Installation and Commissioning Guide - Classic 2 Split Ducted Outdoor Unit
Doc. No.0525-073 Ver. 8 210414
Installation and Commissioning Guide
Classic 2 Outdoor Units
34
16. Control Source Configuration (CtrS)
diS
(Display)
Display system's status and settings
SEr
(Service)
Service use only
SEt
(Settings)
CoPS
Compressor Type and Capacity:
F = Fixed Speed - (kW capacity) (default)
d = Digital - (kW capacity)
I = Inverter - (kW capacity)
CtrS
Control Source:
0 = Third Party
1 = Wall Controller (default)
2 = Basic BMS
3 = Wall Cont Basic BMS
4 = Advanced BMS
5 = Add-on Cooling
bAud
IDU-ODU Baud Rate:
4800 = AMIB
9600 = InZone/CMIB (default)
MENU
Scroll through the items at the same
menu level.
Increment the value being set.
ENTER
Go into the selected menu.
Lock in selected value.
BACK
Go back to the parent menu.
Press and hold to go back to main
menu
DISPLAY
MENU
ENTER
BACK
Outdoor Board
Configurable settings are as follows:
Third Party Control
The unit can be controlled by non-ActronAir wall controller. To do this,
CtrS
on the Outdoor Board must be set to
0
. For
connection details, see the wiring diagram supplied with the outdoor unit.
Wall Controller
ActronAir offers NEO, LR7-1 and LC7-2, a wall controller that can control the available features and maximise the function and
operation of the ActronAir airconditioner. To do this,
CtrS
on the Outdoor Board must be set to
1
.
Basic BMS
The unit can be connected to a network through a BMS card (ICUNO-MOD). This allows the unit to be operated in the same
way the as the NEO, LR7-1 and LC7-2 does. To do this,
CtrS
on the Outdoor Board must be set to
2
.
Wall Cont Basic BMS
The unit can be connected to a network (Basic BMS) and at the same time be controlled using the NEO, LR7-1 or LC7-2
controller. Priority will be given to the most recent command. To do this,
CtrS
on the Outdoor Board must be set to
3
.
Advanced BMS
The unit can be connected for system that requires customised functions not included in the existing software or logic in the
Outdoor Board Controller but still retaining the safety logic. To do this,
CtrS
on the Outdoor Board must be set to
4
.
Add On Cooling
ActronAir offers Add On Cooling models. This control source allows connection to an additional third-party heating system.
To do this,
CtrS
on the Outdoor Board has to be set to
5
.
Auto Fan Function
Auto fan function can only be commissioned by ActronAir wall control such as NEO, LR7-1 and LC7-2.