Commissioning

The procedure detailed under periodic maintenance 

should be followed

Periodic maintenance 

As detailed in BS 9999:2008
1. For dampers this is at least once per year for  

units with spring operation.
2. Units operating in dust laden atmospheres,  

should be checked more often to suit the severity  

of the conditions
3. Units associated with systems may be required  

to be checked, as part of the system, as often 

as once per week or month to ensure ongoing 

confidence in the life safety system. This may  

be seen as analogous to fire alarm systems.

Procedure

1. The units should be carefully inspected and 

cleaned of dust and debris
2. The units should then be lubricated with a light  

oil, by wiping this over all the surfaces
3. The mode should be operated to ensure that it 

is moving the blades from open to closed and the 

reverse.
4. If the end switches (in the mode) are being used, 

it should be checked that they are actually indicating 

that the blades are open or closed. This is done  

by running a cycle and checking both the blades  

(open and closed) and the indication that the  

micro switches are feeding back to.

Actuator fitting (If required)

The control mode/actuator should be fitted in 

accordance with the documentation supplied with it.