Installation and Commissioning Guide
Hercules Package Unit
41
Installation and Commissioning Guide - Hercules Package Unit
Doc. No.0525-021
Ver. 21 221110
17. Control Menu
17.01. Menu Navigation
Esc
Prg
Comp
Rev Vlv
10:20 Unit: OFFbyKEY
External Inputs
Compressor:
Indoor Fan:
90.5%
92.6%
Example
below will show the navigation to
Gfc4. Thermoregulat
.
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc4. Thermoregulat.
Step 1. To get into the main menu in the control interface, press
Prg
. The display will show the list of available sub
menus. Press or button to scroll through the sub menus and select
G. Service.
Press to enter the sub
menu.
A. On / Off Unit
B. Setpoint
Main Menu A
C. Mode of Operation
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Step 2. Press or button to scroll to menu
Gf. Service settings
then press .
Press or button to scroll to menu
Gfc. Thermoregulation
then press .
Service Menu Gf
d. Working hours
f. Service settings
e. Communicate confi g.
a. Working hour set
b . Probe adjustment
c . Thermoregulation
Service Menu Gfc
Step 3. Press or button to scroll to menu
Gfc4 Thermoregulat.
then press .
Set the fi elds based on desired confi guration.
Supply Air Volume
Notifi cation:
125Pa
Setpoint :
7400L/s
Enabled:
Yes
Filter Pressure
Alarm:
150Pa
Thermoregulat. Gfc4
17.02. Service Password
To access the Service Settings pages, a password is required: 7378
G. Service
Gf. Service settings
Change password to 7378
Service Password
Insert service
password (PW1) :
7378
WARNING
Unauthorized access to Service Menu and inadvertent changes to the settings can cause damage to the air conditioning system
which will render ActronAir warranty null and void.