4
CP05 - CP10 Control Interface Insert
Doc. No.0525-035
Ver. 6 220307
CP05 & CP10 CONTROL INTERFACE INSTALLATION GUIDE
SPECIFICATIONS:
Esc
Prg
Control Interface (CP10) Technical Specifications:
Display
Type:
FSTN graphic
Backlighting:
White LEDs (controlled by application software), depending on cod.
Graphic resolution:
132x64 pixel
Text mode:
8 rows x 22 columns (font sizes 5x7 and 11x15 pixels)
4 rows x 11 columns (font size 11x15 pixels)
or mixed modes
Character height:
3.5mm (font 5x7 pixels)
7.5mm (font 11x15 pixels)
Size of active area:
66x32mm
Size of display area:
72x36mm
Keypad LEDs / Buzzer
2 programmable by application software,red and orange ("
Prg"
and " " buttons)
4 green LEDs, used as backlighting for LCD ("
",
"
",
"
"
and "
Esc"
buttons)
Buzzer (optional)
Power supply
Voltage:
Power supply from OD Controller through telephone cable or ext. source
18/30 VDC protected with 2 250 mAT fuse
Maximum power input:
0.8W
Maximum cable length
(Note: To reach the maximum length, use a bus layout with branches not exceeding 5m)
Maximum pLAN length:
500m with 6 Core (3 Pair) Twisted Pair 7/0.20 (AWG24) Shielded Data Cable
Max. OD Controller terminal distance:
50m with 6 Core Flat 7/0.12 (AWG28) Telephone Cable
500m with 6 Core (3 Pair) Twisted Pair 7/0.20 (AWG24) Shielded Data Cable
Materials
Transparent front panel, cover glass/frame:
Transparent polycarbonate
Charcoal grey container back piece
(wall / built-in):
Polycar ABS
Keypad:
Silicon rubber
Self extinguishing classificaion:
V0 for transparent front panel and back piece.
HB for silicon keypad and remaining parts
Others
Index of protection:
IP65 for panel mounting, IP40 for wall mounting, UL type 1
Operating conditions:
-20 to 60
o
C, 90% RH non-condensing
Storage conditions:
-20 to 70
o
C, 90% RH non-condensing
Software class and structure:
A
Classification according to protection
against electric shock:
To be integrated into class 1 or 2 devices
PTI of insulating materials:
PCB: PTI 250; insulation material PTI 175
Period of elect stress across insul. parts
Long period
Category of resistance to fire and heat:
D
Immunity against voltage surges:
Category II
Environmental pollution:
2