8
CP05 - CP10 Control Interface Insert
Doc. No.0525-035
Ver. 6 220307
CP05 & CP10 CONTROL INTERFACE INSTALLATION GUIDE
RJ12 Terminal Connections B:
•
Terminal 1:- Connect to +Vdc on the connector block.
•
Terminal 2:- Connect to GND on the connector block.
•
Terminal 3:- Connect to RX-/TX- on the connector block.
•
Terminal 4:- Connect to RX+/TX+ on the connector block.
•
Terminal 5:- Connect to GND on the connector block.
•
Terminal 6:- Connect to +Vdc on the connector block.
Twisted Pair
Twisted Pair
Twisted Pair
RJ12 Terminal Connections A:
•
Terminal 1:- Connect to +Vdc on the connector block.
•
Terminal 2:- Connect to GND on the connector block.
•
Terminal 3:- Connect to RX-/TX- on the connector block.
•
Terminal 4:- Connect to RX+/TX+ on the connector block.
•
Terminal 5:- Connect to GND on the connector block.
•
Terminal 6:- Connect to +Vdc on the connector block.
DATA CABLE AND RJ12 PLUG PREPARATION:
Option 1 - Data Cable with RJ12 plug at both end:
Option 2 - Data Cable with RJ12 plug at one end
(For Secondary Control Interface)
:
See RJ12 Terminal Connections B below.
RJ12 Plug
(
Installer to Provide
)
RJ12 Plug
(
Installer to Provide
)
VIEW
FROM CABLE END
VIEW
FROM CABLE END
6 Core (3 Pair) Twisted Pair 7/0.20 (AWG24) Shielded Data Cable
200 Max. Length - Field Scope
(
Installer to Provide
)
6
5
4
3
2
1
6
5
4
3
2
1
6 Core Flat 7/0.12 (AWG28) Telephone Cable
50m Max. Length - Field Scope
(
Installer to Provide
)
See RJ12 Terminal Connections A below.
RJ12 Plug
(
Installer to Provide
)
RJ12 Plug
(
Installer to Provide
)
VIEW
FROM CABLE END
VIEW
FROM CABLE END
6
5
4
3
2
1
6
5
4
3
2
1
3
2
1
6
5
4
6 Core Flat 7/0.12 (AWG28) Telephone Cable
50m Max. Length - Field Scope
(
Installer to Provide
)
RJ12 Plug
(
Installer to Provide
)
VIEW
FROM CABLE END
6
5
4
3
2
1
To
CM100
or uPC
11
12
13
14
TERMINAL 12
RX- / TX-
TERMINAL 13
+Vdc
TERMINAL 11
RX
+
/ TX
+
ELECTICAL
PANEL
TERMINAL 14
GND
See RJ12 Terminal Connections A below.
RJ12 Plug
(
Installer to Provide
)
VIEW
FROM CABLE END
6
5
4
3
2
1
6 Core (3 Pair) Twisted Pair 7/0.20 (AWG24) Shielded Data Cable
200 Max. Length - Field Scope
(
Installer to Provide
)
3
2
1
6
5
4
See RJ12 Terminal Connections B below.
11
12
13
14
TERMINAL 12
RX- / TX-
TERMINAL 13
+Vdc
TERMINAL 11
RX
+
/ TX
+
ELECTICAL
PANEL
TERMINAL 14
GND
19 20 21 22
NOTE:
Use these terminals for
Tri-Capacity models.
To
CM100
or uPC