Operation Manual - Hercules CP10 Commercial Control Interface
Doc. No. 0525-022
Ver. 5 190314
... SETTING SUPPLY AIR VOLUME SETPOINT ...
1. Press
“
Prg
”
Button to get into the Main
Menu. Display will show Main Menu
and highlighted Sub-Menu
A. On / Off
Unit
.
2. Press
“ ”
Button to scroll down into
G.
Service
sub-menu.
3. Press
“ ”
Button to lock-in
G. Service
sub-menu. “
Service menu Ga
” (
a.
Change Language
) screen will appear.
4. Press
“ ”
or “ ”
Button to get into “
Service menu Gf
” (f. Service settings sub-menu).
5. Press
“ ”
Button
to lock-in
“
Service menu Gf
”
.
Note
: Service menu is password protected, enter "7378" for access
.
6. “
Service menu Gfa
” (a. Working hour set) screen will appear. Press
“ ”
Button to scroll down
into
c. Thermoregulation
.
7. Press
“ ”
Button
to lock-in
c. Thermoregulation
sub-menu.
Note
: “
Thermoregulat. Gfc1
” screen will appear.
8. Press
“ ”
Button to get into “
Thermoregulat. Gfc4
” screen .
9. Press
“ ”
Button to lock-in “
Thermoregulat. Gfc4
” sub-menu and the “ ” cursor will appear
next to Supply Air Volume Setpoint.
10. Press
“ ” or “ ”
Button to change Supply Air Volume Setpoint and then press
“ ”
Button to
lock-in the setting.
Note
: The Supply Air Volume Setpoint
can be changed with an incremental/decremental
value of 1L/s.
TO RETURN TO THE MAIN MENU
11. Keep
pressing
“
Esc
”
(Escape/Return) Button until you get to the Main Menu screen. Otherwise
press
“
Prg
”
Button.
Esc
Prg
Filter Pressure Alarm
Setpoint: 300Pa
Supply Air Volume
Setpoint: 8850L/s
Apply changes now ? : No
Thermoregulat. Gfc4