A @ 5ms

-30°C...+50°C

CONTINUOUS

M

RED (2)

BLACK (1)

_

+

SUPPLY 24V A.C. or D.C.
TYPICALLY 6W (MOTORING
2W (HOLDING)

~

T

DIAGRAMS SHOWS ACTUATOR IN FULLY CLOSED STATE

NOTE THAT THE FOR INTERMEDIATE
POSITIONS, NEITHER OF THE
CONDITIONS BELOW WILL BE TRUE.

 

Summary of Contents for SmokeShield PTC

Page 1: ...ion for the Electrical Thermal Release ETR to be mounted through the ductwork Ideally this should be in the top half of the duct and or above the level of the interface Apply the self adhesive template located on the rear of the ETR and drill the necessary holes Ø3mm Ø9 5 Ø11mm Push the ETR through the duct and ensure that both screws are used to hold it in position Both screws should be tightened...

Page 2: ...TF 72 C AC 250V 6 3 A BROWN BLUE 1 2 3 4 5 6 L1 SUPPLY 230V AC 50 60Hz TYPICALLY 12W MOTORING 4W RESET COMMON COMMON VOLT FREE CONTACT MADE BETWEEN 1 2 WHEN DAMPER FULLY RELEASED VOLT FREE CONTACT MADE BETWEEN 4 6 WHEN DAMPER FULLY RESET M AC DC 24V 50 60 Hz 14 VA 12 4 W 30 C 50 C CONTINUOUS ELECTRICAL THERMAL RELEASE ETR MUST BE FITTED TO DUCTING FOR DAMPER OPERATION SPRING BIASED TEST SWITCH TF ...

Page 3: ...010 SMOKE SHIELD PTC LEAKAGE RATED SS I F E120 ve ho i o S SS DWFX C SS DWFX F SS OSW E120 ve i o S SS S A E120 ve i o S E120 ho i o E90 ho i o S Sensing element Response temperature 72 C Load Bearing capacity N A Closure times M5 6 22s tamb 20 C M5 3P 16s tamb 20 C Corrosion tested to En 60068 2 52 Pass Operational reliability 20 000 cycles Pass Ambient leakage test Pass LPS 1162 Issue 4 Cert No ...

Page 4: ...ot over tighten The mode is incorrectly wired Check wiring in accordance with procedures The ETR cables have been damaged or tampered with Replace with new mode Control Mode operates but limited or no movement of damper blades is observed The mode is not correctly synchronised with the interface Remove motor from interface Check motor in fully released state Set position of interface and refit mot...

Reviews: