background image

PRELIMINARY DATA ONLY  Ver. 5.01  210406
THIS LABEL TO BE REMOVED ON SIGN-OFF

  

48

Installation and Commissioning Guide- Package Ducted Variable Capacity Commercial

Doc. Part No. 0525-067   Ver. 5  210414

Installation and Commissioning Guide

Variable Capacity Commercial

17.04.  PKV330T-L/R

 APPLICATION RANGE (COMPRESSOR ON)

AIRFLOW

(l/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

250

300

% PWM

W

% PWM

W

% PWM

W

% PWM

W

% PWM

W

% PWM

W

1400

 46 

 536 

 50 

 640 

 55 

 780 

 58 

 876 

 62 

 1002 

 71 

 1168 

1450

 49 

 587 

 53 

 694 

 57 

 810 

 61 

 939 

 65 

 1081 

 76 

 1239 

1500

 52 

 637 

 56 

 747 

 60 

 867 

 64 

 1005 

 68 

 1128 

 79 

 1294 

1550

 55 

 686 

 59 

 801 

 63 

 933 

 67 

 1068 

 71 

 1190 

 83 

 1355 

1600

 58 

 739 

 62 

 862 

 66 

 995 

 70 

 1125 

 74 

 1257 

 89 

 1430 

1650

 61 

 792 

 65 

 925 

 69 

 1051 

 73 

 1188 

 78 

 1330 

 93 

 1504 

1700

 64 

 855 

 68 

 980 

 73 

 1143 

 77 

 1275 

 83 

 1420 

 97 

 1579 

1750

 67 

 912 

 72 

 1067 

 76 

 1198 

 81 

 1357 

 87 

 1494 

1800

 71 

 993 

 75 

 1122 

 80 

 1,282 

 84 

 1431 

 93 

 1583 

1850

 74 

 1047 

 79 

 1205 

 83 

 1349 

 88 

 1513 

 99 

 1682 

1900

 78 

 1129 

 82 

 1265 

 87 

 1450 

 93 

 1619 

MOTOR / BLOWER LIMIT

1950

 82 

 1218 

 86 

 1365 

 91 

 1542 

 97 

 1703 

2000

 84 

 1247 

 90 

 1458 

 95 

 1634 

2050

 89 

 1373 

 94 

 1544 

2100

 93 

 1457 

 99 

 1660 

 REDUCED AIRFLOW (COMPRESSOR OFF)

AIRFLOW

(l/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

250

300

% PWM

W

% PWM

W

% PWM

W

% PWM

W

% PWM

W

% PWM

W

350

 21 

 326 

400

 20 

 293 

 22 

 338 

450

 21 

 302 

 24 

 379 

500

MOTOR / BLOWER LIMIT

 20 

 261 

 23 

 335 

 26 

 406 

550

 22 

 295 

 25 

 365 

 27 

 420 

600

 20 

 235 

 24 

 324 

 26 

 373 

 29 

 454 

650

 22 

 265 

 25 

 329 

 28 

 406 

 31 

 481 

700

 20 

 209 

 24 

 293 

 27 

 363 

 30 

 435 

 33 

 517 

750

 22 

 237 

 25 

 299 

 29 

 391 

 32 

 468 

 35 

 549 

800

 23 

 244 

 27 

 329 

 31 

 423 

 34 

 501 

 37 

 584 

850

 21 

 192 

 25 

 268 

 29 

 357 

 33 

 454 

 36 

 533 

 39 

 619 

900

 23 

 216 

 27 

 297 

 31 

 386 

 35 

 482 

 38 

 567 

 42 

 675 

950

 25 

 238 

 29 

 323 

 33 

 414 

 37 

 516 

 41 

 628 

 44 

 712 

1000

 27 

 264 

 31 

 349 

 36 

 467 

 39 

 548 

 43 

 659 

 47 

 762 

1050

 29 

 288 

 33 

 374 

 38 

 498 

 41 

 580 

 45 

 690 

 50 

 818 

1100

 31 

 312 

 36 

 424 

 40 

 529 

 44 

 638 

 48 

 742 

 53 

 862 

1150

 34 

 357 

 38 

 454 

 42 

 559 

 46 

 666 

 51 

 798 

 55 

 914 

1200

 36 

 383 

 40 

 482 

 44 

 588 

 49 

 719 

 53 

 841 

 58 

 946 

1250

 38 

 411 

 42 

 511 

 47 

 641 

 51 

 751 

 55 

 874 

 60 

 983 

1300

 41 

 461 

 45 

 562 

 49 

 668 

 54 

 813 

 57 

 903 

 64 

 1049 

1350

 43 

 487 

 48 

 615 

 52 

 725 

 56 

 844 

 59 

 944 

 67 

 1103 

NOTES:

*

Reduced fan airflow is the airflow during compressor OFF operation (optional feature)

W

 = Indoor Fan Power, Watts

PWM

 = Pulse Width Modulation Setting, % PWM (Adjustable through NEO / LC7-2 Control Interface or Outdoor Board)           

Default Fan Speed Value

Speed

Default PWM

Indoor Fan PWM Limits

High PWM (%)

92 (adjustable)

High PWM (%)

99

Medium PWM (%)

67 (adjustable)

Low PWM (%)

42

Low PWM (%)

47 (adjustable)

Summary of Contents for PKV290T-L

Page 1: ... That s Actron Variable Capacity Commercial Package Ducted Units Installation and Commissioning Guide PACKAGE MODELS UNDER OVER CONFIGURATION SIDE BY SIDE CONFIGURATION PKV290T T PKV330T T PKV290T L R PKV330T L R Left Air Handing Option shown for illustration purposes only Left Air Handing Option Right Air Handing Option ...

Page 2: ...3 03 Wiring Configuration 2 Alternate 24 14 Wiring Connections 25 14 01 LC7 2 Wall Control Wiring Connections 25 14 02 NEO Wall Control Wiring Connections 25 14 03 LM RS 2 Optional Sensor Wiring Connections 26 14 04 AERSS Optional Duct Sensor Wiring Connections 26 15 Configuring and Commissioning Setup 27 15 01 Menu and Navigation 27 15 02 Configuring Compressor and Capacity cnFg 27 15 03 Configur...

Page 3: ...performance high efficiency reliability supply air quality and quiet operation are the prime priorities The units are built with the latest technology advanced variable speed driven compressor EC indoor fans on specific models low noise outdoor fans and an intelligent electronic control For optimum efficiency your air conditioning unit will deliver the right amount of cooling or heating capacity t...

Page 4: ...hould install and service this air conditioning equipment Improper service or alteration by an unqualified technician could result in significant and major damage to the product or property which may render your warranty null and void Such unqualified service could also lead to severe physical injury or death Follow all safety instructions in this literature and all warning labels that are attache...

Page 5: ...ases Recover and Recycle Refrigerants Never release refrigerant to the atmosphere It is an offence in Australia to do so Always recover recycle and reuse refrigerants When removing from the system properly contain and identify refrigerants in its dedicated container for proper disposal and or storage Always consider the recycle or reclaim requirements of the refrigerant before beginning the recove...

Page 6: ...ge Condenser air inlet located on the coil side of the unit requires sufficient airflow clearance for the optimum unit performance Note the conditioned supply air and return air location Ensure sufficient spaces are allocated for these purposes Refer connection and location of condensate drain in the unit drawing and dimensions section of this manual Wiring connections must be in accordance with t...

Page 7: ...mercial Doc Part No 0525 067 Ver 5 210414 06 Components Overview PACKAGE UNIT COMPONENTS OVERVIEW Left Hand LH Side By Side Configuration shown for illustration purposes only GRILLE PANEL ACCESS EVAP REAR PANEL INDOOR FANS OUTDOOR FANS CONDENSER COIL ASSEMBLY ACCESS EVAP FRONT PANEL LP SWITCH SCROLL COMPRESSOR CRANKCASE HEATER EVAPORATOR COIL ASSEMBLY ELECTRICAL PANEL HP SWITCH ACCESS PANEL COMP E...

Page 8: ...uide Variable Capacity Commercial OUTDOOR UNIT ELECTRICAL PANEL OVERVIEW FANSPEED CAPACITORS EARTHING BOLTS WITH WASHERS AND NUTS OUTDOOR UNIT CONTROL BOARD CONDENSER MAINS INPUT TERMINAL BLOCKS PFC CAPACITOR CONTROL CIRCUIT BREAKER POWER FACTOR CONTACTOR FAN CIRCUIT BREAKERS CONDENSER FAN CONTACTORS FIRE TRIP TERMINAL BLOCKS 3 PHASE PROTECTION RELAY COMPRESSOR OVERLOAD AND CONTACTOR EMC FILTERS C...

Page 9: ...nsions are in mm unless specified Refer to corresponding unit dimensional drawing for mounting hole details 2 Service Access Areas and Spaces for Airflow Clearances given are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkway passage of 1000mm between the units or between the unit and the outside perimeter is available 3 Minimum s...

Page 10: ...OOR FANS ID COIL 800 mm SERVICE CLEARANCE COMPRESSOR AND ELECTRICAL 300 mm SERVICE CLEARANCE AND AIRFLOW ALLOWANCE DUCT WORK HEIGHT CLEARANCE 1500 mm 750 mm SERVICE CLEARANCE AND AIRFLOW ALLOWANCE D B A C YY XX CG NOTE Under all circumstances Condenser Air must not recirculate back onto Condenser Coil Keep all clearances free of any obstructions Base Mounting Details 64 1840 64 1409 64 64 76 692 5...

Page 11: ...sions are in mm unless specified Refer to corresponding unit dimensional drawing for mounting hole details 2 Service Access Areas and Spaces for Airflow Clearances given are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkway passage of 1000mm between the units or between the unit and the outside perimeter is available 3 Minimum se...

Page 12: ...RESSOR AND ELECTRICAL 300 mm SERVICE CLEARANCE AND AIRFLOW ALLOWANCE DUCT WORK HEIGHT CLEARANCE 1500 mm 750 mm SERVICE CLEARANCE AND AIRFLOW ALLOWANCE D B A C OUTDOOR COIL COMP INDOOR COIL INDOOR FANS YY XX CG NOTE Under all circumstances Condenser Air must not recirculate back onto Condenser Coil Keep all clearances free of any obstructions Base Mounting Details 64 1840 64 1409 64 64 76 692 513 U...

Page 13: ...ions are in mm unless specified Refer to corresponding unit dimensional drawing for mounting hole details 2 Service Access Areas and Spaces for Airflow Clearances given are suggested minimum based on the condition that the spaces around the units are free from any obstructions and a walkway passage of 1000mm between the units or between the unit and the outside perimeter is available 3 Minimum ser...

Page 14: ...RESSOR AND ELECTRICAL 300 mm SERVICE CLEARANCE AND AIRFLOW ALLOWANCE DUCT WORK HEIGHT CLEARANCE 1500 mm 750 mm SERVICE CLEARANCE AND AIRFLOW ALLOWANCE D B A C INDOOR FANS INDOOR COIL OUTDOOR COIL COMP YY XX CG NOTE Under all circumstances Condenser Air must not recirculate back onto Condenser Coil Keep all clearances free of any obstructions Base Mounting Details 64 1840 64 1409 64 64 76 692 513 U...

Page 15: ...erved and will take precedence during lifting process Crane Lifting Method Note Crane lifting method is recommended for high rise lifting Fig 1 Connect the loop ends of slings into shackle Provide rubber pads to prevent damage to the unit RUBBER PADS LIFTING POINT Lifting point is located at each corner of the unit 4 Total Size Ø17 5 mm EQUIPMENT REQUIRED FOR CRANE LIFTING 1 x Shackle 2 x Nylon Sl...

Page 16: ...equipment accessories and plant are sufficiently and safely capable to lift the unit in order to prevent potential damage to property severe personal injury or death Check unit weight and weight distribution points on unit drawing dimensions section NOTES Lifting procedure and unit model shown are suggestions and for illustration purposes only It is highly recommended that installer observe curren...

Page 17: ...mmercial Doc Part No 0525 067 Ver 5 210414 09 Outdoor Unit Preparation NOTE It is important to remove the shipping blocks before unit operation Step 1 Remove Access Panel as shown below Access Panel Use allen keys to remove the Access Panel Hex Recess 8mm Remove access panel Do not disconnect Earth Cable B Removal Order Pull Out 20mm Pull Down to remove Access Panel Electrical A B A Earth Cable Re...

Page 18: ... and Commissioning Guide Variable Capacity Commercial Step 2 Remove Shipping Blocks Loosen the set bolts that hold the compressors down onto the unit 4 pcs Slide out shipping block as shown below Loosen Bolts 4 pcs Comp Shipping Blocks GENTLY Push back the Compressor Pull away the Shipping Blocks Step 3 Tighten back the set bolts that hold the compressors down onto the unit 4 pcs Tighten Bolts 4 p...

Page 19: ...nsure Drain Pipe slopes down from the unit at a minimum of 10mm per meter DETAIL A The top of the Trap must be 125mm below the top of the Evaporator Drain Connection 50mm 4 x PVC Elbow Install a T Piece as an Air Vent for long drain runs Hose Clamps Condensate Tray The top of the Vent must be 50mm higher than the top of the Evaporator Condensate Tray 250mm or high enough to maintain positive Air S...

Page 20: ...lations and all wiring connections to be as per electrical diagram provided with the unit Confirm that the power supply available is compatible with the unit nameplate ratings The supply power must be within 10 to 6 of the rated voltage as per AS60038 Protect electrical service from over current and short circuit conditions in accordance with the latest edition of the AS NZS 3000 Australian New Ze...

Page 21: ... WIRING DIAGRAM IS PROVIDED WITH THE UNIT Condenser Side Located at the back of electrical compressor access panel THREE PHASE MAINS WIRING 400 VAC Three Phase Neutral Earth 50Hz DATA CABLE TO WALL CONTROL Cat5E UTP AWG 24 Data Cable 1 2 WALL CONTROL SUB MAINS CIRCUIT BREAKER Field Supplied by Installer DATA CABLE Field Supplied by Installer 2 MAIN SUPPLY FROM DISTRIBUTION BOARD SUB MAIN TO UNIT S...

Page 22: ...ependent on installation method length of cables and ambient temperature Refer to the latest edition of the AS NZS 3000 Australian New Zealand Wiring Rules for more details 13 Maximum Cable Length 13 01 Wall Controller Options Maximum of three 3 wall controllers in below combinations is allowed on unit See below table Combinations Wall Controllers WC 1 WC 2 WC 3 1st Option NEO 2nd Option NEO NEO 3...

Page 23: ... OPTIONAL AERSS OPTIONAL NOTES Diagram shown above is a general representation only Refer to individual unit wiring diagram for complete wiring connection details Long runs beside Mains cables or TV antenna cables should be avoided where possible Daisy connection is not allowed for NEO wall controller Item Description Maximum Cable Length 1 to 2a 1 to 2b Indoor PCB to Wall Control 1 and 2 90 m 1 t...

Page 24: ...LL CONTROL 1 OPTIONAL NOTES Diagram shown above is a general representation only Refer to individual unit wiring diagram for complete wiring connection details Long runs beside Mains cables or TV antenna cables should be avoided where possible ITEM DESCRIPTION MAXIMUM CABLE LENGTH 1 to 2a Indoor PCB to Wall Control 1 optional 100 m 1 to 2c Indoor PCB to Wall Control 3 optional 75m total Daisy Chai...

Page 25: ...BR OR BL BL WH BR WH OR WH BR OR BL BL WH BR WH OR WH INDOOR CONTROL BOARD WALL CONTROL WIRING POWER BROWN ORANGE 485 A BLUE 485 B BLUE WHITE GND BROWN WHITE ORANGE WHITE NOT USED GREEN GREEN WHITE 14 02 NEO Wall Control Wiring Connections 14 02 01 NEO RJ45 Wiring WALL CONTROL TWC 1 12V A B G INDOOR CONTROL BOARD RJ45 WALL CONTROL TWC 2 12V A B G RJ45 WALL CONTROLLER 14 02 02 NEO Hard Wiring WALL ...

Page 26: ... PURPOSES ONLY CUT OFF AND TERMINATE ANY UNUSED PAIRS TO ENSURE NO WIRING IS LEFT EXPOSED REMOTE SENSOR WIRING PAIR 1 BLUE BLUE WHITE PAIR 2 ORANGE ORANGE WHITE NOT USED PAIR 3 GREEN GREEN WHITE NOT USED PAIR 4 BROWN BROWN WHITE 14 04 AERSS Optional Duct Sensor Wiring Connections AUX SENSOR AUX SENSOR S1 S1 COM COM S2 S2 INDOOR CONTROL BOARD INDOOR CONTROL BOARD REMOTE SENSOR WIRING PAIR 1 BLUE BL...

Page 27: ...not enabled default YES Soft Start enabled run no Indoor Fan and Compressor default YES Compressor only odFs Hi High Start up Speed default Lo Low Start up Speed DISPLAY MENU ENTER BACK OUTDOORBOARD Family and Capacity Table Model PKV290T PKV330T Family Capacity kW 02 29 33 MENU Scroll through the items at the same menu level Increment the value being set ENTER Go into the selected menu Lock in se...

Page 28: ...ng software or logic in the Outdoor Board but still retaining the safety logic To do this CtrS on the Outdoor Board has to be set to Ct 4 15 04 Configuring Indoor Fan Setting iduS The fan settings may be configured using three options the Condenser CPU Board NEO or LC7 2 Wall Control and Third Party Control NOTES For Configuring Indoor FAN Setting iduS using wall control please refer to respective...

Page 29: ... adjust the REDUCED AIRFLOW Setting EXIT Service Menu Enter Service Menu Select Menu 03 If required adjust the MED PWM of 3 Speed Setting If required adjust the MED RPM of 3 Speed Setting If required adjust the DEFROST FAN Setting If required adjust the HOT START FAN Setting Procedure 1 Press and hold the REPEAT and the TIMER buttons for 3 seconds then release to enter Service Menu 2 Press the but...

Page 30: ... PWM or accept the default setting 6 Display shows LOW MED HIGH 3 and FAN With LOW blinking to signify current LOW PWM settings for 3 speed fan Press the or buttons to adjust the PWM setting Then press the PROG button to accept NOTE Default setting and adjustable range may vary depending on indoor models 7 Next display will show the RPM setting for LOW SPEED Press the or buttons to adjust the RPM ...

Page 31: ...nge limits Refer to Section 15 for more details Option 3 Third Party Control 0 10V Fan 1 On the Outdoor Board set Control Source to Third Party Using the MENU and the ENTER buttons navigate to SEt Settings CtrS Control Source 2 Use the MENU button to navigate to 0 to select Third Party Control as the control source Press the ENTER button to save the setting 3 On the Indoor Board set the first dip ...

Page 32: ...sioning Guide Option 1 LC7 2 Wall Control 1 Press and hold the REPEAT and the TIMER buttons for 3 seconds then release to enter Service Menu The display will show the Service Menu 01 2 Press the or buttons to scroll to Service Menu 03 Press the PROG button to enter the Service Menu 03 3 Press the PROG button 9 x times to enter the Defrost Fan Settings 4 Press the or buttons to select the desired i...

Page 33: ...Reduced Airflow Settings 4 Press the or buttons to select the desired indoor fan PWM then press the PROG button to accept The available range is from 20 to 100 OFF means that this function is disabled The sample screen below shows the indoor fan is set to 30 PWM 5 Press the EXIT button once to go back to the original status display Option 2 Outdoor Unit CPU Board 1 Using the MENU and the ENTER but...

Page 34: ...Using the MENU and the ENTER buttons navigate to SEt Settings iduS Indoor Settings FiL Filter 2 Keep pressing the MENU button to select the desired filter notification alarm time is shown By default alarm time is set to 200 hrs and is adjustable from 0 to 9900 Note 0 means the Filter Alarm is disabled 3 Press ENTER button to confirm the alarm time settings 4 Press the BACK button twice to go back ...

Page 35: ...t 2 Keep pressing the MENU button to select the desired opening in voltage By default this is set to 0 damper closed Adjustable setting is from 0 to 10V Note that in LED 7 segment display 10 0V will show 100 3 Press ENTER to confirm the desired damper voltage Press BACK button to leave the Menu 4 Press the BACK button three times to go back to the original status display 15 04 07 Fan Continuous ON...

Page 36: ...icator Settings 2 If required press MENU to navigate to YES 16 Optional Output Input Relay 16 01 Filter Indication Relay Output CMI Board Allows for optional connection for Filter Indication Relay 10A 240V Option to use either normally open or normally close relay OPTIONAL FILTER INDICATION RELAY OUTPUT 240VAC 10A Max R This drawing remains the intellectual property of Actron Engineering Pty Ltd R...

Page 37: ...feature allows to set the optional outside air damper opening 0 10V To set up see 15 04 06 Economy Damper 0 10V OUTPUT 0 10V INPUT COM COM CMI POT ADJUST AMB SENSOR FILTER INDICATION FAN IN WALL CONTROLLER OUTDOOR AUX SENSOR ECON OUT AUX OUT AUX IN 12V 0 10V 12V COM COM A A S1 0 10V 0 10V B B COM COM COM G G S2 COIL TEMP DISPLAY PWR 0 10V FAN2 OUT 0 10V FAN1 OUT COM 1 COM 2 COM 3 12VDC POWER IN V ...

Page 38: ...AUX OUT AUX IN 12V 0 10V 12V COM COM A A S1 0 10V 0 10V B B COM COM COM G G S2 COIL TEMP PWR COM 1 COM 2 COM 3 12VDC POWER IN V V ZONE MASTER SECONDARY OFF ON PWM FAN OUTPUT INTERNAL FAN SPEED 1 2 3 4 5 6 7 8 STANDARD DIP SWITCH SETTINGS MANUAL FAN SPEED POT ADJUST OPTIONAL OUTSIDE AIR DAMPER CONTROL OUTPUT OPTIONAL 3RD PARTY FAN CONTROL INPUT HEAT 0 10V G COM 0 10VDC INPUT Input Output Compressor...

Page 39: ...TY COMPRESSOR CONTROL INPUT NOTE As the compressor turns ON and the Indoor fan signal is not available then indoor fan will start to run on medium PWM speed Indoor fan operation when fan signal is available Compressor ON Indoor fan will run on medium speed Compressor OFF Indoor fan will run on reduce airflow operation 16 04 03 Analogue Input for Fixed Compressor with Fixed Indoor Fan Speed This fe...

Page 40: ...allation procedure 2 Connect cables into terminals as shown above and as per wiring diagram provided with the unit DEMAND RESPONSE ENABLING DEVICE DRED CIRCUIT DIAGRAM ODU CPU BOARD DEMAND RESPONSE MANAGEMENT DRED AS4755 COMPLIANT DEVICE OPTIONAL DRED VOLTAGE FREE CONTACTS COM 12V DRM 1 HEAT DRM 2 FAN DRM 3 COMP Demand Management Mode Description Of Mode Allowable Range Operating Mode DRM1 Compres...

Page 41: ...ing in Wall Controller only control mode 1 or BMS Wall Controller control mode 3 for this function to work Turning the system On and Off by remote method Turning the system On Status 1 The system is Off and the remote switch relay has been left in the open position 1 Close remote switch relay 2 System will start in approximately 1 minute Status 2 The system is Off and the remote switch relay has b...

Page 42: ...106 77 1271 83 1414 99 1551 1800 66 877 70 1000 75 1163 79 1316 88 1497 REDUCED AIRFLOW COMPRESSOR OFF AIRFLOW l s EXTERNAL STATIC PRESSURE Pa 50 100 150 200 250 300 PWM W PWM W PWM W PWM W PWM W PWM W 350 21 333 400 20 295 23 372 450 MOTOR BLOWER LIMIT 22 331 24 381 500 21 291 23 340 26 408 550 22 301 25 371 28 439 600 20 242 23 310 27 406 30 480 650 22 274 25 341 28 418 32 521 700 23 282 26 351 ...

Page 43: ...RANGE 50 150 250 100 200 300 0 1300 1250 1500 1350 1550 1400 1600 1450 1650 1200 1800 1750 1700 3 0 P W M 4 0 P W M 3 5 P W M 4 5 P W M 5 5 P W M 6 0 P W M 6 5 P W M 7 0 P W M 7 5 P W M 8 0 P W M 8 5 P W M 9 0 P W M 9 5 P W M 9 9 P W M 5 0 P W M 52 PWM Notes 1 P erformance Fan Curve shown is at Dry Coil Condition 2 Airflow should be reduce with respect to the moisture content in the air 3 All data...

Page 44: ...LOW COMPRESSOR OFF AIRFLOW l s EXTERNAL STATIC PRESSURE Pa 50 100 150 200 250 300 PWM W PWM W PWM W PWM W PWM W PWM W 350 12 174 400 20 289 23 347 450 MOTOR BLOWER LIMIT 22 322 25 393 500 21 287 23 337 26 403 550 22 297 25 370 28 431 600 20 236 23 307 26 378 30 476 650 21 247 25 338 28 415 32 499 700 23 278 26 347 30 446 34 532 750 21 217 24 286 28 380 31 454 35 561 800 22 230 26 316 30 410 33 492...

Page 45: ...should be reduce with respect to the moisture content in the air 3 All data provided does not include filters Please review filter manufacturer for application 4 2 5 m s face velocity point will occur at 2150 l s AIRFLOW l s Nominal Airflow 1750 l s EXTERNAL STATIC PRESSURE Pa 67 PWM 50 150 250 100 200 300 0 1650 1600 1850 1700 1900 1750 1950 1800 2000 APPLICATION RANGE 1550 2100 2050 1500 1450 14...

Page 46: ...88 1505 1800 67 847 72 1003 76 1133 81 1305 85 1454 93 1582 REDUCED AIRFLOW COMPRESSOR OFF AIRFLOW l s EXTERNAL STATIC PRESSURE Pa 50 100 150 200 250 300 PWM W PWM W PWM W PWM W PWM W PWM W 350 21 266 400 20 280 23 297 450 22 315 24 366 500 MOTOR BLOWER LIMIT 21 273 23 320 26 390 550 22 281 25 348 28 431 600 21 244 24 308 27 383 29 437 650 22 252 25 314 28 389 31 466 700 20 198 24 279 27 347 30 41...

Page 47: ...flow should be reduce with respect to the moisture content in the air 3 All data provided does not include filters Please review filter manufacturer for application 4 2 5 m s face velocity point will occur at 2100 l s EXTERNAL STATIC PRESSURE Pa AIRFLOW l s Nominal Airflow 1500 l s APPLICATION RANGE 50 150 250 100 200 300 0 1300 1250 1500 1350 1550 1400 1600 1450 1650 1200 1800 1750 1700 8 0 P W M...

Page 48: ... AIRFLOW l s EXTERNAL STATIC PRESSURE Pa 50 100 150 200 250 300 PWM W PWM W PWM W PWM W PWM W PWM W 350 21 326 400 20 293 22 338 450 21 302 24 379 500 MOTOR BLOWER LIMIT 20 261 23 335 26 406 550 22 295 25 365 27 420 600 20 235 24 324 26 373 29 454 650 22 265 25 329 28 406 31 481 700 20 209 24 293 27 363 30 435 33 517 750 22 237 25 299 29 391 32 468 35 549 800 23 244 27 329 31 423 34 501 37 584 850...

Page 49: ... 72 PWM 50 150 250 100 200 300 0 5 0 P W M 5 5 P W M 6 0 P W M 6 5 P W M 7 0 P W M 7 5 P W M 8 0 P W M 8 5 P W M 90 PW M 95 PW M 99 PW M 4 5 P W M 1650 1600 1850 1700 1900 1750 1950 1800 2000 APPLICATION RANGE 1550 2100 2050 1500 1450 1400 Notes 1 P erformance Fan Curve shown is at Dry Coil Condition 2 Airflow should be reduce with respect to the moisture content in the air 3 All data provided doe...

Page 50: ...ted to a label that is fixed to the unit for future reference CAUTION The system of this unit operates with POE oil that rapidly absorbs moisture The maximum time any system can be opened to atmosphere is 15 minutes REFRIGERANT CHARGE DETAILS R 410A Model Refrigerant Charge g PKV290T T 8 500 PKV330T T 10 800 PKV290T L R 9 000 PKV330T L R 12 600 SUBCOOLING AND SUPERHEAT CHARGING METHOD Parameters L...

Page 51: ...superheat is important for ensuring the evaporator is achieving maximum capacity and avoiding excessive liquid refrigerant returning to the compressor 1 From the R 410A Pressure Temperature Chart record the corresponding Saturated Suction Temperature SST at the given suction pressure 2 Calculate the system superheat using the formula below Superheat SLT SST 3 If superheat is within the range see c...

Page 52: ... 7 12 1050 9 44 2558 5 51 5 3 19 316 9 13 1084 7 45 2621 8 50 10 7 18 332 6 14 1119 2 46 2686 2 49 16 3 17 348 7 15 1154 6 47 2751 8 48 22 2 16 365 2 16 1190 7 48 2818 5 47 28 2 15 382 3 17 1227 5 49 2886 4 46 34 0 14 399 7 18 1265 2 50 2955 5 45 40 9 13 417 7 19 1303 6 51 3025 7 44 47 8 12 436 2 20 1342 9 52 3097 2 43 54 8 11 455 1 21 1382 9 53 3169 9 42 62 1 10 474 6 22 1423 9 54 3243 7 41 69 6 ...

Page 53: ...vertently energised Failure to disconnect power before maintenance procedures can result in serious injury and or death Annual Maintenance Checklists Perform general maintenance inspections Perform scheduled start up checks Leak test refrigerant circuits Inspect contacts of all contactors and relays Replace all worn contacts as required Inspect clean and tighten all electrical connections Check fa...

Page 54: ... coils Straighten bent coil fins with fin comb Prepare the detergent solutions according to the manufacturer s instructions Spray solution at a 90o angle to the coils keeping a minimum nozzle spray angle of 15o with at least a 1800mm distance from the coils and 600 psi pressure Spray leaving air side of the coils first then the air inlet side Allow the solution to stand on the coils for five minut...

Page 55: ...rosive environment wash panels quarterly with water and neutral detergent solution Wax panels Repair re paint where required Insulation Visual check for insulation conditions Repair replace insulation material Fan Visual check for run out of balance and dust attached Clean off dust as necessary to negate possibility of fan running out of balance Motor Ω Visual check on wiring Insulation resistance...

Page 56: ...sistance should be more than 1MΩ Heat Exchanger Check for clogging by dust Check for leaks damage Clean air inlet side as necessary Straighten any bent fins using fins comb Condensate Drain Line if available Check for obstructions and free flow of water Clean to eliminate obstructions sludge and check condition of drain line Pour water to ensure free flow Compressor Ω Check for high low pressure M...

Page 57: ...ATURE SETTINGS AND AMBIENT TEMPERATURE SYSTEM 1 SYSTEM 2 Supply Air Temperature C Supply Air Temperature C Return Air Temperature C Return Air Temperature C Suction Temperature C Suction Temperature C Discharge Temperature C Discharge Temperature C Condenser Coil Temperature C Condenser Coil Temperature C Ambient Temperature C INDOOR FAN SETTINGS Indoor Fan Current Amps Outdoor Fan Current Amps In...

Page 58: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...

Page 59: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...

Page 60: ...neering Pty Limited ABN 34 002767240 Registered Trade Marks of Actron Engineering Pty Limited ActronAir is constantly seeking ways to improve the design of its products therefore specifications are subject to change without notice Document 0525 067 Ver 5 Issue Date 04 2021 ...

Reviews: